Safety Instructions 

Please read instructions carefully and use the product as specified in this manual.  Be sure to keep this manual near by for ready 
reference.  

Usage Restrictions 

This product is targeted for general air conditioning.  Do not use this product in a situation where human life may be affected.  If 
this product is used in a clean room or a place where reliability or control accuracy is particularly required, please contact Azbil 
Corporation’s sales representative.  Azbil Corporation will not bear any responsibility for the results produced by the operators.

 

 WARNING  

 

  DANGER: To prevent the risk of severe or fatal electrical shock, always disconnect power source and product 

power supply before performing any wiring. 

 

  Be sure to ground with 100 

 or lower ground resistance.  Improper grounding may cause electrical shock or

equipment damages. 

 

  Do not detach the terminal cover at any time except when wiring.  After wiring, be sure to attach the terminal cover. 

Before attaching/detaching the terminal cover, make sure that the wires are not current-carrying to prevent 
electrical shock. 

 

  Disconnect power before the product replacement to prevent electrical shock. 

 

  Wire strip length to be connected to the quick-fit screwless terminal block must be 8 mm.  If the strip length is longer 

than 8 mm, the conductor will be exposed, causing electrical shock or short circuit between adjacent terminals.  If 
it is shorter, the conductor will not contact the connector. 

 

  Do not disassemble the product.  Disassembly may result in electrical shock or equipment damage. 

 

 CAUTION 

 

  Installation and wiring must be performed by qualified personnel in accordance with all applicable safety 

standards. 

 

  This product must be operated under the operating conditions (power, temperature, humidity, vibration, shock, 

installation position, atmospheric condition, etc) specified in this manual to prevent equipment damages. 

 

  All wiring must comply with local codes of indoor wiring and electric installation rules. 

 

  Use crimp terminal lugs with insulation for electric wires connected to the screw terminals.

 

 

  Connect cables to the power source with terminals or the like for permanent connection. 

 

  Make sure all the wires are tightly connected to prevent heat generation or equipment damages. 

 

  If more than the rated power supply voltage is applied, product replacement is required for safety. 

 

  Install this product in a location out of reach of unauthorized people. (e.g. Inside of the control panel cabinet) 

 

  Lightening protection based on the regional characteristics and the building structure is needed to minimize 

equipment damages. 

 

  Noise protection is necessary when the product is installed in a location close to many noise sources. 

 

  Do not block the vent holes on the upper or lower part of the product to prevent equipment damages.  Remove 

protective sheet after installation and wiring.

 

 

  After mounting on DIN rail, make sure that the holding parts of all the connected modules are securely fixed on the 

DIN rail.  The modules may drop from the DIN rail and get damaged due to improper mounting.

 

 

  Dispose of the lithium battery in accordance with your local regulations. 

 

  Dispose of this product in accordance with your local regulations.  Do not reuse all or a part of this product. 

 
Trademark information: 
Infilex, Neopanel, PARAMATRIX and savic-net are trademarks or registered trademarks of Azbil Corporation in Japan or in other countries. 
BACnet is a registered trademark of American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). 

Summary of Contents for Infilex ZM WY5122

Page 1: ... unit Infilex ZM can perform such managements of remote units by group and is applicable to any group configuration consisting of up to 50 units of Infilex VC and Infilex FC Additionally Infilex ZM provides flexible management For example group ON OFF can be commanded even when individual measuring is commanded Risk diversification and high speed supervision Infilex ZM has 50 programs of time sche...

Page 2: ...ll applicable safety standards This product must be operated under the operating conditions power temperature humidity vibration shock installation position atmospheric condition etc specified in this manual to prevent equipment damages All wiring must comply with local codes of indoor wiring and electric installation rules Use crimp terminal lugs with insulation for electric wires connected to th...

Page 3: ...l WY5110 PMX III Model WY2001 Infilex ZM Model WY5122 Infilex FC Model WY5205 Infilex VC Model WY5206 BMIF Building Multi Air Conditioning Interface DIF DGP Data Gathering Panel Interface DIF II DGP Interface II DSS Data Storage Server MIS Management Integration Server NC bus New Controller bus PMX III PARAMATRIX III SC bus Sub Controller bus SCS System Core Server SMS System Management Server Neo...

Page 4: ...eration Red LED ON Minor failure or system restart Operation Minor failure ERR2 Red LED OFF Normal operation NC bus Transmit TX Receive RX Communication SC bus Transmit TX Receive RX LED Flashing ON OFF POWER ON OFF NC bus TX Normal Abnormal NC bus RX Normal Abnormal SC bus TX Normal Abnormal SC bus RX Normal Abnormal ERR1 Abnormal Normal LED indication Description of LED indication ERR2 Abnormal ...

Page 5: ...ng bands so as not to hide LED Data Setter connector mark switch battery holder or tag JIS Japanese Industrial Standards JCS Japanese Electric Wire and Cable Makers Association CE Marking Conformity This product must be installed in a panel cabinet Besides the product in the panel cabinet must be out of reach of unauthorized people who are not well trained for electric facilities This product comp...

Page 6: ...AB 6439 6 Dimensions Figure 3 Dimensions mm 140 60 90 8mm Stripping Length BATT S S NC bus NC bus CN1 O 3 2 1 POWER I SC bus ERR1 ERR2 S1 H MMI RX Tx RX Tx 6 5 7 8 9 10 SC bus E 4 12 11 ...

Page 7: ...At this time hold the male connector with the mark facing left and insert it as the mark points to the mark on the Infilex ZM main unit 2 Connection of Data Setter Model QY7211A Convert the D SUB connector to the mini DIN connector with the conversion cable Part No 83104995 001 At this time hold the male connector with the mark facing left and insert it as the mark points to the mark on the Infile...

Page 8: ...hows the maintenance clearance Figure 6 Mounting dimensions DIN rail mounting mm Direct screw mounting When Infilex ZM is mounted with screws the screw tab Part No 83165861 001 is required Mount and fix Infilex ZM on the wall with two M4 8 screws Lengthwise mounting Incorrect mounting Crosswise 2 face up Notes 1 Hatched are shows the maintenance space 2 Do not mount Infilex ZM in crosswise face up...

Page 9: ...he cables connected to Infilex ZM so as not to hide the parts shown in Fig 8 Make sure there is no slack in the wires from the cable ducts to Infilex ZM Figure 8 Connected wires in position System indication label for the controller number The indication tag has the system indication label on its back Turn it over and fill in the controller number on the label Figure 9 System indication label Prot...

Page 10: ...n use in ON state If the product has never or hardly been operated in OFF state for a year replace the lithium battery before the product operation Battery replacement Replace the battery with the Infilex ZM in ON state Figure 11 Battery replacement 1 Pull out the battery holder using a slotted screwdriver 2 Disconnect the connector and detach the lithium battery from the battery holder 3 Place a ...

Page 11: ...e correctly connected Several tens of seconds are required for the product normal operation after the power is turned on During this time the red LED ERR1 major failure on the front lights up indicating major failure temporarily but this does not indicate an error Do not connect wires to vacant terminals Leave at least 35 mm clearance between the top bottom surfaces of the product and other device...

Page 12: ...AB 6439 Specifications are subject to change without notice Building Systems Company http www azbil com Rev 8 0 Sep 2015 AB 6439 H W03 J AI 6439 Rev 4 2 Printed in Japan 12 ...