Installation 

Precautions for installation 

 

CAUTION 

 

  Installation and wiring must be performed by qualified personnel in accordance with all applicable safety 

standards. 

 

  Install the product in the proper position as specified in this manual.   

Excessively tight connection to a pipe or improper installation position might damage the product. 

 

  Use full gaskets for the flat face flanges. 

Failure to do so might damage the valve or cause fluid leakage. 

 

  When installing the product with flange gasket, do not allow the flange gasket to go inside the pipe.   

Doing so might cause incorrect measurement and control of flow. 

 

  Do not use rubber gaskets.  

Doing so might cause incorrect measurement and control of flow. 

 

  After installation, make sure no fluid leaks from the valve-pipe connections. 

Incorrect installation might cause fluid leakage. 

 

  Do not allow any foreign objects inside the pipes during installation. Flush the piping to remove the foreign objects 

after installation. 
Foreign objects inside the piping might damage the product. 

 

  Install the valve to the pipe so that they are electrically connected at the same potential. If the valve and the pipe 

are electrically isolated, noise will be generated, causing incorrect measurement and control of flow. 

 

IMPORTANT: 
 

Model FVY5160J requires straight pipe runs (valve diameter 

×

2 long) on the inlet and outlet sides for accurate 

flow measuring. 

 

 

Model FVY5160J is the valve and actuator integrated into a single unit. Do not combine the valve with any other actuator, or 
do not combine the actuator with any other valve. 

 

To remove foreign objects inside the pipes, install a strainer with 40 or more meshes on the inflow side of each valve. If the 
strainers cannot be installed on the inflow side of each valve, install it on the pipe diverting sections (sections diverting from 
main piping system to sub piping system). 

 

Install the valve so that the flow direction of process fluid agrees with the arrow indicated on the valve body. 

 

Summary of Contents for ACTIVAL FVY5160J0011

Page 1: ...ion Model FVY5160J communicates with a controller via SAnet Flow rate signal or position control signal is input from the controller and flow rate pressure temperature measuring signal and position si...

Page 2: ...e product with a vehicle or enough manpower in an appropriate manner Careless lift or accidental drop of the product might cause injury or product damage Before wiring be sure to turn off the power to...

Page 3: ...Firmly tighten the terminal screws Insufficient tightening of the terminal screws might cause overheating or fire Be sure to provide a circuit breaker for the power to the product as the product does...

Page 4: ...odel VY516_J or Single Model MY804_A requires one SAnet address Figure 1 System configuration example SAnet connection in our BMS Building Management System BMS Infilex AC Model WY5117C Infilex GC Mod...

Page 5: ...ed Specifications For weight refer to the table shown in the section Dimensions Valve and actuator as a single unit specifications Item Specification Environmental conditions Rated operating condition...

Page 6: ...0J0061 DN65 2 1 2 95 1 0 MPa Size Cv Close off rating FVY5160J0081 DN80 3 125 1 0 MPa Applicable fluid Chilled hot water Allowable fluid temperature 0 C to 80 C Non freezing Frozen process fluid aroun...

Page 7: ...ion distance varies depending on the number of devices and the type of devices to be connected to For details regarding the transmission distance refer to Installation Manual of Intelligent Component...

Page 8: ...suring Accuracy 1 C factory preset 8 Notes 1 Pv is differential pressure between valve inlet pressure Pvin and outlet pressure Pvout 2 Flow rate measuring accuracy above may change depending on the co...

Page 9: ...m Seal connector for the cable gland Part No 83104346 014 Applicable wire size 9 mm to 11 mm Seal connector for the cable gland is necessary for IEC IP54 protection Cable gland with three ports Part N...

Page 10: ...27 60 18 90 125 19 4 6 6 FVY5160J004X 40 241 103 165 82 5 20 105 140 19 4 10 0 FVY5160J0051 50 245 107 178 89 20 120 155 19 4 11 5 FVY5160J0061 65 262 124 190 90 22 140 175 19 4 16 0 FVY5160J0081 80 2...

Page 11: ...ector for the Pipe sensor Service pin switch Port for the Pipe sensor cable Operation status LED 1 Flow rate status LEDs 4 Connector for Display Panel Terminal block Ground terminal Port for Display P...

Page 12: ...es during installation Flush the piping to remove the foreign objects after installation Foreign objects inside the piping might damage the product Install the valve to the pipe so that they are elect...

Page 13: ...e the actuator in water Although Model FVY5160J can be used outdoors be sure not to expose Model FVY5160J to direct sunlight Provide the outdoor cover optional to install outdoors Install Model FVY516...

Page 14: ...hed to the yoke Install a bypass pipe and gate valves on the inflow outflow and bypass sides Also install a strainer with 40 or more meshes on the inflow side Before activating Model FVY5160J fully op...

Page 15: ...ally open close valve do not turn the joint beyond the fully open 100 closed 0 mark To manually open close the valve slowly turn the joint If shock is sent to the actuator the actuator may get damaged...

Page 16: ...tage e g 100 V AC 200 V AC to Model FVY5160J To prevent damage cover the terminals except when connecting disconnecting wires Do not leave any refuse including metal chips inside the actuator after cu...

Page 17: ...ual of Intelligent Component Series for SAnet Communication AB 6713 To keep IP54 protection dust proof and splash proof Use a water proof connector for Model FVY5160J in a high humidity environment or...

Page 18: ...ing wire colors of the Display Panel are also described in the Specifications Instructions of Display Panel AB 6922 If you use a different cable be sure to match the terminal numbers to connect the wi...

Page 19: ...t addressing operation of Data Setter or PC MMI Then press the service pin switch Do not keep the switch pressed for longer than 5 seconds 3 Address will be set within 5 seconds after pressing the ser...

Page 20: ...a clean location with no dust oil or moisture Attach the system indication label by pressing the whole surface of the label to stick on the product surface Operation Check in Manual Operation Mode In...

Page 21: ...F Manual operation Repetition of 0 25 second ON 0 25 second OFF 0 25 second ON 1 25 second OFF Error during manual operation Repetition of 0 25 second ON 0 25 second OFF 0 25 second ON 0 25 second OFF...

Page 22: ...onding actions shown in the table If your problem is not solved by the corresponding action please contact Azbil Corporation near you Table 3 Inspection items and details Inspection item Inspection in...

Page 23: ...brates or produces an abnormal noise Insufficient air vent inside piping Primary Pvin pressure condition Differential pressure Pvin Pvout condition Take air out of piping Adjust the mounting position...

Page 24: ...n other countries KPEV is a registered trademark of Furukawa Electric Co Ltd Specifications are subject to change without notice Building Systems Company 1 12 2 Kawana Fujisawa Kanagawa 251 8522 JAPAN...

Reviews: