Installation and configuration
AutroSense Micra 10 Aspirating Smoke Detector Installers Handbook
13
No more than one air handling unit may be protected with one detector. In this
application, ensure that the sampling pipe is raised clear of high velocity air in the
immediate vicinity of the air intake grill on standoff posts as shown in Figure 5.
Figure 5: Air handling unit in vicinity of the detector (exhaust shown for clarity)
(1) Incorrect location
(2) Detector
(3) Sampling pipe
(4) Standoff posts
(5) Correct location
(6)
Detector
(7) AHU
(8) Equipment cabinet
(9) Direction of smoke