background image

Commissioning of a SOLO-system

Commissioning of a SOLO-system requires a MIFARE DESFire EV2 card or tag. If data in the sys-

tem should be spread by the cards/tags of the users, the Master reader should be the reader

where most users passes.

1. Select the master reader.

2. If not already done, connect and commission the reader

3. Enter the programming mode of the selected master reader.

The programming mode is entered by pressing the programming button (the rightmost

round button) and entering of the programming code. (Default set to 112233).

4. Navigate to menu

Options > Operating mode and select Master.

5. Return to main menu and navigate to

tags menu. Select New tag and present a

MIFARE DESFire EV2 tag, from now referred to as programming tag. Select

Yes if the

question to

erase tag appears.

6. Perform configuration of tags, codes time schedules and so on.

7. Exit the programming mode

8. Present the Programming tag to the master reader until

Hold tag disappears.

9. For all slave readers,

i. If not already done, connect and commission the reader

ii. Enter programming mode

iii. Navigate to menu

Options > Operating mode and select Slave.

iv. Select

Pair system.

v. Present the Programming tag to the reader until

Hold tag disappears.

vi. Set time/date and active buttons for radio keys.

vii. Exit the programming mode

5 (9)

ManualA66 SOLO

Summary of Contents for VAKA A66 SOLO

Page 1: ...Axema Access ControlAB Box 90215 120 23 Stockholm Sweden 46 0 8 722 34 40 info axema se www axema se Reader VAKA A66 SOLO offline Manual Updated 11 20 2020...

Page 2: ...dministration of a SOLO system 6 Synchronisation of all readers 6 Programming 7 To be programmed in the master reader 7 To be programmed in each slave reader 7 Initialization of a new slave reader 8 C...

Page 3: ...rs are set as Slaves The configuration of the master reader is distributed to the slave readers by MIFARE DESFire EV2 credentials Axema radio keys RN18 MIFARE Classic and EM credentials can be used in...

Page 4: ...s the door is opened even if the unlocking time is longer A closed door is to be indicated by a closed contact between the terminals Commissioning A66 1 Connect the power supply to the A66 The display...

Page 5: ...tions Operating mode and select Master 5 Return to main menu and navigate to tags menu Select New tag and present a MIFARE DESFire EV2 tag from now referred to as programming tag Select Yes if the que...

Page 6: ...ensure that the database is quickly synchronized in all readers the slave readers can be updated manually If the system has readers whose users do not also pass the master reader these readers must b...

Page 7: ...tch means that codes only works in the master reader l Daily unlocked function l Exit button l EM on off l Programming code l Language l Automatic daylight saving time adjustments To be programmed in...

Page 8: ...amming mode 9 Follow the instructions in Maintenance administration of a SOLO system Convert a slave reader to a master reader If the master reader needs to be replaced any slave reader can be set as...

Page 9: ...elect the ID of the slave reader to be replaced 7 Exit the programming mode 8 Follow the instructions in Initialization of a new slave reader About MIFARE DESFire EV2 tags A MIFARE DESFire EV2 tag can...

Reviews: