Avtec TAKU Premier Ventilation Operator'S Manual Download Page 11

 

 

Start / Check / Balance 

 

 

DIRECT DRAW HOODS 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

MAKE-UP AIR HOODS 

Exhaust Fan(s) 

 
 
 
 
 

SUPPLY FAN OR 

MAKE-UP AIR UNIT 

 

 

 

 

1. Close all doors and windows. 

2. Operate all exhaust fans, even fans serving other hoods, make-up air units and  
 

building HVAC. 

3. Turn on all cooking equipment under the hood to preheat to operating temperature. 

4. Produce large quantities of smoke. 

5. Observe capture of vapors. 

6. If all vapors are not captured, increase exhaust fan RPM. 

7. Check air pressure in kitchen. Pressure must be negative relative to dining  
  room pressure. 

8. Air velocities entering the kitchen from the dining room should not exceed 100 FPM.  
  No air should be moving toward the dining area. 

9. Repeat steps 6 and 7 until all vapors are captured. 

10. Same as step 7 with bottom of next page. 

NOTE: The exhaust and supply (if any) air flow rates were established under con- 
trolled laboratory conditions, and greater exhaust and/or lesser supply air may be 
required for complete vapor and smoke removal in specific installations. 

 
 

1. Open all doors and/or windows leading to outside. 

2. Start the exhaust fan only. Do not run the supply fan or make-up unit. 

3. Refer to drawings and/or UL information label on hood for proper CFM  
  requirements. 

4. Adjust speed of exhaust fan to obtain proper air velocities and CFM through  
  grease filters. 

1. Start the supply fan and/or make-up unit only. Do not run the exhaust fan.  

2. Refer to drawings or UL information label on hood for proper CFM requirements. 

  

11  

Summary of Contents for TAKU Premier Ventilation

Page 1: ...mage to make a notation on the delivery receipt It will be the responsibility of the consignee to file a claim with the carrier We recommend that you do so at once Information contained in this docume...

Page 2: ...1 Direct Draw Hoods page 11 Make Up Air Hoods page 11 Final Air Balance Make Up Air Hood back cover SAFETY PROCEDURES Do not attempt to service this unit yourself as removing covers may cause unnecess...

Page 3: ...is manual for future reference NOTICE Due to a continuous program of product improvement Avtec reserves the right to make changes in design and specifications without prior notice NOTICE Please read t...

Page 4: ...ng systems for duct hood protection They are available with or without an automatic re damper These models utilize high velocity removable grease extractors The canopy contains a hidden grease trough...

Page 5: ...ation and very carefully uncrate hood 3 Raise hood to proper hanging height 4 Suspend hood from adequate roof supports using 1 2 threaded rods with nuts and washers See Fig 1 5 Level hood left to righ...

Page 6: ...and airline cable on exhaust fan cap and metal curb Remember to leave ample room for fan to tilt back Fan will remain in tilted back position 7 Install grease collection box on side of fan that has g...

Page 7: ...designed to control the operation of the ventilator exhaust and make up air fans and wash the grease extraction plenum with hot water detergent solution The fan operation and wash sequence can be sta...

Page 8: ...vided HING 40 MINIMUM EXHAUST DUCTALL WELD CONSTRUCTION CEILING See Fig 6 1 Side skirts are offset at the top and have a 90 bend inward at the rear 2 Skirts are to overlap the outside of the hood Bolt...

Page 9: ...e panels are to be installed Retaining nuts and washers are installed on the studs prior to shipping 2 Loosen nuts on studs Slide enclosure panel under loosened nuts Holes in panels are open on end so...

Page 10: ...er panel by sliding tabs into slotted holes in upper panel screw bottom flange to wall 4 Caulk horizontal seam with NSF approved silicone sealant 5 When hood is hung it will rest on top panel NOTE Be...

Page 11: ...moving toward the dining area 9 Repeat steps 6 and 7 until all vapors are captured 10 Same as step 7 with bottom of next page NOTE The exhaust and supply if any air flow rates were established under...

Page 12: ...t to operating temperature 4 Produce large quantities of smoke or steam 5 Observe capture of vapors 6 If all vapors are not totally captured ne tune the system by adjusting the air volume control damp...

Reviews: