Assembly
80
AVENTICS
| PROFINET-IO | R412015162–BDL–001–AE
5.3.2
Connecting the bus coupler
1.
Set up the correct pin assignment (see Table 5 on page 79)
on the plug connections if you do not use pre-assembled
cables.
2.
Connect the incoming bus connection to X71 (
2
) and connect
the module with a hub or switch if further slaves are to be
connected.
Connections X71 and X72 are equal.
3.
Connect the shield on both sides of the bus cable directly to
the plug housing (EMC housing), if non-pre-assembled
cables and plugs with metal housing are used. This protects
data lines from terminal interference.
Ensure that the plug housing is securely fitted to the bus
coupler housing.
5.3.3
Pin assignment for the bus coupler with
M12 plug for power supply
When connecting the logic and load supply of the bus coupler,
ensure pin assignment according to Table 6.
W
U
L
, U
Q1
and U
Q2
are galvanically connected to one another.
W
Groups of valves can be supplied with power via the U
Q1
and
U
Q2
valve supplies.
W
The S4, S5, S6, and S7 sliding switches are used to assign
the valve groups (4 or 8 valves) (see “Assigning the valve
supply on the bus coupler with M12 plug” on page 87). It is
therefore possible to switch off the valves before or after an
emergency OFF.
1
2
1
2
2
1
4
3
PO WE R
X10
Table 7:
Assignment of the X10 plug (POWER), M12, A-coded
Pin
X10
Assignment
1
UL
Power supply for bus coupler logic and sensor
supply for digital input modules
2
U
Q1
First valve power supply
3
OV
Ground for U
L
, U
Q1
and U
Q2
4
U
Q2
Second valve power supply
Summary of Contents for PROFINET-IO
Page 2: ......
Page 114: ...Disposal 114 AVENTICS PROFINET IO R412015162 BDL 001 AE...
Page 174: ...Elimination des d chets 174 AVENTICS PROFINET IO R412015162 BDL 001 AE...
Page 236: ...ndice 236 AVENTICS PROFINET IO R412015162 BDL 001 AE...
Page 347: ...Nyckelordsregister AVENTICS PROFINET IO R412015162 BDL 001 AE 347 Svenska...