Azbil HTY7903T Specifications & Instructions Download Page 8

AB-5963 

O-ring 

Attachment 

Conduit fixing screws 

Conduit nut 
Conduit connector 
(DN 25) 
 
 Straight box connector 
 (DN 24 - DN 25) 

a. Pull.

b. Seal the wiring port.

 Conduit 

connection 

Prepare the appropriate conduit set (with separate order 
required), depending on the quantity of core cables.  
Temporarily screw the conduit connector and the 
attachment, and select an O-ring appropriate for the 
cable. 

 

 

 

 

 

 

Figure 13.  Conduit connection (1/2) 

 

Lead the cable in, as shown in Fig. 14.  Pull up the cable 
(‘a’ in Fig. 14) and screw the attachment onto the wiring 
port.  Tighten the conduit nut on the conduit at a position 
where the conduit set screw can be tightened easily.  
Then, seal the wiring port (‘b’ in Fig. 14). 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Figure 14.  Conduit connection (2/2) 

 

3)  Connect the cables to the terminals. 

Connect the core cables to the terminals, and attach the 
front cover. 

 

 

 

 

 

 

 

Figure 15.  Attaching the front cover 

 

Then, tighten the seal connector (for seal connector 
connection). 

 

 

 

 

 

 

 

 

Figure 16.  Tightening the seal connector 

 

 

 

 

 

 

 

 

Figure 17.  Connection of 7- and 4-core cables to terminals 

 

  CAUTION 

  Make sure all the wires are tightly connected to 

prevent heat generation or equipment 
malfunction.  Insufficient tightening of the screw 
terminals also can cause inaccurate 
measurement. 

  Leave vacant terminals unconnected to prevent 

product damage. 

 

IMPORTANT: 
  Do not remove the terminal cover except when 

connecting or disconnecting the wires.  When 
removing the terminal cover, make sure that the 
wires are not electrified before connecting/ 
disconnecting wires.  After the connection/ 
disconnection, be sure to attach the terminal cover 
again. 

 

4)  After completing wiring, be sure to attach the front cover. 

Attachment Conduit 

nut 

Conduit connector 
(DN 25) 

Tighten. 

Models 
HTY7903T1P00 
HTY7903T4P00 
HTY7903T6P00 
HTY7913T1P00 
HTY7913T4P00 
HTY7913T6P00 
(7-core cable) 

Models 
HY7903T1000
HY7903T4000
HY7903T6000
HY7913T1000
HY7913T4000
HY7913T6000
(4-core cable)

24 V

 AC

 

24 V

 D

C

 

1-

5 V D

C

 

0-

10 V

 D

C

 

4-

20 m

A

 

Pt 100 

(+)

(-)

+

-

A

B

B

Power 

supply 

Dewpoi

nt 

temperat

ure 

Tempera

ture 

1

2

3

4

5

6

7

Summary of Contents for HTY7903T

Page 1: ...t is suitable for various applications such as a duct or chamber for building air conditioning and outdoor air measurement as well as industrial applications Model HY79X3 series for dewpoint temperatu...

Page 2: ...is necessary to minimize lightning damages to the product Always disconnect power source before performing any wiring to prevent equipment damages Use crimp terminal lugs with insulation for electric...

Page 3: ...Model number Description Insertion length HTY7903T1P00 Dewpoint temperature 1 5 V temperature Pt100 Long HTY7903T4P00 Dewpoint temperature 4 20 mA temperature Pt100 Long HTY7903T6P00 Dewpoint tempera...

Page 4: ...0 Power consumption Models HTY79X3T1 HY79X3T1 series with 1 5 V output Models HTY79X3T4 HY79X3T4 series with 4 20 mA output Models HTY79X3T6 HY79X3T6 series with 0 10 V output 0 7 VA for 24 V AC 600 m...

Page 5: ...ls HTY7903 HY7903 series Models HTY7913 HY7913 series Mounting bracket Part No 83157235 001 Figure 1 Dimensions mm 70 247 6 A A 51 3 45 6 67 3 113 5 110 20 70 108 6 51 3 45 6 67 3 113 5 110 20 30 25 5...

Page 6: ...t Figure 2 Indicator label on the duct 2 Fix the mounting bracket onto the duct with M4 screws supplied with the bracket inserting packing between the duct and the bracket The side with longer protrud...

Page 7: ...nel with the mounting bracket 4 Completely insert the probe into the panel Then fix the probe and the bracket by turning the stopper 45 degrees from b to a shown in Fig 10 to lock Figure 10 Fixing the...

Page 8: ...seal connector connection Figure 16 Tightening the seal connector Figure 17 Connection of 7 and 4 core cables to terminals CAUTION Make sure all the wires are tightly connected to prevent heat generat...

Page 9: ...19 Correct wiring separate 24 V AC transformers 24 V DC Transformer shared with two sensors Fig 20 shows wiring example of Model HY78X3T For connecting terminals and E 3 and 2 use power with 0 022 F...

Page 10: ...oint single point calibration Replace the sensor Filter replacement CAUTION Installation must be performed by qualified personnel in accordance with all applicable safety standards IMPORTANT Be sure n...

Page 11: ...le measuring instrument for single point calibration with correct procedure in appropriate environment Calibrated digital multimeter is recommended to check output Figure 26 Single point calibration M...

Page 12: ...AB 5963 Specifications are subject to change without notice Building Systems Company http www azbil com Rev 6 0 Sep 2015 AB 5963 J AI 5963 Rev 5 2 Printed in Japan 12...

Reviews: