AB-6209-U 

Safety Instructions 

Please read instructions carefully and use the product as specified in this manual. Be sure to keep this manual nearby for quick 
reference.  

Usage Restrictions 

This product is targeted for general air conditioning. Do not use this product in a situation where human life might be affected.
Also, do not install this product in an atmosphere containing explosive gas or flammable gas. 
If this product is used in a clean room or a place where particularly high reliability or control accuracy is required, please contact
our sales representative. Azbil Corporation will not bear any responsibility for the results produced by the operators. 

 

Warnings and Cautions 

 WARNING

 

Alerts users that improper handling may cause death or serious injury. 

 CAUTION

 

Alerts users that improper handling may cause minor injury or material loss. 

 

Signs 

 

Alerts users possible hazardous conditions caused by erroneous operation or erroneous use. The symbol inside I 
indicates the specific type of danger.  
(For example, the sign on the left warns of the risk of electric shock.) 

 

Notifies users that specific actions are prohibited to prevent possible danger. The symbol inside Q graphically 
indicates the prohibited action.  
(For example, the sign on the left notifies that disassembly is prohibited.)  

 

Instructs users to carry out a specific obligatory action to prevent possible danger. The symbol inside d graphically 
indicates the actual action to be carried out.  
(For example, the sign on the left indicates general instructions.) 

 

 CAUTION 

 

Install and use this product under the operating conditions (for temperature, humidity, power, vibration, shock,
mounting direction, atmosphere, etc.) listed in the specifications. Failure to do so might cause fire or device failure. 

 

Use the product within its lifespan and avoid instrumentations that keep the product to operate excessively. 
Continued use beyond the lifespan might cause fire or device failure. 

 

Keep the products in package for storage. Failure to do so might damage or stain the products. 

 

Installation and wiring must be performed by qualified personnel in accordance with all applicable safety standards.

 

For installation, do not mount the valve in an improper position or overtighten the threaded connections. 
Doing so might damage the product. 

 

After installation, make sure no fluid leaks from the valve-pipe connections.  
Incorrect installation might cause fluid leakage. 

 

Install the product so that no foreign objects remains inside the pipes. Be sure to provide a strainer on the inflow side
of the piping. Flush the piping to remove the foreign objects after installation. Foreign objects inside the piping might
damage the product. 

 

Do not excessively screw a pipe into the valve. Doing so might damage or deform the inside of the valve causing 
leakage and malfunction. 

 

Do not allow the fluid to freeze. Doing so might damage the valve body and cause fluid leakage. 

 

Do not install the product nearby a steam coil, pressurized hot-water coil, or any high heat source. High temperature 
radiation might cause malfunction of its actuator. 

 

Do not use the product in an atmosphere corrosive to the actuator, valve, and their components. Doing so might
damage the product. 

 

Do not disassemble the product. Doing so might cause device failure. 

 

Do not carelessly touch this product when being used to control hot water. The product temperature is hot, and you 
might get burned. 

 

Dispose of the product as industrial waste in accordance with your local regulations. Do not reuse all or part of this 
product. 

Summary of Contents for ACTIVAL VY5303B Series

Page 1: ...e can be installed in a restricted space such as inside of compact AHU Bronze valve body applicable to 230 psig Easy assembly with Model MY53X0A actuator using no tool and no adjustment required Linea...

Page 2: ...mosphere etc listed in the specifications Failure to do so might cause fire or device failure Use the product within its lifespan and avoid instrumentations that keep the product to operate excessivel...

Page 3: ...inal size Cv Close off rating Inch DN VY5303B0021 3 4 20 4 0 72 psig VY5303B0022 3 4 20 6 3 72 psig VY5303B0023 1 25 10 72 psig VY5303B0031 1 1 4 32 16 43 psig VY5303B 041 1 1 2 40 25 43 psig Mounting...

Page 4: ...he inflow side of each valve install it on the pipe diverting sections sections diverting from main piping system to sub piping system Install the valve so that the flow direction of process fluid agr...

Page 5: ...ces Fully open in 100 position the ACTIVAL to flush Factory preset position Port A 100 Flow direction Figure 6 Flow direction Identification of the ports A and B Valve body without heat insulation mat...

Page 6: ...the actuator onto the valve Mounting procedure 1 Manually turn the indicator manual lever of the actuator to 100 with the lever release button pressed Figure 10 Indicator manual lever at 100 fully ope...

Page 7: ...e Mixing application Figure 15 Application example Mixing valve Mounting Examples Diverting application Upright 90 tilted Figure 16 Mounting examples Diverting valve Mixing application Upright 90 tilt...

Page 8: ...operate smoothly valve stops halfway valve does not operate at all Conditions of the power applied and of the input signal applied to the actuator Wiring condition disconnected wires of the actuator F...

Reviews: