Digital Temperature Sensors (TMP-SDT-SEN, TMP-DOT-SEN & TMP-DFT-SEN)
Install Your Digital Temperature Sensor
Do not use this sensor in hazardous (classified) locations or life safety applications.
1. Locate the sensor (the end with the red cap, red silicone cover or clear
propylene glycol-filled tube) where you wish to measure temperature.
Shown here are the Digital Temperature Sensor placed behind a server
rack, the Digital Outdoor Sensor placed outside a window and the
Digital Fluid Temperature Sensor installed in a freezer.
2. If necessary to hold the sensor in place, mount it with a cable clip, Velcro or nylon tie.
3. Run the built-in 25' cable back to your Room Alert. Try to avoid running it near large
electromagnetic devices or fluorescent lights, which produce EMI that can interfere
with sensor readings.
4. Connect the sensor to a digital sensor port on your Room Alert.
Digital Temperature Sensor Features & Specifications
Environment Condition Monitored
Temperature
Digital Temperature Sensor
(TMP-SDT-SEN)
Indoor ambient temperature
Digital Outdoor Temperature Sensor
(TMP-DOT-SEN)
Outdoor ambient temperature
Digital Fluid Temperature Sensor
(TMP-DFT-SEN)
Fluid temperature
Type Of Sensor
Digital
Power Supply
Powered by Room Alert
Sensor Cable Type
RJ-11 (standard straight-through telephone cord)
Included
Yes (built-in)
Length
25' (50' and 100' also available)
Maximum Extendible Length
100' total
Temperature Range
-67º F to 257º F (-55º C to 125º C)
Accuracy
+/- 2º C
Resolution
0.0625º C
Compatible Products
Any Room Alert, TemPageR or Wireless Sensor Hub
AVT-171211-2.1.0