Avtec TAKU Premier Ventilation Operator'S Manual Download Page 7

 

 

Installation Instructions  

Control Panel 

(if provided) 

 

WALL ATTACHMENT 
 
 
 
 
 
SURFACE MOUNTED 

 
 

RECESSED MOUNTED 

 
 
 
 
 
 
 
 

FRESH AIR SUPPLY FAN  
  (See Fig. 5 on page 8) 

 

Control panels are provided with all auto wash type ventilators (Model AW) and are 
optional with  all  baffle filter  type (AF) and modular grease extractor type  (AX). 
Control panels with models (AF) and (AX) do not have the auto wash plumbing assembly 
compartments. 

Control panel dimensions and connection detail are shown on the enclosed shop drawing. 
Panels may be surfaced mounted, partially recessed or fully recessed. 

 

Drill four holes in ventilator plumbing compartment as required. Be careful not to damage 
any components.  Avoid drilling into electrical compartments. Bolt to  wall  with anchor 
bolts or other acceptable means. Weight of control panel varies from 90 to 200 lbs. 

 

Cut hole in wall 1/2” greater than overall dimensions of the control box (shown on shop 
drawing). Spacers or support angles may be necessary to provide proper support. It is 
recommended  that  the  panel  be  bolted  to  wall  similar  to  method  used  for  surface 
mounted above. 

 

PAWS CONTROL PANEL 

The Programmable Automatic Wash Sequence (PAWS) panel is designed to control the 
operation of the ventilator exhaust and make-up air fans and wash the grease extraction 
plenum  with hot  water/detergent solution. The fan operation and wash sequence can be 
started and stopped manually or programmed for automatic operation. 

 

1. Check all local codes prior to installation. 

2. Supply fan inlet must be located to minimum 10’-0” from the exhaust fan. If 10’ is  
  not possible a 3’ vertical separation 

may*

 be acceptable. 

3. Cut and seal supply fan curb to roof. 

4. Duct shall be constructed of 22 or 24 gauge steel. Insulated duct material should be  
  used to eliminate frost and/or condensation. 

5. Duct shall be sized to provide air velocities not exceeding 1200 FPM. 

6. A volume control damper, provided in the duct just above the supply collar that  
  contains the UL listed   re damper, should be properly set to supply CFM required. 

7. If the hood is provided without the supply collar installed, it must be installed per the  
  instructions provided on the collar. 

8. Carefully place the supply fan on roof curb. Face supply fan inlet away from  
  prevailing winter wind. Electrical back draft damper is recommended in cold  
  climates. 

9. Bolt or screw fan to fan curb. 

10. Make all necessary electrical connections and check fan for proper rotation. 

NOTE: Fan will supply air running in wrong direction. 

*Dependent on local code requirements. 

 

7  

Summary of Contents for TAKU Premier Ventilation

Page 1: ...mage to make a notation on the delivery receipt It will be the responsibility of the consignee to file a claim with the carrier We recommend that you do so at once Information contained in this docume...

Page 2: ...1 Direct Draw Hoods page 11 Make Up Air Hoods page 11 Final Air Balance Make Up Air Hood back cover SAFETY PROCEDURES Do not attempt to service this unit yourself as removing covers may cause unnecess...

Page 3: ...is manual for future reference NOTICE Due to a continuous program of product improvement Avtec reserves the right to make changes in design and specifications without prior notice NOTICE Please read t...

Page 4: ...ng systems for duct hood protection They are available with or without an automatic re damper These models utilize high velocity removable grease extractors The canopy contains a hidden grease trough...

Page 5: ...ation and very carefully uncrate hood 3 Raise hood to proper hanging height 4 Suspend hood from adequate roof supports using 1 2 threaded rods with nuts and washers See Fig 1 5 Level hood left to righ...

Page 6: ...and airline cable on exhaust fan cap and metal curb Remember to leave ample room for fan to tilt back Fan will remain in tilted back position 7 Install grease collection box on side of fan that has g...

Page 7: ...designed to control the operation of the ventilator exhaust and make up air fans and wash the grease extraction plenum with hot water detergent solution The fan operation and wash sequence can be sta...

Page 8: ...vided HING 40 MINIMUM EXHAUST DUCTALL WELD CONSTRUCTION CEILING See Fig 6 1 Side skirts are offset at the top and have a 90 bend inward at the rear 2 Skirts are to overlap the outside of the hood Bolt...

Page 9: ...e panels are to be installed Retaining nuts and washers are installed on the studs prior to shipping 2 Loosen nuts on studs Slide enclosure panel under loosened nuts Holes in panels are open on end so...

Page 10: ...er panel by sliding tabs into slotted holes in upper panel screw bottom flange to wall 4 Caulk horizontal seam with NSF approved silicone sealant 5 When hood is hung it will rest on top panel NOTE Be...

Page 11: ...moving toward the dining area 9 Repeat steps 6 and 7 until all vapors are captured 10 Same as step 7 with bottom of next page NOTE The exhaust and supply if any air flow rates were established under...

Page 12: ...t to operating temperature 4 Produce large quantities of smoke or steam 5 Observe capture of vapors 6 If all vapors are not totally captured ne tune the system by adjusting the air volume control damp...

Reviews: