Rev.1.0
Key Function
1.In normal display, The key function is call out adjustment display scale page
2.Into parameter setting page, the parameter mark & data is alternate display,If need modify data can
press
key into setting procedure, The display is lock parameter data, this time must let off key
about 0.2 sec, press again, the parameter data will increment. (Key Response about 0.2 sec). If the
setting value have negative,Shift cursor(twinkle express) to the leftest and Press
key
can positive
/
negative number alternate display
&
Key Function
1.In setting group or setting page press
&
key return normal display, but if in setting page the
modify data will be lost
No Key in anything
1.In setting group or setting page no key in anything about 2 minutes, return normal display, but if in
Setting page the modify data will be lost
Step Parameter mark description Parameter mark
Operation manual
1
Normal display
Press
/FUNC key into P.COD
E setting page
2
P.CODE(Pass code input page)
1.Key in 5 digit pass code with
or
key
2.Press
key, the pass code is right into setting group, otherwise
return normal display
SYS(System setting group)
ROP(Alarm setting group)
AOP(Analog output setting
group)
3
DOP(Communication setting
group)
1.
Select setting group with
key
2.
Press
key into setting page of selection setting group
4
SYS(System setting group)
1.Press
key decide SYS setting group , press
key into DP setting
page
4-1
DP(Decimal Point)
Default = 0
1.
Decide decimal point position with
key (0~4)
2.
Press
key enter data and into TYPE setting page
4-2
TYPE(Type)
Default = 1U2G
1.Decide input type with
key (1U2G,1G2U,1D2G,1G2D
,1U2D,1P2D,1A2B)
2. Press
key enter data and into CNTS setting page
4-3
CNTS(Count Rates Select)
Default = 50KHZ
1.Decide Count Rates Select with
key (50HZ,50KHZ)
2. Press
key enter data and into P.OFF.M setting page
4-4
P.OFF.M(Power Off Mode)
Default = RESET
1.Decide Power Off Mode with
key (RESET or MEMOR)
2. Press
key enter data and into CODE setting page
Note:RESET(Power Off Reset):Count value and Alarm is reset
MEMOR(Power Off Memory) :Count value and Alarm is save
4-5
CODE(Pass Code)
Default = 0
1.Decide pass code with
or
key (0~99999)
2. Press
key enter data and into LOCK setting page
4-6
LOCK(Panel Lock)
Default = NO
1. Decide panel lock with
key(NO or YES)
2. Press
key enter data and return SYS setting group
5
ROP( Alarm setting group)
1.Press
key decide ROP setting group, press
key into OP.MODE
setting page
5-1
OP.MODE(Output Mode )
Default = N
1. Decide output mode with
key (N,F,R,Q,C,P,K)
2. Press
key enter data and into ACT1.T setting page
5-2
ACT1.T(Active 1 Time )
Default = 0
1.Decide Active 1 Time with
or
key (0.0~99.9)sec.
2. Press
key enter data and into ACT2.T setting page
3.ACT1.T=0 sec. is self-holding output 1
.ACT1.T=0.1~99.9 sec. is one-shot output 1
Note:When :OP.MODE=N, ACT1.T = 0 sec.
5-3
ACT2.T(Active 2 Time )
Default = 0
1. Decide Active 2 Time with
or
key (0.0~99.9)sec.
2. Press
key enter data and return ROP setting group
3. ACT2.T=0 sec. is self-holding output 2
ACT2.T=0.1~99.9 sec. is one-shot output 2