3
System Configurations
Infilex GC integrated into BMS: savic-net
™
FX
Figure 1. System configuration example of BMS-integrated Infilex GC
Notes:
∗
MIS may be used instead of SMS and DSS for your system. Note that MIS cannot be mixed with SMS or DSS in the same system.
∗
On 1 channel of LC-bus (2 lines for 1 channel), max. 50 remote units (also called ‘controllers’) can be connected. For Infilex ZM, however,
max. 10 units can be connected on LC-bus (5 units per 1 line, 2 lines for 1 channel).
∗
Max. wiring length of LC-bus (2 lines for 1 channel) is 900 m.
∗
On LS-bus, max. 50 remote units (also called ‘sub-controllers’) can be connected.
∗
Max. wiring length of LS-bus is 900 m.
Standalone Infilex GC
LonTalk
®
protocol
LS-bus (LonTalk
®
protocol)
Neopanel
™
Neoplate
(Digital user terminal) (Analog
user terminal)
Figure 2. System configuration example of standalone Infilex GC
Notes:
∗
On LS-bus, max. 50 controllers can be connected.
∗
Max. wiring length of LS-bus is 900 m.
Infilex
™
AC
Model WY5317C
Infilex
™
GC
Model WY5311
Infilex
™
ZM
Model WY5322
Infilex
™
VC
Model WY5306
Infilex
™
FC
Model WY5305
Infilex
™
VC
Model WY5306
Infilex
™
GC
Model WY5311
Infilex
™
AC
Model WY5317C
Infilex
™
GD
Model WY5310
PMX-III*
3
Model WY7400
Infilex
™
ZM
Model WY5322
Infilex
™
FC
Model WY5305
Infilex
™
VC
Model WY5306
DSS: Data Storage
MIS: Management Integration Server
PMX-III: PARAMATRIX
™
-III
SCS: System Core Server
SMS: System Management Server
BACnet
®
IP
(with Web browser)
LC-bus (LonTalk
®
protocol)
LS-bus (LonTalk
®
protocol)
Neopanel
™
(Digital user terminal)
Temperature
sensor
Neopanel
™
Model QY7205
(Digital user terminal)
Neoplate
Model QY7290
(Analog user terminal)
Infilex
™
SC
Model WY5307
Neopanel
™
(Digital user terminal)
Client PC
SMS
DSS
MIS
SCS