ATTENTION: ADDITIONAL MAINTENANCE FOR BOILERS WITH
ALUMINUM
HEAT
EXCHANGERS
-
Boilers with Aluminum heat exchangers deposite white salt on the neutralization media that
restricts flow through the neutralizer. To clean the media, remove the pump and cover,
thoroughly rinse the media with water, washing the salt out of the tank. Replace the pump
and cover.
Troubleshooting Chart
Problem
Resolution
The unit does not run.
a) Check the power supply.
b) Check the appliance to see if the condensate is actually being
produced.
c) Make sure the inlet piping is not clogged. If it is clogged, the
appliance may eventually be damaged.
The unit makes loud noises
when running.
a) Make sure the inside of reservoir is clean.
b) Make sure there is no siphoning action.
The unit runs but does not
pump the liquid out.
a) Check that the highest point of the outlet piping does not
exceed the maximum delivery head of the pump.
b) Make sure the outlet piping is not clogged.
c) Inspect the check valve following the maintenance
instructions.
Liquid drains back into the
pump from the outlet piping.
a) The check valve may have debris in it. Clean the check valve
following the maintenance instructions.
Liquid leaks from around the
check valve.
a) Make sure the outlet piping is tightly connected with the
check valve.
b) Make sure the check valve is fastened properly.
c) If the O-ring under the check valve is damaged, replace with
a new one.
Limited Warranty
The NT25-P18 is warranted against defects in materials and workmanship for one year.
7
Figure 7:
Salt precipitate deposited on
neutralization media from Aluminum heat
exchangers
Figure 8:
Neutralization media that has
been rinsed with clean water