39
Chapter 7. Specifications
Item
Description
General
specifications
Protective
structure
IP40: if sideboards (81447515-001) are attached to the sub-base (model BC-R05)
IP10: (sub-base (model BC-R05) only)
Overvoltage
category
II
Pollution degree
PD2
Automatic action Type 2.A.V
Software
Class C
Case color
Black
Case material
Denatured PPE resin (UL 94-V0 PTI materials group IIIa)
General
specifications
Structure
Sub-base and main unit
Mounting
orientation
Vertical or horizontal
For horizontal mounting, the 7-segment display must face upward (DIN rail mounting or
direct mounting through screw holes in base)
Standards
compliance
JIS C 9730-2-5:2010 (Automatic Electrical Controls for Household and Similar Use - Part
2-5: Particular Requirements for Automatic Electrical Burner Control Systems)
JIS C 9730-1:2010 (Automatic Electrical Controls for Household and Similar Use - Part 1:
General Requirements)
Dimensions
W95 × H105 × D110 mm (incl. sub-base)
Weight
Approximately 600 g (incl. sub-base)
Wiring types and max.
wiring length
•
Start
Copper 600 V PVC-insulated cable (IEC 60227-3), 1.25 mm
2
,
recommended length: 20 m or less, max. wiring length: 100 m
•
Contact reset
Copper 600 V PVC-insulated cable (IEC 60227-3), 1.25 mm
2
,
recommended length: 20 m or less, max. wiring length: 100 m
•
AUD300C/500C (F, G, S1, S2)
Copper 600 V PVC-insulated cable (IEC 60227-3), 1.25 mm
2
, max. wiring length: 200 m
•
Flame rod (F, G)
RG-11U (JAN standard: US DoD compliant specification) or the equivalent, 5C2V,
7C2V (JIS standard)
Recommended length: 20 m or less, max. wiring length: 30 m
•
RS-485 communications (3-wire system)
0.2–1.5 mm
2
shielded, twisted pair cable (recommended), max.
wiring length: 500 m
•
Flame voltage output signal
Copper 600 V PVC-insulated cable (IEC 60227-3), 0.75 mm
2
min.,
max. wiring length: 10 m
•
Event output
JIS C 3306: 0.75 mm
2
min.
•
Flame relay N.C. output
Copper 600 V PVC-insulated cable (IEC 60227-3), 1.25 mm
2
•
Flame output (with start check)
Copper 600 V PVC-insulated cable (IEC 60227-3), 1.25 mm
2
•
Flame output
Copper 600 V PVC-insulated cable (IEC 60227-3), 1.25 mm
2
*
Contact reset input (terminal 24) (p. 18) (for details on the contact reset input specifications)
Summary of Contents for AUR355
Page 10: ......
Page 52: ......
Page 53: ...Revision History CP SP 1454E Date Edn New Page No Description June 2021 1 ...