Azbil ACTIVAL+ FVY513E Series Specifications & Instructions Download Page 2

AB-7131 

Safety Instructions 

Please read instructions carefully and use the product as 
specified in this manual. Be sure to keep this manual 
nearby for quick reference.  

Restrictions 

This product is targeted for general air conditioning. Do not 
use this product in a situation where human life may be 
affected. If this product is used in a clean room or a place 
where reliability or control accuracy is particularly required, 
please contact our sales representative. Azbil Corporation 
will not bear any responsibility for the results produced by 
the operators. 

 

 

Warnings and Cautions 

 WARNING

 

Alerts users that improper handling 
may cause death or serious injury. 

 CAUTION

 

Alerts users that improper handling may 
cause minor injury or material loss. 

 

 

Signs 

 

Alerts users possible hazardous conditions caused 
by erroneous operation or erroneous use. The 
symbol inside 

 indicates the specific type of 

danger.  
(For example, the sign on the left warns of the risk of 
electric shock.) 

 

Notifies users that specific actions are prohibited to 
prevent possible danger. The symbol inside 

 

graphically indicates the prohibited action.  
(For example, the sign on the left notifies that 
disassembly is prohibited.)  

 

Instructs users to carry out a specific obligatory 
action to prevent possible danger. The symbol 
inside 

 graphically indicates the actual action to 

be carried out.   
(For example, the sign on the left indicates general 
instructions.) 

 

 WARNING  



When handling or transporting any heavy product 
(more than 18 kg), carefully move the product with 
a hand truck or the like, or with 2 or more people.  
Careless lifting or accidental dropping of the 
product may result in injury or product damage. 

 

 

 CAUTION 

(1/2)

 



Provide a circuit protector (e.g., a fuse or circuit 
breaker) for the power source.  
Failure to do so may cause a short circuit leading to 
fire or device failure. 



Do not freeze this product.  
Doing so may damage the valve body and cause 
leakage. 



When piping this product, be sure there is no 
foreign matter in the pipes. 
If foreign matter remains in the pipes, the product 
may break down. 

 
 

 

 CAUTION 

(2/2)

 



Install, wire, and use this product under the 
conditions specified by this manual.  
Failure to do so may cause fire or device failure. 



When installing this product, hold it in the proper 
position and securely fasten it to the pipes. 
Excessive tightening or improper installation 
position may damage the valve. 



After installation, make sure no fluid leaks from the 
valve-pipe connections. 
Improper piping may cause fluid leakage outside of 
the valve. 



Do not put a load or weight on this product.  
Doing so may damage the product. 



Installation and wiring of the actuator must be 
performed by personnel qualified to do 
instrumentation and electrical work.  
Mistakes in installation or wiring may cause fire or 
electric shock. 



Before wiring, setting, maintenance, or 
replacement, be sure to turn off the power to this 
product.  
Failure to do so may result in electric shock or 
device failure. 



All wiring must comply with applicable codes and 
ordinances.  
Otherwise there is a danger of fire. 



For wiring, strip the insulation from cables as 
specified in this manual.  
If the length of exposed wire is longer than 
specified, it may cause electric shock or short 
circuit between adjacent terminals.  
If it is too short, it may not make proper contact. 



Use crimp terminals with insulation for connections 
to the product terminals.  
Failure to do so may cause short circuit leading to 
fire or device failure. 



Tighten the terminal screws with the specified 
torque.  
Insufficient tightening of the terminal screws may 
cause fire or overheating. 



After wiring, setting, engineering, maintenance, or 
replacement work, be sure to reattach the cover. 
Failure to do so may result in electric shock. 



Do not carelessly touch this product when it is used 
to control hot water.  
Doing so may result in burns, because the product 
reaches a high temperature. 

 
 

Summary of Contents for ACTIVAL+ FVY513E Series

Page 1: ...Infilex AC Model WY5117 Flow data stored in Model FVY513EJ FVY514EJ is retrieved via RS 485 communication Modbus protocol The retrieved flow data is effective for energy saving facility operation JIS...

Page 2: ...Do not freeze this product Doing so may damage the valve body and cause leakage When piping this product be sure there is no foreign matter in the pipes If foreign matter remains in the pipes the prod...

Page 3: ...control the quality of process fluid water and do not allow rust or foreign object inside the valve Rust or foreign object inside the valve lowers flow rate measuring accuracy Thermally insulate the v...

Page 4: ...ns of the pipe sensor refer to AB 6923 Specifications Instructions of Temperature Sensor for Pipe Surface Model TY7820Z0P05 Total length 5 m Model TY7820Z0P10 Total length 10 m Model TY7820Z0P30 Total...

Page 5: ...End connection JIS 20K flanged end raised flange Size Cv Close off rating Model number Nominal size Cv Close off ratings FVY513EJ0012 FVY514EJ0012 DN15 1 2 2 5 1 0 MPa FVY513EJ0013 FVY514EJ0013 DN15...

Page 6: ...ion 6 pin 3 pin 2 connector Display Panel 4 pin connector Enclosure rating IEC IP54 dust proof and splash proof Operation status indicator LED 1 red LED Status LED indication Normal Repetition of 1 se...

Page 7: ...FVY513EJ0081 FVY514EJ0081 DN80 3 125 1250 l min Measuring accuracy Factory preset Notes 1 The flow measurement accuracy figures assume a temperature range of 7 17 C or 45 65 C internal pipe pressure...

Page 8: ...racy and the error due to wiring length 7 Energy calculation accuracy is calculated from the flow rate measuring accuracy at 1 C measuring error of the temperature difference 8 The flow rate measuring...

Page 9: ...f the product relay terminal block wiring and the relay terminal block load device in connection 2 JCS Japanese Electric Wire and Cable Makes Association 3 KPEV Wire standard provided by Furukawa Elec...

Page 10: ...water temperature Reset switch Connector for Display Panel 24 V AC Power Port for Display Panel cable Port for temperature sensor Pt100 input cable Port for valve sensor cable Port for temperature se...

Page 11: ...side of the valve For chilled hot water 40 or more meshes If the strainer cannot be installed just before the inlet of each valve install it on the pipe diverting sections for each piping system Insta...

Page 12: ...or faces downward Flow direction Flow direction Flow direction Figure 5 Incorrect mounting orientations Piping CAUTION When installing this product hold it in the proper position and securely fasten i...

Page 13: ...oduct Heat insulating Apply heat insulation as illustrated by in Fig 6 If the yoke and or the actuator are covered with insulation material the point cannot be checked or may be distorted If the heat...

Page 14: ...ve the actuator may break down Do not manually open or close the valve more than 100 or less than 0 scale 1 Turn off the power 2 Hold the joint using a wrench etc gently turn the wrench to the desired...

Page 15: ...it may not make proper contact Use crimp terminals with insulation for connections to the product terminals Failure to do so may cause short circuit leading to fire or device failure Tighten the term...

Page 16: ...sor Pt100 input Terminal Wire color Description Temperature sensor for pipe surface Insertion type pipe temperature sensor T1A Red Red Pt100 A supply water temperature T1B White Black Pt100 B supply w...

Page 17: ...the recommended cable 1 Pass the 4 core cable of Display Panel through the actuator port for Display Panel See Fig 3 for the location of the port 2 Strip the wire sheath Strip length is 8 mm See Fig...

Page 18: ...pply cable Attach the optional cable gland with three ports Model DY7000A1000 to the wiring port to share the wiring port with signal lines Connect the wires of RS 485 communication cable to the conne...

Page 19: ...with multiple 4 20 mA input type products See Figs 23 and 24 4 20 mA control signal input is not isolated from the power and the 4 20 mA input impedance is 282 For connecting a controller the relatio...

Page 20: ...Terminals 2 6 and 8 of the product are internally connected 3 Refer to 6 Single transformer with two products in the Precautions for connection section Figure 24 Connection example Two Model FVY513EJ...

Page 21: ...izing pulse output open collector output Model FVY51XEJ This product 3 4 V Protection diode Magnetic counter 0 V Figure 29 Connection example Magnetic counter with relay coil Master Slave Model R seri...

Page 22: ...y release all the latches start with the one which cannot be visibly checked 1 Press the upper part of one of the male latches 1 in the figure below 2 Press up the lower part of the one of the male la...

Page 23: ...port 3 Connect the seal connectors optional to the cover of the cable gland IMPORTANT When tightening a seal connector to the cover be sure not to press excessive force on the latches Figure 32 Connec...

Page 24: ...without insulation sleeve is crimped on a wire end use a tube marker for safety During wire termination do not allow any foreign objects including chips and stripped insulation to get inside the prod...

Page 25: ...h the base of the cable gland from the wiring port of the product IMPORTANT Carefully handle the O rings attached to the cable gland Check that the cable gland has 3 O rings and be sure to keep these...

Page 26: ...Visual inspection Semiannual Fluid leakage from the gland and the flange face Loosened bolts Valve and actuator damages Operating status Semiannual Unstable open close operation Abnormal noise and vi...

Page 27: ...he valve position detecting accuracy Disposal Dispose of this product as industrial waste in accordance with your local regulations Do not reuse all or any part of the product 1 cm Lower setscrew of t...

Page 28: ...na Fujisawa Kanagawa 251 8522 JAPAN https www azbil com Rev 6 0 Apr 2020 AB 7131 J AI 7131 Rev 4 0 28 ACTIVAL and ACTIVAL are trademarks of Azbil Corporation in Japan or in other countries This produc...

Reviews: