AB-7258
8
Installation steps: Neostat directly on a wall (for new installation)
1) Mount the outlet box cover (conforming to JIS C8340:1999 Boxes and box covers for rigid metal conduits (mounting
dimension: 66.7 mm)) so that the two mounting holes are vertically aligned.
2) Remove the cover from Neostat. (See the
Cover removal
section.)
3) Unscrew the Neostat main unit screw. Then, hold and lift the guide to remove the main unit from the base.
Do not hold the setting dial to remove the main unit.
4) Attach the Neostat base to the outlet box cover so that the arrow (indicated with "UP") points upwards, using two pan-head
machine screws (M4 x 10) supplied with Neostat. (Tightening torque: 78.5 Nꞏcm)
5) Wire Neostat. (See the
Wiring
section.)
6) Attach the Neostat main unit to the base, using the main unit screw (M3) preassembled with the Neostat main unit.
(Tightening torque: 39.2 N cm)
7) Attach the Neostat cover to the main unit. (See the
Cover removal
section.)
Figure 4. Installation: Neostat directly on a wall (for new installation)
66.7 mm
Base of Neostat
2 pan-head machine screws (M4 x 10)
of Neostat
Main unit screw (M3)
preassembled with the main unit
Main unit of Neostat
Cover of Neostat
Outlet box cover (JIS C8340
with 66.7 mm mounting dimension,
commercially available)