![Autronica AutroFlame X33AF Instructions Manual Download Page 28](http://html.mh-extra.com/html/autronica/autroflame-x33af/autroflame-x33af_instructions-manual_3023449028.webp)
Instructions, AutroFlame X33AF, 116-P-X33AF/IGB, rev . E, 2013-08-13, P/N 95-8625-17 .1, Rev: 2/13
Autronica Fire and Security AS
Page A-5
FM Approval and Performance Report – Continued
FALSE ALARM IMMUNITY
Very High Sensitivity
False Alarm Source
Distance
feet (m)
Modulated Response
Unmodulated Response
Sunlight, direct, reflected
—
No alarm
No alarm
Vibration
N/A
No alarm
N/A
Radio frequency interference
1 (0 .3)
No alarm (keyed)
No alarm (steady)
Arc welding
40 (12 .2)
No alarm
No alarm
6 kw heater
3 (0 .9)
No alarm
No alarm
250 w vapor lamp
3 (0 .9)
No alarm
No alarm
300 w incandescent lamp
3 (0 .9)
No alarm
No alarm
500 w unshielded quartz halogen lamp
8 (2 .4)
No alarm
No alarm
500 w shielded quartz halogen lamp
8 (2 .4)
No alarm
No alarm
1500 w electric radiant heater
3 (0 .9)
No alarm
No alarm
Two 34 w fluorescent lamps
3 (0 .9)
No alarm
No alarm
Medium Sensitivity
False Alarm Source
Distance
feet (m)
Modulated Response
Unmodulated Response
Sunlight, direct, reflected
—
No alarm
No alarm
Vibration
N/A
No alarm
N/A
Radio frequency interference
1 (0 .3)
No alarm (keyed)
No alarm (steady)
Arc welding
10 (3)
No alarm
No alarm
6 kw heater
3 (0 .9)
No alarm
No alarm
250 w vapor lamp
3 (0 .9)
No alarm
No alarm
300 w incandescent lamp
3 (0 .9)
No alarm
No alarm
500 w unshielded quartz halogen lamp
8 (2 .4)
No alarm
No alarm
500 w shielded quartz halogen lamp
3 (0 .9)
No alarm
No alarm
1500 w electric radiant heater
3 (0 .9)
No alarm
No alarm
Two 34 w fluorescent lamps
3 (0 .9)
No alarm
No alarm
T-Low Sensitivity
False Alarm Source
Distance
feet (m)
Modulated Response
Unmodulated Response
Sunlight, direct, reflected
—
No alarm
No alarm
Vibration
—
No alarm
No alarm
Arc welding
5 (1 .5)
No alarm
No alarm
6 kw heater
3 (0 .9)
No alarm
No alarm
70 w sodium vapor
3 (0 .9)
No alarm
No alarm
250 w vapor lamp
3 (0 .9)
No alarm
No alarm
300 w incandescent lamp
3 (0 .9)
No alarm
No alarm
500 w shielded quartz halogen lamp
3 (0 .9)
No alarm
No alarm
1500 w electric radiant heater
3 (0 .9)
No alarm
No alarm
Two 34 w fluorescent lamps
3 (0 .9)
No alarm
No alarm
Low Sensitivity
False Alarm Source
Distance
feet (m)
Modulated Response
Unmodulated Response
Sunlight, direct, reflected
—
No alarm
No alarm
Vibration
—
No alarm
No alarm
Radio frequency interference
N/A
No alarm
N/A
Arc welding
5 (1 .5)
No alarm
No alarm
6 kw heater
3 (0 .9)
No alarm
No alarm
250 w vapor lamp
3 (0 .9)
No alarm
No alarm
300 w incandescent lamp
3 (0 .9)
No alarm
No alarm
500 w shielded quartz halogen lamp
3 (0 .9)
No alarm
No alarm
1500 w electric radiant heater
3 (0 .9)
No alarm
No alarm
Two 34 w fluorescent lamps
3 (0 .9)
No alarm
No alarm