Calibration
Model PTG71 / 72 - Smart Pressure Transmitter 4-1
Chapter 4 : Calibration
With the Model PTG Transmitter, no span interference will occur once its zero-
point calibration is complete. That is, only one zero-point adjustment is needed for a
complete calibration.
Note: Adjust the zero point in an area that does not require explosion-proofing.
Zero adjustment
Caution: Zero adjustment must be performed in a non-hazardous area.
Calibration procedure
1.
Connect the power supply to the Transmitter.
2. Apply the pressure corresponding to 0% output. In order to set this 0% output
to 0 kPaG, release any gas or liquid from the wetted part and leave it open to
atmospheric pressure.
3.
This product has two zero adjustment terminal pins.
Using a flat-head screwdriver, allow the two terminal pins to contact each other
simultaneously (for about one second). (For products equipped with a built-in
digital indicator, when two terminal pins contact each other the word “ZERO”
will appear on the indicator.)
4. The Step 3 above completes zero adjustment.
Test terminal
When checking the output from the Transmitter for maintenance purpose, connect an
amperemeter to the “CHK +” terminal and to “-” of the Transmitter’s “SUPPLY”
terminal.
SUPPLY
CHK
ZERO
+
+
Ð
Flat-head screwdriver
Zero adjustment terminal pin
Zero adjustment terminal
Figure 4-1 Zero adjustment
Summary of Contents for PTG71
Page 1: ...Smart Pressure Transmitter Model PTG71 72 User s Manual CM2 PTG300 2001...
Page 12: ...Preface Azbil Corporation x Model PTG71 72 Smart Pressure Transmitter...
Page 16: ...Table of Contents...
Page 20: ...Descriptions of Parts Azbil Corporation 1 4 Model PTG71 72 Smart Pressure Transmitter...
Page 36: ...Azbil Corporation 2 16 Model PTG71 72 Smart Pressure Transmitter...
Page 42: ...Calibration Azbil Corporation 4 2 Model PTG71 72 Smart Pressure Transmitter...
Page 78: ...Spare Parts Azbil Corporation 10 2 Model PTG71 72 Smart Pressure Transmitter...
Page 79: ......
Page 82: ......
Page 84: ......