Attach gearbox to appropriate
ring. Attach Gear box ring
snugly to pipe. Tighten set
screws by hand until they
touch the pipe, then turn
them one-quarter turn
with the wrench.
Apply pressure to valve body,
AVT recommends 10Bar or
1.5 times maximum system
pressure.
8
7
9
Level valve and tighten bolts.
DO NOT tighten valve body
all the way down! Between
¼ (6MM) and 3/8 (9MM) inch
gap is the standard.
User Manual