CHAPTER 5
Instructions, use and maintenance manual
Page 64
D r a g o P 1
5.9.4.2.
LPG CONNECTION
Burner supply using LPG can be via:
•
a 500-litre tank, equipped with a first stage pressure reducer and pressure regulator (minimum 12 kg/h);
•
cylinders, with a capacity of at least 50 kg, equipped with a manifold with a 30 mm diameter with the following
equipment: safety valve, pressure gauge, first stage reducer APZ 30-60 Kg/h calibrated to 1.5 bar, pressure
regulator 12 kg/h calibrated to 30 mbar (visible from the special pressure gauge) and 1/2” piping.
All accessories needed for burner connection (with systems that use cylinders) are sold separately; please
contact AVANZINI BRUCIATORI s.r.l. for information on how to purchase these accessories.
6
7
4
2
3
1
5
Gas ramp -
LPG
1
ø30 manifold with pressure gauge and safety valve.
2
Hoses to the cylinders with Italian coupling.
3
APZ 30-60 kg reducer calibrated at 1.5 bar.
4
12 kg pressure regulator adjusted at 30 mbar.
5
Outfeed pressure gauge.
6
1/2 fitting hose to burner.
7
Burner Drago P1.
CAUTION!
For component No.2 (flexible hose to the cylinders), it is possible that the connections provided by
us are not compatible with the cylinders that the customer is able to find locally; the customer is
responsible for the cylinder connection.