Avtron SMARTach III AV850 Manual Download Page 4

AV850 4

  NOTE

  If additional magnetic shielding (option 004) has  

 

  been added to the sensors, be sure to remove the  

 

  sensors before installing the stator housing.

The stator housing is retained to the motor using four, 1/2-13 x 3” bolts 

and spring type lock washers (supplied). If the stator is to be sandwich 

mounted between an accessory such as a brake and the motor, select 

the bolt length accordingly. Apply anti-seize compound to the perimeter 

of the AV850 where it will contact the motor C-face.
Carefully move the stator housing into position, avoiding contact with 

the rotor. DO NOT FORCE the housing into place. Install the four 

mounting bolts (torque 30 to 35 foot pounds) [47.5-40.6 n-m].

CAUTION

DO NOT use silicone sealants or caulk of any kind on the 

motor or encoder face; these can cause misalignment or 

sensor scraping damage. Do apply anti-seize compound 

(copper) to the encoder face to assist in easy removal. The 

AV850 electronics are fully sealed; water may enter and 

leave the rotor area as needed. Remove the bottom pipe 

plug in the housing if frequent moisture buildup is expected.

(OPTIONAL) OUTBOARD SEAL PLATE KIT 

INSTALLATION.

For applications requiring shafts to pass completely through the AV850, 

Avtron offers an outboard through-shaft seal plate kit with V-ring seal. 

See Table 4 for part numbers and Figure 4.
 

1. Install the encoder rotor as shown above.

 

2. Remove the existing cover of the encoder. Retain the screws    

 

  and washers.

 

3. Mount the AV850 stator housing as shown in Figure 4.

 

4. Install new through-shaft cover using the (4) #10-24 screws    

 

  and washers from step 2.

 

5. Apply silicone lubricant or medium grade machine oil (20  

 

 

  weight) to the outboard side of the cover where the V-ring seal   

 

will contact it.

 

6. Slide the V-ring seal onto the shaft, and ensure that it is  

 

 

  compressed against the cover. See installation Figure 4.

(OPTIONAL) SHAFT GROUNDING KIT INSTALLATION

(Rotors “FA-F9”, “GA-G9”)

Refer to separate Shaft Grounding Kit Instructions (M190-AV850)

(OPTIONAL) CHECK ROTOR POSITION

 

1. Remove a sensor or blank side cover plate.

 

2. Verify the rotor magnetic stripe is aligned with the grooves (see   

 

Figure 5).

 

3. Replace the sensor or side cover plate.

WIRING INSTRUCTIONS

CAUTION

Remove power before wiring.

Wiring diagrams are shown in Figure 6 and 7.
For bidirectional operation of the encoder, proper phasing of the two 

output channels is important. Phase A channel leads phase B channel 

for clockwise shaft rotation as viewed from the anti-drive or accessory 

end of the motor (encoder mounting end). Wiring option “G” provides 

a pinout compatible with Northstar™ encoders, with a cable shield 

connection on pin 10. Note that this option does not ground the shield; 

Avtron still recommends grounding the shield at the drive end of the 

cable for all wiring options.

CORRECTIVE ACTION FOR PHASE REVERSAL

 

1) Remove Power.

 

2) Exchange wires on cable, either at encoder cable end or at    

 

  speed controller end (but not both).

 

    a. Single Ended 2 Phase Wiring (see wiring diagram)  

 

 

      Exchange A and B at the use end of the wires.

 

    b. Differential 2 Phase Wiring (see wiring diagram) Exchange  

     either 

with 

A in the phase A pair OR B with B in the  

 

 

      phase B pair but NOT both.

 

3) Apply power.

 

4) Verify encoder feedback is correct, using hand rotation of shaft,  

 

  or jog mode of the speed controller.

Interconnecting cables specified in the WIRE SELECTION CHART in 

Figure 6 are based on typical applications. Refer to the system drawing 

for specific cable requirements where applicable.
Physical properties of cable such as abrasion, temperature, tensile 

strength, solvents, etc., are dictated by the specific application.
General electrical requirements are: stranded copper, 22 thru 16 gauge 

(Industrial EPIC Connector options can use 14-20 AWG), each wire pair 

individually shielded with braid or foil with drain wire, 0.05 uF maximum 

total mutual or direct capacitance, outer sheath insulator, 1,000 ft. 

max. See WIRE SELECTION CHART in Figure 6 for some suggested 

cables.
See Figure 7 for examples of alarm output wiring.

NOTE

When using the industrial connector (“1”, “G”, “P”, “Q”, 

“V”, “X”, or “Z” options), the minimum wire size is 20 gage, 

and 20 gage (only) wire ends must be tinned with solder 

before connection at the screw terminals.

MAINTENANCE
GENERAL

This section describes routine maintenance for the Avtron AV850 

Encoder. For support, contact field service for Avtron Encoders at  

216-642-1230. For emergency after hours service contact us at  

216-641-8317. The AV850 SMARTach III circuitry includes a diagnostic 

package that includes Adaptive Electronics and a Fault-Check output.

ADAPTIVE ELECTRONICS

A perfect duty cycle consists of a waveform whose “high” and “low” 

conditions are of the same duration (50%/50%). The AV850 adaptive 

electronics extends the life of the AV850 by constantly monitoring and 

correcting duty cycle over time.

FAULT-CHECK

After power-up and the rotor position is checked by the sensor, the 

Fault-Check LED will turn GREEN. 
If the adaptive electronics reach their adjustment limit for any reason, 

the Fault-Check alarm and LED will notify the drive and operator of an 

impending failure. The LED will turn RED if the Adaptive Electronics 

reach their adjustment limit. This output occurs before an actual 

failure, allowing steps to be taken to replace the unit before it causes 

unscheduled downtime. Fault-Check annunciation is available as an 

“alarm” output through the connector and as an integral LED.

TROUBLESHOOTING:

If the drive indicates a loss of encoder/tach fault and the AV850 fault-

check LED is not illuminated, check the encoder power supply. If power 

is present, check polarity; one indicator of reversed power supply is that 

all outputs will be high at the same time. If the drive indicates encoder 

fault, but the LED shows GREEN, then check the wiring between the 

drive and the encoder. If the wiring appears correct and in good shape, 

test the wiring by replacing the AV5 sensor module. If the new module 

shows GREEN, and the drive still shows encoder loss/tach fault, then 

the wiring is faulty and should be repaired or replaced.

If the alarm output and/or LED indicate a fault (RED):
 

1. Remove a sensor plate or one of the sensors, and use  

 

 

  the built-in gauge to check the location of the rotor (see Figure    

 

2.1). Ensure the label marked “This side out” is facing away  

 

 

  from the motor.

Summary of Contents for SMARTach III AV850

Page 1: ...4 Install rotor as usual but gage location from the shield See Figure 3 The outer edge of the rotor may be damaged by scratches severe blows and strong magnetic fields GENERAL The Avtron Model AV850...

Page 2: ...Shaft G Universal with Grounding Kit Q EOS Adapter for Stacked Encoders F 1 125 GE CD180 320 N 2 125 GE CD360 P 2 375 GE CD400 2 2 875 GE CD500 R GE CD507 509 9 GE CD6000 6100 6200 6700 6800 6900 V GE...

Page 3: ...0 004 0 10mm Apply anti seize compound to the shaft CAUTION Do not strike the encoder or rotor at any time Damage will result and the warranty will be void At installation clean and remove paint and b...

Page 4: ...hase Wiring see wiring diagram Exchange either A with A in the phase A pair OR B with B in the phase B pair but NOT both 3 Apply power 4 Verify encoder feedback is correct using hand rotation of shaft...

Page 5: ...roubleshooting process if possible spin the encoder while replacing individual output connections This may make the ORANGE LED condition occur faster Once the shorted output s are located correct the...

Page 6: ...Temperature 40 to 100 C 0 100 condensing humidity Vibration 18 g s Shock 1 meter drop test LINE DRIVER OPTIONS SPECIFICATIONS Alarm not available on connector option G NorthstarTM compatible pinout E...

Page 7: ...OUT ALM RED BLUE GREEN BLACK ORANGE BROWN VIOLET OPTION OPTION OPTION OPTION T OPTION B E D A C F J 6 3 2 1 4 5 10 D B A F C NC NC B C E A D NC NC OPTION E F 6 3 2 1 4 NC NC 10 E D A F NC NC NC OPTION...

Page 8: ...POWER SUPPLY 115 VAC SINK 100 mA MAXIMUM WITHSTAND 50 V MAXIMUM REFERENCED TO COMMON ENCODER FUNCTIONAL DIAGRAM B A A B LINE DRIVER N K W A B C L P V X Z Example 2 Alarm Output Using Separate 24 VDC...

Page 9: ...2 2 3 0 2 4 3 A 3 C 4 1 5 1 3 B 3 C 3 T 5 1 9 0 3 B 3 T 0 0 5 3 A N A N 3 4 9 1 7 4 3 2 3 0 2 4 3 A A N A N 4 T 5 1 9 0 3 B 4 T 5 7 8 3 A N A N A N 4 2 3 0 2 4 3 A A N A N 6 T 5 1 9 0 3 B 6 T 0 0 5 4...

Page 10: ...0 MIN OPTION X SURFACE MOUNT CONNECTOR ONLY OPTION Z WITH MATING PLUG 0 53 13 5 0 41 10 5 1 20 30 5 4 31 109 5 1 574 40 0 2 13 54 0 3 228 82 0 3 70 94 0 0 18 4 5 0 217 5 50 4 Holes 36 50 927 0 MIN ON...

Page 11: ...DULE 0 53 13 5 3 83 97 3 4 66 118 4 OPTION K 2 80 71 1 3 06 11 7 1 53 38 9 OPTION A BULKHEAD CONNECTOR ONLY OPTION B WITH MATING PLUG CABLE GROMMET 1 97 50 0 3 67 93 2 Assembled 0 53 13 5 1 66 42 2 OP...

Reviews: