Azbil HTY7903T Specifications & Instructions Download Page 4

AB-5963 

Specifications 

Item Specification 

Temperature -20 

°

C to 60 

°

Measurement range 

Dewpoint temperature  -40 

°

C to 60 

°

C DP (-20 

°

C to 60 

°

C) (non-condensing) 

Temperature 100 

Ω

 / 0 

°

C  

Models HTY79X3T1, HY79X3T1 series: 
1 V DC to 5 V DC (linear to -40 

°

C to 60 

°

C DP)  

(Input impedance of the controller connected: 10 k

Ω

 or higher) 

Models HTY79X3T4, HY79X3T4 series: 
4 mA DC to 20 mA DC (linear to -40 

°

C to 60 

°

C DP)  

(Maximum allowable load: 300 

Ω

 or lower) 

Output signal 

Dewpoint temperature 

Models HTY79X3T6, HY79X3T6 series: 
0 V DC to10 V DC (linear to -40 

°

C to 60 

°

C DP)  

(Input impedance of the controller connected: 10 k

Ω

 or higher) 

Temperature 

±

0.3 

°

C (at -20 

°

C to 60 

°

C) (Pt100 element) 

Sensing accuracy 

Dewpoint temperature 

±

°

C DP (at 30 %RH to 90 %RH, 25 

°

C) 

±

2.5 

°

C DP (at 30 %RH to 90 %RH, -5 

°

C to 60 

°

C) 

Temperature 

4 min. or less 

Time constant 
(at 2 m/s air velocity) 

Dewpoint temperature  1 min. or less (at constant temperature) 
 

 

Rated/extreme operating conditions Transport/storage 

conditions 

Temperature 
range 

-20 

°

C to 60 

°

C -30 

°

C to 70 

°

Temperature 
measuring 

Humidity 
range 

0 %RH to 100 %RH  
(non-condensing) 

5 %RH to 95 %RH 
(non-condensing) 

Temperature 
range 

-20 

°

C to 60 

°

C -30 

°

C to 70 

°

Environmental 
conditions 
 

Dewpoint temperature 
measuring 

Humidity 
range 

Rated: 10 %RH to 100 %RH 
Extreme: 0 %RH to 100 %RH 
(non-condensing) 

5 %RH to 95 %RH 
(non-condensing) 

 Vibration 

 

4.9 

m/s

2

 (10 Hz to 150 Hz) 

9.8 m/s

2

 (10 Hz to 150 Hz) 

(in packaged form) 

 

Air velocity 

 

Extreme: 0 m/s to 15 m/s 

 

Power supply voltage  24 V AC +10/-15 % (50 Hz/60 Hz), 24 V DC 

±

10 % 

Power consumption 

Models HTY79X3T1, HY79X3T1 series with 1-5 V output:  
Models HTY79X3T4, HY79X3T4 series with 4-20 mA output:  
Models HTY79X3T6, HY79X3T6 series with 0-10 V output:

0.7 VA for 24 V AC / 600 mW for 24 V DC 
1.4 VA for 24 V AC / 1200 mW for 24 V DC 
0.7 VA for 24 V AC / 600 mW for 24 V DC 

Withstand voltage 

1 mA or less leakage current at 500 V AC for 1 minute (between the housing and terminals) 

Insulation resistance 

500 V DC, 20 M

Ω

 or higher (between the housing and terminals) 

Enclosure rating 

Housing: IP54 (dust-proof and splash-proof with specified water-proof gland and multi-core cables used or with 
specified conduit connected.) 

Installation 

Duct, chamber, thermometer shelter (with dedicated bracket) 

Connection 

 

Terminal block connection 

Material, color 

Housing: 20 % GF containing polycarbonate resin, gray 
Filter cap: Modified PPE resin, gray 

Weight 

Models HTY7903, HY7903 series: Approx. 250 g  
Models HTY7913, HY7913 series: Approx. 220 g 

Accessories None 
Parts (separate order 
required) 

Part No. 83157235-001:  
Part No. 83157240-004:  
Part No. 83104098-004: 
Part No. DY8000A1001:  
Part No. DY3002A1005:  

Mounting bracket (packing, indicator label for installation holes, M4 screws) 
Conduit mounting set (cable with 

φ

11 mm to 

φ

14 mm outer diameter is applicable.) 

Seal connector (cable with 

φ

10.5 mm to 

φ

14.5 mm outer diameter is applicable.) 

Sensor shield for outdoor 
Mounting bracket for thermometer shelter (L-type bracket) 

Replacement part 
(separate order 
required)  

Part No. 83162945-003: Filter set (filter, filter cap) 

 
CE Marking Conformity  

This product complies with the following Electromagnetic Compatibility (EMC). 

EMC :  EN61326-1 

Class B, Table 1 (For use in a basic electromagnetic environment)  

Summary of Contents for HTY7903T

Page 1: ...t is suitable for various applications such as a duct or chamber for building air conditioning and outdoor air measurement as well as industrial applications Model HY79X3 series for dewpoint temperatu...

Page 2: ...is necessary to minimize lightning damages to the product Always disconnect power source before performing any wiring to prevent equipment damages Use crimp terminal lugs with insulation for electric...

Page 3: ...Model number Description Insertion length HTY7903T1P00 Dewpoint temperature 1 5 V temperature Pt100 Long HTY7903T4P00 Dewpoint temperature 4 20 mA temperature Pt100 Long HTY7903T6P00 Dewpoint tempera...

Page 4: ...0 Power consumption Models HTY79X3T1 HY79X3T1 series with 1 5 V output Models HTY79X3T4 HY79X3T4 series with 4 20 mA output Models HTY79X3T6 HY79X3T6 series with 0 10 V output 0 7 VA for 24 V AC 600 m...

Page 5: ...ls HTY7903 HY7903 series Models HTY7913 HY7913 series Mounting bracket Part No 83157235 001 Figure 1 Dimensions mm 70 247 6 A A 51 3 45 6 67 3 113 5 110 20 70 108 6 51 3 45 6 67 3 113 5 110 20 30 25 5...

Page 6: ...t Figure 2 Indicator label on the duct 2 Fix the mounting bracket onto the duct with M4 screws supplied with the bracket inserting packing between the duct and the bracket The side with longer protrud...

Page 7: ...nel with the mounting bracket 4 Completely insert the probe into the panel Then fix the probe and the bracket by turning the stopper 45 degrees from b to a shown in Fig 10 to lock Figure 10 Fixing the...

Page 8: ...seal connector connection Figure 16 Tightening the seal connector Figure 17 Connection of 7 and 4 core cables to terminals CAUTION Make sure all the wires are tightly connected to prevent heat generat...

Page 9: ...19 Correct wiring separate 24 V AC transformers 24 V DC Transformer shared with two sensors Fig 20 shows wiring example of Model HY78X3T For connecting terminals and E 3 and 2 use power with 0 022 F...

Page 10: ...oint single point calibration Replace the sensor Filter replacement CAUTION Installation must be performed by qualified personnel in accordance with all applicable safety standards IMPORTANT Be sure n...

Page 11: ...le measuring instrument for single point calibration with correct procedure in appropriate environment Calibrated digital multimeter is recommended to check output Figure 26 Single point calibration M...

Page 12: ...AB 5963 Specifications are subject to change without notice Building Systems Company http www azbil com Rev 6 0 Sep 2015 AB 5963 J AI 5963 Rev 5 2 Printed in Japan 12...

Reviews: