Address Setting (Addressing) 

To SAnet interface module, Model FVY5160J and other Intelligent Component Series devices are connected via SAnet. Set 
address for the terminal devices so that the SAnet interface module can recognize all the terminal devices connected. Follow the 
procedure below to set the address. For details regarding address setting (addressing), ask our salesperson/serviceperson. 

1)  Unscrew the 3 setscrews and remove the terminal cover. See Fig. 10 for removing the terminal cover. 

 

2)  Set address. (See Table 1.)  Address can be set with rotary switch, with service pin switch, or based on SAnet ID. Rotary 

switch and service pin switch are provided on this product. To set the address with service pin switch or based on SAnet ID, 
Azbil Corporation’s engineering tool (Data Setter or PC-MMI) is required. Set the address in either way according to your 
availability.  

 

Setting with rotary switch: 
Turn the rotary switch using a precision Phillips screwdriver and set. 

 

Setting with service pin switch: 
1.  Set the rotary switch to ‘0’. 
2.  Start addressing operation* of Data Setter or PC-MMI. Then, 

press the service pin switch. (Do not keep the switch pressed for 
longer than 5 seconds.) 

3.  Address will be set within 5 seconds after pressing the service

pin switch.  

  For the addressing operation of Data Setter or PC-MMI, ask our 

salesperson/serviceperson. 

 

Setting based on SAnet ID: 
1.  Set the rotary switch to ‘0’. 
2.  With Data Setter or PC-MMI, enter the SAnet ID (on the product

code label) and address number to set. The product code label is 
attached on the rear side surface of the actuator, as shown in
Fig. 16. 

  For the addressing operation of Data Setter or PC-MMI, ask our 

salesperson/serviceperson. 

 

3)  Attach the terminal cover after setting the address. 

 
 
 
 
 
 
 
 
 
 

IMPORTANT: 

  While the terminal cover is removed, do not touch the terminal block or allow anything to touch the terminal 

block. 

  If the service pin switch is kept pressed for longer than 5 seconds, the mode will be switched and operation 

error (data point trouble) will be occurred. In such a case, press the service pin switch again and keep it 
pressed for longer than 10 seconds to go back to the normal mode. 

 

 

SAnet ID

Figure 16.  SAnet ID on the product code label 

Service pin switch 

Figure 15.  Setting switches 

(without terminal cover) 

Rotary switch 

Summary of Contents for ACTIVAL FVY5160J0011

Page 1: ...ion Model FVY5160J communicates with a controller via SAnet Flow rate signal or position control signal is input from the controller and flow rate pressure temperature measuring signal and position si...

Page 2: ...e product with a vehicle or enough manpower in an appropriate manner Careless lift or accidental drop of the product might cause injury or product damage Before wiring be sure to turn off the power to...

Page 3: ...Firmly tighten the terminal screws Insufficient tightening of the terminal screws might cause overheating or fire Be sure to provide a circuit breaker for the power to the product as the product does...

Page 4: ...odel VY516_J or Single Model MY804_A requires one SAnet address Figure 1 System configuration example SAnet connection in our BMS Building Management System BMS Infilex AC Model WY5117C Infilex GC Mod...

Page 5: ...ed Specifications For weight refer to the table shown in the section Dimensions Valve and actuator as a single unit specifications Item Specification Environmental conditions Rated operating condition...

Page 6: ...0J0061 DN65 2 1 2 95 1 0 MPa Size Cv Close off rating FVY5160J0081 DN80 3 125 1 0 MPa Applicable fluid Chilled hot water Allowable fluid temperature 0 C to 80 C Non freezing Frozen process fluid aroun...

Page 7: ...ion distance varies depending on the number of devices and the type of devices to be connected to For details regarding the transmission distance refer to Installation Manual of Intelligent Component...

Page 8: ...suring Accuracy 1 C factory preset 8 Notes 1 Pv is differential pressure between valve inlet pressure Pvin and outlet pressure Pvout 2 Flow rate measuring accuracy above may change depending on the co...

Page 9: ...m Seal connector for the cable gland Part No 83104346 014 Applicable wire size 9 mm to 11 mm Seal connector for the cable gland is necessary for IEC IP54 protection Cable gland with three ports Part N...

Page 10: ...27 60 18 90 125 19 4 6 6 FVY5160J004X 40 241 103 165 82 5 20 105 140 19 4 10 0 FVY5160J0051 50 245 107 178 89 20 120 155 19 4 11 5 FVY5160J0061 65 262 124 190 90 22 140 175 19 4 16 0 FVY5160J0081 80 2...

Page 11: ...ector for the Pipe sensor Service pin switch Port for the Pipe sensor cable Operation status LED 1 Flow rate status LEDs 4 Connector for Display Panel Terminal block Ground terminal Port for Display P...

Page 12: ...es during installation Flush the piping to remove the foreign objects after installation Foreign objects inside the piping might damage the product Install the valve to the pipe so that they are elect...

Page 13: ...e the actuator in water Although Model FVY5160J can be used outdoors be sure not to expose Model FVY5160J to direct sunlight Provide the outdoor cover optional to install outdoors Install Model FVY516...

Page 14: ...hed to the yoke Install a bypass pipe and gate valves on the inflow outflow and bypass sides Also install a strainer with 40 or more meshes on the inflow side Before activating Model FVY5160J fully op...

Page 15: ...ally open close valve do not turn the joint beyond the fully open 100 closed 0 mark To manually open close the valve slowly turn the joint If shock is sent to the actuator the actuator may get damaged...

Page 16: ...tage e g 100 V AC 200 V AC to Model FVY5160J To prevent damage cover the terminals except when connecting disconnecting wires Do not leave any refuse including metal chips inside the actuator after cu...

Page 17: ...ual of Intelligent Component Series for SAnet Communication AB 6713 To keep IP54 protection dust proof and splash proof Use a water proof connector for Model FVY5160J in a high humidity environment or...

Page 18: ...ing wire colors of the Display Panel are also described in the Specifications Instructions of Display Panel AB 6922 If you use a different cable be sure to match the terminal numbers to connect the wi...

Page 19: ...t addressing operation of Data Setter or PC MMI Then press the service pin switch Do not keep the switch pressed for longer than 5 seconds 3 Address will be set within 5 seconds after pressing the ser...

Page 20: ...a clean location with no dust oil or moisture Attach the system indication label by pressing the whole surface of the label to stick on the product surface Operation Check in Manual Operation Mode In...

Page 21: ...F Manual operation Repetition of 0 25 second ON 0 25 second OFF 0 25 second ON 1 25 second OFF Error during manual operation Repetition of 0 25 second ON 0 25 second OFF 0 25 second ON 0 25 second OFF...

Page 22: ...onding actions shown in the table If your problem is not solved by the corresponding action please contact Azbil Corporation near you Table 3 Inspection items and details Inspection item Inspection in...

Page 23: ...brates or produces an abnormal noise Insufficient air vent inside piping Primary Pvin pressure condition Differential pressure Pvin Pvout condition Take air out of piping Adjust the mounting position...

Page 24: ...n other countries KPEV is a registered trademark of Furukawa Electric Co Ltd Specifications are subject to change without notice Building Systems Company 1 12 2 Kawana Fujisawa Kanagawa 251 8522 JAPAN...

Reviews: