Troubleshooting
If you encounter difficulties while using our
EZTouch I/O
Jr. device, please consult the table
below. Additional assistance is also available within the
Panel Editor Programming Software
Help
. Alternatively, you may also find answers to your questions in the operator interface
section of our website @ flash.ezautomation.net.
Problem
Possible
Cause
Suggested Action
Operation
Indicator LED
is off
Disconnected or
faulty power
source
Check and repair power
source.
Check the wiring for loose
contacts and secure them if
found.
(for 24 VDC powered
EZTouch I/O
Jr.)
Ensure that proper polarity
is observed.
Input power
level is outside
of
EZTouch I/O
Jr.'s
power rating
specifications
Ensure that the power
being
presented to the
EZTouch I/
O
terminal is within
the
.
Indicator LED is
blinking red
Outdated
firmware
Update
for unit.
Real Time Clock
function not
enabled
Low Battery
Remove old battery and
lithium battery.
Communication
No communication
with PC via
Ethernet
Disconnected or
loose cable
Check the wiring for loose
contacts and secure them if
found.
Wrong IP
Address
Update
associated with unit and
reattempt a connection.
No communication
with the PC (RS232
Port error)
Disconnected or
loose cable
Check the wiring for loose
contacts and secure them if
found.
Wrong/broken
cable
Ensure the correct
communication cable is
being used (PGMCBL).
Summary of Contents for EZTouch I/O Jr.
Page 1: ...Copyright 2012 by AVG Automation All Rights Reserved EZTouch I O Jr ...
Page 19: ...EZTouch I O Jr 19 52 Digital I O Specifications Analog Voltage Specifications and Wiring ...
Page 20: ...EZTouch I O Jr 20 52 Analog Current Specifications and Wiring ...
Page 21: ...EZTouch I O Jr 21 52 ...
Page 23: ...EZTouch I O Jr 23 52 Pinout Information for 26 Pin Connector ...
Page 24: ...EZTouch I O Jr 24 52 Pinout Information for 44 Pin Connector ...