UMAX180800, 20 Thermocouple, 2 RTD, 4 Inputs, 6 Relays Dual CAN Controller
Version 1
Page: 13-71
Object ID
Object Name
Description
0x01
ProductCode
Controller P/N.
“AX180800”
0x02
MajorMinorRevision
Current firmware version. For example,
“V1.00”
0x03
VendorUrl
“www.axiomatic.com”
0x04
ProductName
“IO Controller”
0x05
ModelName
Same as ProductCode. Controller P/N.
“AX180800”
0x06
UserApplicationName Firmware description. Depends on the firmware version. For
V1.xx:
“20 Thermocouple, 2 RTD, 4 Inputs, 6 Relays Dual CAN
Controller
”
0x80
SerialNumber
Private Object. Controller S/N.
For example, “0012020016”
All device identification objects are presented in ASCII strings.
2.7 Discovery Protocol
The controller supports an Axiomatic proprietary protocol that allows the discovery of
Axiomatic controllers on a LAN by sending a global UDP request on port 35100
1
.
1
O. Bogush, "Ethernet to CAN Converter Discovery Protocol. CAN-ENET, AX140900, Project 15129.
Document version: 1," Axiomatic Technologies Corporation, October 26, 2016.
Axiomatic provides a Windows console application
AxioDisc.exe
that can be used to
discover the controller. The application shows the controller MAC address, IP address, web
server port (not used), device port (Modbus port), device port type (TCP), the controller part
number and serial number, see Figure 2.
The
AxioDisc.exe
. application is available upon request.
Figure 2. Discovery of the Controller on LAN Using
AxioDisc.exe
Application
2.8 Default Settings
The controller
Universal Inputs
are configured to input voltages in the
0…5V voltage range by
default. These voltages can be read through Modbus interface.
The CAN output messages are not set up by default. They can be configured to accommodate
user-specific application requirements, see
Error! Reference source not found.
in