31
Chapter 7. MAINTENANCE
Fig. 7-1. Points To Be Serviced For Maintenance
7-1. Periodical Inspection
(1) Check the air pipes and joints for leak.
(2) Check the air supply line drain, filter, compressor, air cleaner/drier, and tanks.
(3) Check the instrument filters and restrictions for stains. Replace the stained filters. Clean
the dirty restrictions using a needle wire of 0.12 mm diameter.
7-2. Controller Unit
(1) Turn off the air supply and remove the deviation link.
(2) Remove the four screws of the base, take out the controller unit, and clean the nozzle.
(3) Install the controller unit following the removing procedure in the reverse order. Adjust
the controller. Make sure that the O-rings are installed. Fix the controller securely with the
four screws and confirm that there is no air leak.
Summary of Contents for KFDB
Page 1: ...OM2 6220 0000 Field Mounted Indicating Controller Model KFDB KFKB KFLB User s Manual...
Page 4: ......
Page 7: ...3 Fig 1 2 Layout of Internal Components...
Page 18: ...14...
Page 27: ...23...
Page 28: ...24...
Page 38: ...32 Fig 7 2 Maintenance of Controller Unit...
Page 42: ...36 Pneumatic Circuit Diagram...
Page 43: ......
Page 46: ......
Page 48: ......