X33AF Reflector Plates
X33AF models are supplied with either a black or a
stainless steel reflector plate . These plates are not
interchangeable . Order the replacement that matches the
reflector plate on your X33AF flame detector .
PERIODIC CHECKOUT PROCEDURE
In compliance with SIL 2, a checkout of the system using the
Mag
oi
or Man
oi
feature should be performed regularly
to ensure that the system is operating properly . Refer to
Table 1 in the X33AF Safety Manual (116-P-X33AF-SIL2/
CGB) for frequency of proof tests . To test the system,
perform the “Fire Alarm Test” as described in the “Startup
Procedure” section of this manual .
CLOCK BATTERY
The real time clock has a backup battery that will operate
the clock with no external power for nominally 10 years .
It is recommended that the battery be replaced every
7 years . Return the device to the factory for battery
replacement if needed .
NOTE
If the backup battery is depleted, there is no effect
on the operation of the flame detector, but the time
stamping of the data log may be affected.
FEATURES
•
Long detection range to carbonaceous fires .
•
Unequaled false alarm rejection .
•
Responds to a fire in the presence of modulated
blackbody radiation (i .e . heaters, ovens, turbines)
without false alarm .
•
Microprocessor controlled heated optics for increased
resistance to moisture and ice
•
Automatic, manual or magnetic optical integrity (
oi
)
testing
•
Easily replaceable
oi
plate .
•
Fire, fault and auxiliary relays standard
•
0 to 20 mA isolated output (optional)
•
HART communication (optional)
•
EDT/DMT capable
•
Multiple sensitivity levels
•
A tricolor LED on the detector faceplate indicates
normal condition and notifies personnel of fire alarm
or fault conditions
•
Operates under adverse weather conditions and in
dirty environments
•
Mounting arm allows easy sighting
•
Integral wiring compartment for ease of installation .
•
Explosion-proof/flame-proof detector housing . Meets
FM, CSA, ATEX Directive and CE certification
requirements
•
Class A wiring per NFPA-72
•
Meets NFPA-33 response requirement for under 0 .5
second (available when model selected)
•
5 year warranty
•
RFI and EMC Directive compliant
ASSOCIATED MANUALS
List of X33AF related manuals:
TITLE
FORM NUMBER
SIL 2 (Safety)
116-P-X33AF-SIL2/CGB
HART Addendum
116-P-X33AFADDENDUM/YGB,