(
9.52)
(
15.88)
( 6)
( 6)
( 6)
(
9.52)
(
12)
(
15.88)
(
9.52)
INSTALLATION MANUAL---Information for the installer
(1) Refer to the data rating label sticked on the outdoor unit.
TIGHTENING TORQUE FOR PROTECTION CAPS AND FLANGE CONNECTION
21
Model number
Liquid pipe diameter
Gas pipe diameter
Length of pipe with standard charge
Maximum distance between indoor and outdoor unit
Additional gas charge
Max. diff. in level between indoor and outdoor unit
Type of refrigerant(1)
1/4
1/4
1/4
3/8
1/2
3/8
5/8
3m
T27-M11
T33-M11
T50-M11
T70-M11
T70-M11i
3m
4m
4m
4m
15m
15m
15m
15m
15m
20g/m
20g/m
30g/m
30g/m
30g/m
5m
5m
5m
5m
5m
R410A
R410A
R410A
R410A
R410A
3/8
5/8
PIPE
1/4
( 6)
3/8
(
9.52)
1/2
(
12)
5/8
(
15.88)
TIGHTENING TORQUE
[N x m]
TIGHTENING TORQUE
[N x m]
CORRESPONDING STRESS
(using a 20 cm wrench)
15 - 20
31 - 35
35 - 45
75 - 80
Service port nut
Protection caps
7 - 9
25 - 30
wrist strength
arm strength
arm strength
arm strength
(
12)
1/2