AB-6880
19
Address Setting (Addressing)
To SAnet interface module, Model FVY5160J and other Intelligent Component Series devices are connected via SAnet. Set
address for the terminal devices so that the SAnet interface module can recognize all the terminal devices connected. Follow the
procedure below to set the address. For details regarding address setting (addressing), ask our salesperson/serviceperson.
1) Unscrew the 3 setscrews and remove the terminal cover. See Fig. 10 for removing the terminal cover.
2) Set address. (See Table 1.) Address can be set with rotary switch, with service pin switch, or based on SAnet ID. Rotary
switch and service pin switch are provided on this product. To set the address with service pin switch or based on SAnet ID,
Azbil Corporation’s engineering tool (Data Setter or PC-MMI) is required. Set the address in either way according to your
availability.
Setting with rotary switch:
Turn the rotary switch using a precision Phillips screwdriver and set.
Setting with service pin switch:
1. Set the rotary switch to ‘0’.
2. Start addressing operation* of Data Setter or PC-MMI. Then,
press the service pin switch. (Do not keep the switch pressed for
longer than 5 seconds.)
3. Address will be set within 5 seconds after pressing the service
pin switch.
∗
For the addressing operation of Data Setter or PC-MMI, ask our
salesperson/serviceperson.
Setting based on SAnet ID:
1. Set the rotary switch to ‘0’.
2. With Data Setter or PC-MMI, enter the SAnet ID (on the product
code label) and address number to set. The product code label is
attached on the rear side surface of the actuator, as shown in
Fig. 16.
∗
For the addressing operation of Data Setter or PC-MMI, ask our
salesperson/serviceperson.
3) Attach the terminal cover after setting the address.
IMPORTANT:
•
While the terminal cover is removed, do not touch the terminal block or allow anything to touch the terminal
block.
•
If the service pin switch is kept pressed for longer than 5 seconds, the mode will be switched and operation
error (data point trouble) will be occurred. In such a case, press the service pin switch again and keep it
pressed for longer than 10 seconds to go back to the normal mode.
SAnet ID
Figure 16. SAnet ID on the product code label
Service pin switch
Figure 15. Setting switches
(without terminal cover)
Rotary switch