Avtron SMARTSafe XR125 Manual Download Page 3

XR125 3

 CAUTION

 

DO NOT use silicone sealants or caulk of any kind on  

 

the motor or encoder face; these can cause  

 

misalignment or sensor scraping damage. Do apply  

 

antiseize compound (copper) to the encoder face to  

 

assist in easy removal. The XR125 electronics are fully  

 

sealed; water may enter and leave the rotor area as  

 

needed. Remove the bottom pipe plug in the housing if  

 

frequent moisture buildup is expected.

 

A special marine-sealed version of the housing is available (option 

006) if there is a concern about ice or salt buildup inside the 

encoder.

(OPTIONAL) OUTBOARD SEAL PLATE KIT INSTALLATION 

For applications requiring shafts to pass completely through the 

XR125, Avtron offers an outboard through-shaft seal plate kit with 

V-ring seal. See Table 3 for part numbers and Figure 3. Note that 

for large through-shaft bores T8 and T9, no seal is available. For T9 

through-shafts, no cover is needed.

1.  Install the encoder rotor as shown above.

2.  Remove the existing cover of the encoder. Retain the screws  

 

and washers.

3.  Mount the XR125 stator housing as shown above.

4.  Install new through-shaft cover using the (4) #10-24 screws 

and  

 

washers from step 2.

5.  Apply silicone lubricant or medium grade machine oil (20  

 

 weight) 

 

 

to the outboard side of the cover where the V-ring seal will  

 

contact it.

6.  Slide the V-ring seal onto the shaft, and ensure that it is  

 

compressed against the cover. See installation Figure 3.

MOUNTING THE XR125/XR12 WITHOUT A STATOR HOUSING

The XR125 (XR12 rotor) may be mounted without the use of 

a C-face or XR125 stator housing.  See XR12 manual for details.

WIRING INSTRUCTIONS

 CAUTION

 

Be sure to remove power before wiring the encoder. 

 

Be sure to ground the cable shield: Avtron recommends 

 

grounding the shield at the isolator module for Zone 1 

 

applications or in the drive cabinet for Zone 2 

 

applications. Cable should not be grounded multiple 

 

places. An intrinsic safety ground is required at the  

 

XRB1 Isolator Module.

 

 CAUTION

 

SMARTSafe encoders include a local ground lug for  

 

customer convenience and encoder frame grounding  

 

if required to meet local electric code requirements or  

 

site operator protection standards.  This is NOT the  

 

required XRB1 intrinsic safety ground connection  

 

required for hazard protection against ignition of  

 

explosive atmospheres for Zone 1 and Zone 21  

 applications!

 CAUTION

 

The XRB1 isolator used for Zone 1 and Zone 21   

 

 

protection requires an intrinsic safety ground to provide  

 

hazard protection.  Failure to connect this ground, or    

 

providing an inadequate safety ground path can result  

 

in an spark/ignition hazard which can result in property  

 

damage,  injury, or even death.

For bi-directional operation of the encoder, proper phasing of the two 

output channels is important. Phase A channel typically leads phase 

B channel for clockwise shaft rotation as viewed from the anti-drive 

or accessory end of the motor (encoder mounting end).  

See Pinout and Phasing tables for exceptions. 

Wiring option “G” provides a pinout compatible with Northstar

TM

 

encoders, with a cable shield connection on pin 10. Note that this 

option does not ground the shield.

CORRECTIVE ACTION FOR PHASE REVERSAL

1)  Remove Power. 

2)  Exchange wires on cable, either at encoder cable  

 

end or at speed controller end (but not both). 

 

a)  Single Ended 2 Phase Wiring  

 

 

(see wiring diagram)  

 

 

Exchange A and B connections at the device end. 

 

b)  Differential 2 Phase Wiring (see wiring diagram) Exchange  

 

 

either A with A– in the phase A pair OR B with B– in the    

 

 

phase B pair but NOT both. 

3)  Apply Power. 

4)  Verify encoder feedback is correct, using hand rotation of shaft,  

 

or jog mode of the speed controller.

Interconnection cables specified in the wire selection chart are 

based on typical applications. Cable must be selected and installed 

in accordance with IEC/EN60079-14 and IEC/EN60079-25. Physical 

properties of cable such as abrasion, temperature, tensile sstrength, 

solvents, etc., are dictated by the specific application. General 

electrical requirements are : stranded copper, 20 through 16AWG 

(Industrial EPIC connector type options can use 14 AWG). Each twisted 

wire pairs overall shielded with braid or foil with drain wire, .05uf of 

maximum total uutual or direct capacitance, outer sheath insulator. 

See specifications for maximum cable length. Stranded 20 AWG wire 

should not be used for cable runs greater then 61 meters. If 20AWG is 

used with EPIC type connector options the wire ends should be tinned. 

 

See wiring diagram for examples of alarm output wiring.

MAINTENANCE

GENERAL

This section describes routine maintenance for the Avtron XR125 

Encoder. For support, contact Avtron’s field service department at 

216-642-1230. For emergency after hours service contact us at 

216-641-8317.

The XR125 SMARTach II circuitry includes a diagnostic package that 

includes Adaptive Electronics and a Fault-Check output.

FAULT-CHECK

After power-up and the rotor position is checked by the sensor, the 

Fault-Check LED will turn green.

If the adaptive electronics reach their adjustment limit for any 

reason, the Fault-Check alarm and LED will notify the drive and 

operator of an impending failure. The LED will turn red if the 

Adaptive Electronics reach their adjustment limit. This output occurs 

before an actual failure, allowing steps to be taken to replace 

the unit before it causes unscheduled downtime. Fault-Check 

annunciation is available as an “alarm” output through the connector  

(Zone 2 configuration only) and as an integral LED.

TROUBLESHOOTING:

If the drive indicates a loss of encoder/tach fault and the XR125 

fault-check LED is not illuminated, check the encoder power supply. 

If power is present, check polarity; one indicator of reversed power 

supply is that all outputs will be high at the same time. If the drive 

indicates encoder fault, but the LED shows GREEN, then check the 

wiring between the drive and the encoder. If the wiring appears 

correct and in good shape, test the wiring by replacing the XR5 

sensor module. If the new module shows GREEN, and the drive still 

shows encoder loss/tach fault, then the wiring is faulty and should 

be repaired or replaced.

Summary of Contents for SMARTSafe XR125

Page 1: ...the XR125 is determined by the sensor only Unlike older models any PPRs can be mixed and matched Selection of the rotor is based only on the shaft mounting requirements and not PPR ADAPTIVE ELECTRONICS A perfect duty cycle consists of a waveform whose high and low conditions are of the same duration 50 50 It is possible over time for the duty cycle and edge separation to change due to component dr...

Page 2: ...and strong magnetic fields At installation clean and remove paint and burrs from motor shaft and mounting face Apply anti seize compound supplied to each except cam screw rotors INSTALLATION HARDWARE Supplied XR125 Encoder 1 Washer Spring Lock 1 2 4 2 Hex Hd Cap Screw 5 8 11 x 4 00 4 Rotor 1 Rotor Installation Hardware Kit 2 Anti Seize Compound copper 3 Thread Locker blue Not Supplied 15 16 Wrench...

Page 3: ...ions Wiring option G provides a pinout compatible with NorthstarTM encoders with a cable shield connection on pin 10 Note that this option does not ground the shield CORRECTIVE ACTION FOR PHASE REVERSAL 1 Remove Power 2 Exchange wires on cable either at encoder cable end or at speed controller end but not both a Single Ended 2 Phase Wiring see wiring diagram Exchange A and B connections at the dev...

Page 4: ...tter or accordion effect see figure below check rotor position If the rotor position is correct the motor or shaft may be highly magnetized Replace any magnetized material nearby with non magnetic material aluminum stainless shafts etc For GE CD frame motors and similar styles Avtron offers non magnetic stub shafts included with all U style rotor kits If variations persist consider replacing the s...

Page 5: ...4 375 T6 4 500 TD 4 625 TE 4 690 TA 4 875 TG 5 000 T7 5 375 T8 6 750 T9 7 875 Connector Options Zone 1 21 Remote Protection and Zones 2 22 Zones 1 21 Local Protection Mounted on Encoder Body 3 Cable XRB1 in EX Box Industrial Connector 10 pin MS Other Twist Lock Other 5 6 G NorthstarTM Pinout with Plug P with Plug A without Plug B with Plug clamp R Twist Lock Mini MS with Plug 4 Terminal box S Mini...

Page 6: ... the motor E Phase Sep 15 minimum F Frequency Range 0 to 165 000 Hz G PPR 8 5000 H Line Driver Specs See table I Connectors See connector options on page 1 J Integral LED Indicator GREEN power on unit ok RED alarm on MECHANICAL A Rotor Inertia 0 17 0 36 Oz In Sec 2 B Acceleration 5000 RPM Sec Max C Speed 5400 RPM Max D Weight 2 3 lbs 0 9kg to 1 36kg E Sensor to Rotor Air Gap nominal 0 030 0 76mm T...

Page 7: ...TV A35681 A34376 9 471907 3 250 TW B31204 TW A35681 A34376 19 471907 3 375 TY B31204 TY A35681 A34376 10 471906 3 875 T4 B31204 T4 A35681 A34376 11 471943 4 125 TB B31204 TB A35681 A34376 21 471943 4 250 T5 B31204 T5 A35681 A34376 12 471944 4 375 TC B31204 TC A35681 A34376 22 471944 4 500 T6 B31204 T6 A35681 A34376 13 471944 4 625 TD B31204 TD A35681 A34376 23 471950 4 690 TE B31204 TE A35681 A343...

Page 8: ...n Pin Outs 0V Gnd A B Z Alm Vin A B Z Alm 10 Pin MS Avtron on 12 Cable Y A CW Pin A D E C NC B G H I NC 10 Pin MS Mini Twist Lock R S A CW Pin F A B C NC D H J K NC 10 Pin Mini Industrial Avtron Pinout P A CW Pin 1 2 3 4 5 6 7 8 9 10 10 Pin Mini Industrial Northstar Pinout G A CW Pin 1 2 3 4 NC 6 7 8 9 NC 3 Cable Sealed W A CW Color BLK GRN BLU ORG BRN RED YEL GRA WHT VIO Phasing is defined as the...

Page 9: ...IRING 2 Pair 3 Pair 4 Pair 5 Pair Belden Alpha 9552 9553 9554 1328A 2242C 2243C 2244C 2245C 5 24 Volts Out Customer Equipment A B Z GND 0 K1 0V 1 K2 E 2 Ub K0 ZONE 2 HAZARDOUS AREA SAFE AREA ENCODER LINE DRIVER OPTION 7 Typical Cable 500 150M max 18AWG Twisted Pair Overall Shield See A ached for Connector Op on Pin Outs SINGLE ENDED 2 PHASE WIRING v alm 5 24 Volts Out Customer Equipment ZONE 2 HAZ...

Page 10: ...Y 115 VAC SINK 100 mA MAXIMUM Q5 MMFT6661 ENCODER FUNCTIONAL DIAGRAM ØB ØA ØA ØB LINE DRIVER NOTE 1 CR8 L W P Z See specifications for Zone 2 power supply limits Example 2 Alarm Output Using Separate VDC Power Supply and Relay Applies to all XR56 models except wiring options G R and S ALARM OUTPUT CONNECTION Avtron THIN LINE II encoders provide an alarm signal if maintenance is required under spec...

Page 11: ... 584 0 100 14 8mm 2 5mm ROTOR ALIGNMENT GROOVE Rotor magnetic strip aligns with groove A 0 21 5 3 MIN 0 27 6 9 MIN 0 31 7 9 MIN 0 38 9 7 MIN A ADD L SHAFT LENGTH REQ D FOR V RING 0 19 0 02 4 6 0 5 0 24 0 03 6 1 0 8 0 28 0 04 7 1 1 0 0 35 0 05 8 9 1 3 2 75 3 00 70 0 79 4 0 38 9 7 MIN 0 35 0 05 8 9 1 3 Add 0 22 5 6 for cover depth 3 00 75mm 1 50 2 63 38 1 66 7 0 87 1 38 22 2 34 9 0 50 0 63 12 7 15 8...

Page 12: ... 3 67 93 2 Assembled 0 53 13 5 1 66 42 2 1 42 36 0 OPTION W 0 53 13 5 36 50 927 0 MIN 4 31 109 5 1 1 29 1 1 29 4 31 109 5 1 574 40 0 2 13 54 0 0 18 4 5 0 217 5 50 4 Holes 3 10 78 7 0 25 6 3 0 18 4 6 Ø 12 502 12 504 Ø317 55 317 60 1 85 47 0 Ø 12 500 12 498 Ø 317 50 317 45 6 21 157 8 3 83 97 3 LED ALARM INDICATOR 1 2 14 NPT OPTIONAL 2nd ISOLATED OUTPUT COVER PLATE SINGLE OUTPUT ONLY 45 Ø 0 671 17 0 ...

Reviews: