background image

  

Installation Note

 

Temperature & Environment Monitoring... 

Made Easy!

 

Flood Sensor - Cable

AVTECH

AVTECH’s Flood Sensor - Cable

 detects liquid when 

it bridges any pair of conductive threads twisted 

along the length of the patented orange cable.

The cable’s design allows you to position it in a 

variety of ways to detect water where it runs or 

settles, such as on the floor around valuable IT 

equipment; around a pipe that water runs down; 

or on a tray in a drop-ceiling beneath a dripping air 

conditioner.

Flood Sensor - Cable Package Contents

•  One (1) Flood Sensor box

•  One (1) Flood Cable w/ 25' RJ-11 leader

•  One (1) 25' speaker wire

•  One (1) AVTECH 5V power adapter

•  Two (2) mounting screws

Flood Sensor Box

Cable Fault

Detection 

Port

Flood 

Detection

Port

Right

Status

LED

Power

Port

Left

Front

RJ-11 Leader 

Port

Flood Sensor - Cable Features

Switch Ports

Flood Detection Port

Use this port to monitor the presence/absence of liquid. Its switch state becomes Open 

(alarm state) when liquid is detected.

Cable Fault Detection Port (Optional use)

If you wish to monitor the state of the Flood Sensor Cable itself, use this port. Its switch 

state becomes Open (alarm state) under these circumstances:

•  The RJ-11 leader is disconnected from the Flood Sensor box.

•  There’s a severe pinch, twist or other physical damage to the orange-twisted Flood Cable. 

•  Power is no longer being supplied to the Flood Sensor box.

Conductive

Threads

Flood

Cable

RJ-11 

Leader

Flood Box

Summary of Contents for RMA-F008-SEN

Page 1: ...re One 1 AVTECH 5V power adapter Two 2 mounting screws Flood Sensor Box Cable Fault Detection Port Flood Detection Port Right Status LED Power Port Left Front RJ 11 Leader Port Flood Sensor Cable Features Switch Ports Flood Detection Port Use this port to monitor the presence absence of liquid Its switch state becomes Open alarm state when liquid is detected Cable Fault Detection Port Optional use...

Page 2: ...ome in contact with liquid The box itself plugs into main power and must stay dry 1 Locate the Flood Sensor box away from water and above any anticipated water line the box itself plugs into main power and must stay dry You may mount it using the two included mounting screws 2 Run the orange twisted Flood Cable where water is most likely to run or settle Step 2 Connect the Flood Sensor Cable to th...

Page 3: ...t The leads are non polarized so you may connect either lead to either side of the open port Step 4 Connect your Flood Sensor Cable to a power source Use only the AVTECH 5V power adapter Others may damage the sensor 1 Connect the included power adapter to the power port on the Flood Sensor box 2 Then insert the power adapter plug in to a power source Notice that the Status LED lights up when the b...

Page 4: ... in Length 25 7 6 m Maximum Extendible Length 100 30 5 m Flood Cable Included Yes Length 8 2 4 m 24 7 3 m and custom lengths available Compatible Products Any Room Alert model Previous Generation Flood Sensor Cable In the previous generation of Flood Sensor Cable the orange twisted Flood Cable and the RJ 11 leader are separate components that must be fitted together To assemble the previous genera...

Page 5: ...X Label you may leave the default Switch Sen X or enter something more descriptive of up to 15 characters You may use the following characters in sensor labels letters numbers spaces hyphens underscores _ and periods 4 In Alarm On select the alarm state Open or Closed for your switch sensor You may find the alarm state of your switch sensor under the Features Specifications section of this Install...