Maintenance and troubleshooting of this instrument
Model: MVC10A/10F - Multivariable Air Flow Meter 5-7
In addition to the above-mentioned items, check the following items:
•
Is air flowing?
•
Is any fluid other than air flowing?
•
Is the flow direction correct?
•
Is there not any leakage in pipe joints?
•
Is there not any loosening of tightened bolts on the product side?
•
Is there not any sagging or open circuit in wiring?
•
Is there not any error in wiring connection?
•
Are the power voltage and load resistance as specified?
• Is there not any abnormality such as clogging, foreign matter, or deformation of
detector?
• Is there not any clogging or foreign matter in the connecting tube from the
detector to the converter? (In the case of MVG10F)
•
Are the pressure and temperature as specified?
•
Is there not any intense magnetic or noise generating source located nearby?
Display and output state beyond the range of flow rate measurement
When flow rate is beyond the limits of the measuring range, the displayed and the
output values are as follows:
Overload condition
Conditions when
exceeding allowable
maximum flow rate
value setting
Conditions when
exceeding the flow
rate range
Conditions
beyond JIS
standards
differential
pressure >
static pressure
×
0.25
Main display
Flashing
Flashing
Flashing
Flashing
Instantaneous flow
rate (cost) display
“HHHH” displayed
“HHHH” displayed
URL display
included
Display
% output display
“HHHH” displayed
“HHHH” displayed
Display
Display
Sub display
Instantaneous flow
rate (cost) display
“O/L” displayed
“OverFlow” displayed
Display
Display
Static pressure
display
“O/L” displayed
Display
Display
Display
Flow velocity
“O/L” displayed
“OverFlow” displayed
Display
Display
% output display
“O/L” displayed
“OverFlow” displayed
Display
Display
Display damping
Displayed in 0 second
damping
Displayed in 0 second
damping
Displayed
per damping
instruction
Displayed
per damping
instruction
4 - 20 mA output
3.8 mA maximum
20.8 mA minimum
Output up to 20.8
mA
Measured
values output
Output damping
Normal operation
Normal operation
Normal operation
Normal
operation
Pulse output
Interrupted
Interrupted
Counted up to
URL
Measured value
Totalized flow (cost)
calculation
Interrupted
Interrupted
Calculated up to
URL
Measured value
Leak check
Check the static
pressure at the start of
flow. (Specified in the
User's Manual.)
Use the measured
value
Use the measured
value
Use the
measured value
Auto ranging (peak
value)
Do not used the
measured value.
URL
Use the measured
value
Use the
measured value