background image

 
 

 

 

 

12/12 

AXITEC INSTALLATION 

– USA 170727 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

AXITEC, LLC 

1819 Underwood BLVD, Suite 5 

Delran, New Jersey 08075 

United States of America 

 

www.axitecsolar.us

  

 

This document is subject to change without notice.  

 

Summary of Contents for 60-CELL

Page 1: ...1 12 AXITEC INSTALLATION USA 170727 Installation Manual AXITEC SOLAR MODULES ...

Page 2: ...ONS 5 2 INSTALLATION AND OPERATION 5 3 MECHANICAL INSTALLATION 5 3 1 60 CELL MODULES 6 3 2 72 CELL MODULES 7 3 3 MOUNTING WITH BOLTS 8 3 4 MOUNTING WITH CLAMPS 9 3 5 GROUNDING 9 4 ELECTRICAL INSTALLATION 9 4 1 GENERAL WIRING 9 4 2 MODULE WIRING 10 4 3 ARRAY WIRING 10 5 JUNCTION BOX AND TERMINATION 10 6 MAINTENANCE 11 7 SPECIFICATION 11 7 1 ELECTRICAL SPECIFICATION Typical 11 7 2 GENERAL SPECIFICAT...

Page 3: ...o make changes to the product specifications or this manual without prior notice Without any prior written authorization AXITEC LLC will not accept any returned modules GENERAL INFORMATION The installation of solar modules must only be performed by skillful and qualified professionals SAFETY Follow all permission installation and inspection requirements Must contact the appropriate authorities to ...

Page 4: ...dry modules and tools Do not break the glass surfaces of modules Do not drop a module Do not allow children and unauthorized persons near the installation site or storage area of modules All modules have been complete grounding to earth with electrical insulation Do not open the cover of the junction box Do not disassemble the module or remove any part installed by the manufacturer Wear suitable p...

Page 5: ...dule Although AXITEC LLC modules are quite rugged the glass may be broken and the module will no longer work properly if it is dropped or hit by tools or other objects Sunlight shall not be concentrated on the module The module frames is made of anodized aluminum and therefore corrosion can occur if the module is placed in a salt water environment with contact to a rack of an other type of metal E...

Page 6: ...6 12 AXITEC INSTALLATION USA 170727 3 1 60 CELL MODULES Figure 1 A distance 7 87 inch 200 mm B clamping zone 7 87 inch 200 mm C clamping zone 11 81 inch 300 mm D clamping zone 7 87 inch 200 mm ...

Page 7: ...7 12 AXITEC INSTALLATION USA 170727 3 2 72 CELL MODULES A distance 11 42 inch 290 mm B clamping zone 7 87 inch 200 mm ...

Page 8: ...e mounted on the roof of a building The modules are supported parallel to the surface of the building roof To prevent wiring damage and to allow air to circulate behind the module clearance between the module frames and surface of the roof is required The standoff minimum height is 3 9 inch about 100 mm refer to Figure 2 If other mounting means are employed this may affect the listing for fire cla...

Page 9: ...grounded in accordance with the appropriate respective National Electrical Code Proper grounding is achieved by bounding the module frame and all metallic structural members together continuously using a suitable grounding conductor The grounding conductor or strap may be copper copper alloy or other material acceptable for use as an electrical conductor per respective National Electrical Codes Th...

Page 10: ...and temperature rating of the conductors to be used Size 12AWG Type Tinned fine copper strands according to VDE 0295 IEC60228 class 5 Temperature rating 40 C up to 125 C 4 3 ARRAY WIRING Use copper wire only Cu only that is sunlight resistant and is insulated to withstand the maximum possible system open circuit voltage For use with non metallic wiring systems only For field connections use minimu...

Page 11: ...and VOC marked on this module should be multiplied by a factor of 1 25 when determining component voltage ratings conductor ampacity fuse sizes and size of controls connected to the PV output Refer to Section 690 8 of the National Electrical Code for an additional multiplying factor of 125 percent 80 percent derating which may be applicable 7 2 GENERAL SPECIFICATION Axitec LLC reserves the right t...

Page 12: ...12 12 AXITEC INSTALLATION USA 170727 AXITEC LLC 1819 Underwood BLVD Suite 5 Delran New Jersey 08075 United States of America www axitecsolar us This document is subject to change without notice ...

Reviews: