Commissioning and Operation
98
AVENTICS
| PROFINET-IO | R412015162–BDL–001–AE
6.3
Test, diagnosis, and error messages
on the modules
6.3.1
Reading the diagnostic display on
the bus coupler
The LEDs on the front panel of the bus coupler show the
O
Before commissioning and during operation, regularly check
bus coupler functions by reading the diagnostic displays.
Table 21:
Definitions for diagnostic LEDs on the bus coupler
LED
Signal
Description
UL/DIA
Green
UL logic supply, OK; no overload
Red
W
Valve driver overload, message for the channels
W
Module error
W
System error (see Table 23 on page 101)
W
SREG short circuit
Off
No U
L
logic supply
UQ1
1)
4)
1)
Load supply U
Q1
:
– available (U
Q1
> threshold)
– Undervoltage (12 V < U
Q1
< threshold)
– Not available (U
Q1
< 12 V)
Green
Load supply U
Q1
available
Red
Diagnosis: Undervoltage
Off
Load supply U
Q1
not available (e.g. emergency OFF)
UQ2
2)
3)
4)
2)
Load supply U
Q2
:
– available (U
Q2
> threshold)
– Undervoltage (12 V < U
Q2
< threshold)
– Not available (U
Q2
< 12 V)
3)
In the CMS-B-BPIO_32-7/8" version, LED U
Q2
does not light up.
4)
The switching point (voltage) for the U
Q1
and U
Q2
LEDs cannot be changed.
Green
Load supply U
Q2
available
Red
Diagnosis: Undervoltage
Off
Load supply U
Q2
not available (e.g. emergency OFF)
BF
Red
Bus error
LNK/ACT 1
Yellow
Active data exchange with network
Green
Port connection to PROFINET-IO network active
LNK/ACT 2
Yellow
Active data exchange with network
Green
Port connection to PROFINET-IO network active
Summary of Contents for PROFINET-IO
Page 2: ......
Page 114: ...Disposal 114 AVENTICS PROFINET IO R412015162 BDL 001 AE...
Page 174: ...Elimination des d chets 174 AVENTICS PROFINET IO R412015162 BDL 001 AE...
Page 236: ...ndice 236 AVENTICS PROFINET IO R412015162 BDL 001 AE...
Page 347: ...Nyckelordsregister AVENTICS PROFINET IO R412015162 BDL 001 AE 347 Svenska...