background image

 Major Products

Parameter

Display Description

Input sensor

IN-T

Setting range: Refer to '  Input Sensor And Temperature Range'.

  If changing input sensor, SV, 

IN-B

H-SV

L-SV

AL1

AL2

LBaT

,  

LBaB

AHYS

 parameter values are initialized. 

Temperature unit

UNIT

?C

    

?F

  If changing temperature unit, SV, 

IN-B

H-SV

L-SV

AL1

AL2

LBaT

LBaB

AHYS

 parameter values are initialized. 

Input correction

IN-B

Setting range

 

KCaH

JIcH

LIcH

TCcH

RPR

SRP

DPtH

CUsH

:-999 to 999

/

 

KCaL

JIcL

LIcL

TCcL

DPtL

CUsL

: -199.9 to 999.9

/

Input digital filter

MAvF

Setting range: 0.1 to 120.0 sec.

SV low-limit value

L-SV

Setting range: Within the rated temperature range by input sensor

L-SV

(

H-SV

-1digit)] 

When changing SV lower limit value, if  SV   

ㅑL

-SV

, SV is initialized as  

L

-SV

.

 In case of changing input sensor type[

IN-T

], it changes automatically as min. 

value of the changed input sensor.

SV high-limit 

value

H-SV

Setting range: Within the rated temperature range by input sensor[

 

H-SV

 (

L-SV

+1digit)]

When changing SV higher limit value, if SV   

H-SV

, SV is initialized as 

H-SV.

 In case of changing input sensor type [

IN-T

], it changes automatically as 

max. value of the changed input sensor.

Control output 

operation

O-FT

HEAT 

 

 COOLㅑㅑ

When changing control output operation, 

ErMV

 is initialized. 

Control type

ㅑC-MD

PID 

 

 ONOF

ㅑㅑㅑㅑㅑㅑㅑㅑㅑ

 

When changing control type, 

ErMV 

is initialized (control output MV is 

below 100%) and 

DI-T

 turns OFF automatically.  

Control output type

OUT

RLY 

 

 SSR

SSR drive output 

method

ㅑㅑㅑSSrM

STND 

  

CYCL 

  

PHAS 

  It is displayed when selecting control output [

OUT

] as [

SSR

].   

It is not displayed for AC/DC power model 

  (

T

S

4

 

 

-22R).

Control cycle

ㅑT

Setting range: 0.5 to120.0 sec. 

  In case of Relay drive output [

RLY

] of control output [

OUT

], it is set as 

20.0  sec. In case of SSR drive output [

SSR

] of that, it is set as 2.0 sec.

 

T

 is not displayed when SSR drive output [

SSR.M

] method is set as 

CYCL

PHAS

.

AL1 alarm 

operation mode

AL-1

 ㅑㅑAM)

_  

   AM!

A   

   AM@

A  

   AM^

  

   SBa

  

   LBa

A

AM!

 

AM!

B

 

 AM!

C

 

 

AM!

 AM!

E

 

 AM!

F

For more details refer to   Functions 6. Alarm.

 Black: Flashes, Gray: Fixed

 When changing AL1, AL2 alarm operation mode, AL1, AL2 alarm 

    temperature value are initialized. 

AL2 alarm 

operation mode

AL-2

Alarm output 

hysteresis

ㅑAHYS

Setting range: Refer to   Functions 4. Alarm output hysteresis. 

  

AHYS

 is not displayed when AL1, AL2 alarm operation mode [

AL-1

,  

 

AL-2

] is set as [

AM0._

SBa

LBa

].  

LBA monitoring 

time

LBaT

Setting range: 0 to 9999 sec.

 

'0' is set, loop break alarm function is OFF. 

  

LBaT

 is displayed when AL1, AL2 alarm operation mode [

AL-1

  

AL-2

] is set as 

LBa

.

LBA monitoring

range

LBaB

Setting range: 0 to 999(0.0 to 999.9)

, '0' is set, loop break alarm function is OFF. 

  

LBaB

 is displayed when AL1, AL2 alarm operation mode [

AL-1

 

AL-2

] is set as 

LBa

 and 

LBaT

 is not '0'. 

Digital input key

DI-K

ㅑㅑSTOP

  

  

AlRE  

  

AT  

  

OFF

Press       keys for 3 sec. and it executes the set function.

For more information, refer to   Functions 5. Digital input key. 

 When control type [

C-MD

] is 

ONOF

AT

 is not displayed.    

Control output 

MV in case of 

input break error

ErMV

Setting range 0.0 to 100.0%

  Only 0.0, 100% are displayed when control type [

C-MD

] is set as 

ONOF

.

  When changing PID control to ON/OFF control, if MV is below 

100.0%, it is initialized as 0.0%. 

Parameter lock

LOC

OFF

  

  

LOC1  

  

LOC2  

  

LOC3

LOC1

: Locks parameter 2 group, 

LOC2

: Locks parameter 1, 2 group

LOC3

: Locks parameter 1, 2 group and SV setting

 

Parameter setting values are still possible to check when parameter lock is set.

 Cautions during Use

 Factory Default

2. Parameter 2group

3. Parameter 1 group

Parameter

Display Description

AL1 alarm temp.

AL1

Setting range: Deviation alarm(-F.S to F.S), Absolute value alarm(temperature range) 

In case alarm operation mode [

AL-1

AL-2

] of Parameter 2 group

  AMㅑ)_

/

SBa

 / 

LBA

, no parameters is displayed.

AL2 alarm temp.

AL2

Auto tuning

AT

OFF

    

ON   

Front AT indicator flashes during auto tuning operation. 

Proportional band

ㅑP

Setting range: 0.1 to 999.9

Integral time

I

Setting range: 0 to 9999 sec. Integral operation is OFF when set value is "0". 

Derivative time

D

Setting range: 0 to 9999 sec. Derivative operation is OFF when set value is "0".

Manual reset

REST

Setting range: 0.0 to 100.0%

/ It is displayed in P/PD control.

Hysteresis

HYS

Setting range

 

KCaH

JIcH

LIcH

TCcH

RPR

SRP

DPtH

CUsH

1 to 100

 

KCaL

JIcL

LIcL

TCcL

DPtL

CUsL

0.1 to 50.0

 It is displayed when control type [

C-MD

] of parameter 2 group is set 

ONOF

.

4. SV setting

You can set the temperature to control with 

 

         keys. 

Setting range is within SV lower limit value [

L-SV

] to SV higher limit value [

H-SV

].

E.g.) In case of changing set temperature from 210ºC to 250ºC

 Functions

6. Alarm

5. Digital input key ( +  3sec.) [

DI-K

]

 

AM!A

 

Alarm 

operation

Alarm 

option

3)Sensor break alarm

The function that alarm output will be ON when sensor is not connected or when sensor's disconnection

is detected during temperature controlling. You can check whether the sensor is connected with buzzer 

or other units using alarm output contact. It is selectable between standard alarm [

SBaA

] or alarm latch 

[

SBaB

].

4)Loop break alarm(LBA)

It checks control loop and outputs alarm by temperature change of the subject. For heating 

control(cooling control), when control output MV is 100%(0% for cooling control) and PV is not 

increased over than LBA detection band [

LBaB

] during LBA monitoring time [

LBaT

], or when control 

output MV is 0%(100% for cooling control) and PV is not decreased below than LBA detection band 

[

LBaB

] during LBA monitoring time [

LBaT

], alarm output turns ON. 

10. Error

Display

Description

Troubleshooting

OPEN

Flashes if input sensor is disconnected or sensor is not connected.  Check input sensor state. 

HHHH

Flashes if measured sensor input is higher than temperature range. When input is within the rated 

temperature range, this display 

disappears. 

LLLL

Flashes if mesured sensor input is lower than temperature range

Temperature controller

 

(T

S

4 series)

Power

100-240VAC

50/60Hz 

SSR drive output

(12VDC)

SSR Module

Load

  When selecting phase or cycle control mode, 

the power supply for load and temperature 

controller must be the same.

  In case of selecting  PID control type and phase [

PHAS

] / cycle [

PHAS

] control output modes, control 

cycle [

T

] is not allowed to set.

  For AC/DC power model (

  

T

S

 

 

-22R), this parameter is not displayed and it is available only 

standard control by relay or SSR.

1)Standard ON/OFF control mode

 [

STND

]

A mode to control the load in the same way as Relay output type. 

(ON: output level 100%, OFF: output level 0%)

7. Manual reset[

REST

]

When selecting P/PD control mode, certain temperature

difference exists even after PV reaches stable status  because 

heater's rising and falling time is inconsistent due to thermal 

characteristics of controlled objects, such as  heat capacity, 

heater capacity. This temperature difference is called offset 

and manual reset  [

REST

] function is to set/correct offset. 

When PV and SV are equal, reset value is 50.0%. After  control

is stable, PV is lower than SV, reset value is over  50.0% or PV 

is higher than SV, reset value is below 50.0%.

Set below 50.0 as reset value 

Set over 50.0 as reset value 

Offset

SV

Offset

Measured value

·Manual reset [

REST

] by control result

Start control 

to 

When control output MV is 100%, PV is increased over than LBA detection band [

LBaB

] during 

LBA monitoring time [

LBaT

].  

 to 

The status of changing control output MV (LBA monitoring time is reset.)  

 to 

When control output MV is 0% and PV is not decreased below than LBA detection band [

LBaB

during LBA monitoring time [

LBaT

], loop break alarm (LBA) turns ON after LBA monitoring time.

 to 

Control output MV is 0% and loop break alarm (LBA) turns and maintains ON.

 to 

The status of changing control output MV (LBA monitoring time is reset.)  

 to 

When control output MV is 100% and PV is not increased over than LBA detection band [

LBaB

during LBA monitoring time [

LBaT

], loop break alarm (LBA) turns ON after LBA monitoring time.

 to 

When control output MV is 100% and PV is increased over than LBA detection band [

LBaB

] during 

LBA monitoring time [

LBaT

], loop break alarm (LBA) turns OFF after LBA monitoring time.

 

to

 

The status of changing control output MV (LBA monitoring time is reset.)  

2)Alarm opetion

Option Name

Description

ㅑㅑㅑㅑㅑㅑAM

.A

Standard 

alarm

If it is an alarm condition, alarm output is ON. If it is a clear alarm condition, alarm output 

is OFF.

AM

ㅑ.ㅑㅑㅑㅑㅑㅑㅑㅑㅑㅑB

Alarm latch If it is an alarm condition, alarm output is ON and maintains ON status. 

(Alarm output HOLD) 

AM .C

Standby 

sequence 1

First alarm condition is ignored and from second alarm condition, standard alarm 

operates. When power is supplied and it is an alarm condition, this first alarm condition 

is ignored and from the second alarm condition, standard alarm operates. 

AM .D

Alarm latch 

and standby 

sequence 1

If it is an alarm condition, it operates both alarm latch and standby sequence. When 

power is supplied and it is an alarm condition, this first alarm condition is ignored and 

from the second alarm condition, alarm latch operates. 

AM .E

Standby 

sequence 2

First alarm condition is ignored and from second alarm condition, standard alarm 

operates. When re-applied standby sequence and if it is alarm condition, alarm output 

does not turn ON. After clearing alarm condition, standard alarm operates.

AM .F

Alarm latch 

and standby 

sequence 2

Basic operation is same as alarm latch and standby sequence1. It operates not only by 

power ON/OFF, but also alarm setting value, or alarm option changing. When re-applied 

standby sequence and if it is alarm condition, alarm output does not turn ON. After 

clearing alarm condition, alarm latch operates.

2)Cycle control mode 

[

CYCL

]

A mode to control the load  by repeating output ON / OFF according to the rate of output within setting 

cycle. Having improved ON / OFF noise feature by Zero Cross type.

3)Phase control mode 

PHAS

A mode to control the load by controlling the phase within AC half cycle. Serial control is available.

RANDOM Turn-on type SSR must be used for this mode.

4. Alarm output hysteresis [

AHYS

]

It displays alarm output ON and OFF interval and hysteresis is applied to both AL1 OUT and AL2 OUT.

 

KCaH

JIcH

,

 ㅑLIcH

,

 TCcH

,

 RPR

SPR

DPtH

,

 ㅑCUsH

: 1 to 100

 

KCaL

,

 JIcL

,

 LIcL

,

 TCcL

,

 DPtL

,

 CUsL

: 0.1 to 50.0

E.g.) AL1 alarm operation[

AL-1

]: 

AM#A

AL1 alarm operation[

AL1

]: 10ºC 

Alarm output hysteresis[

AHYS

]: 4 210ºC

SV 200ºC

190ºC

Temp.

Time

210

190

194

206

AL1 OUT ON

OFF

AHYS

: 4

AHYS

: 4

PV

1)Alarm operation

 When executing auto-tuning, LBA detection band[

LBaB

] and LBA monitoring time are automatically set 

based on auto tuning value. When alarm operation mode [

AL-1

AL-2

] is set as loop break alarm(LBA)

[

LBa

], LBA detection band [

LBaB

] and LBA monitoring time [

LBaT

] parameter is displayed. 

LBa

 

ㅑLBa

A

SBa

 

SBa

A

 key: Moves parameter and saves the set,   key: Moves digit, 

 or   key: Changes the set

8. Input correction

[

IN-B

]

Controller itself does not have errors but there may be error by external input temperature sensor. 

This function is for correcting this error. 

E.g.)  If actual temperature is 80ºC but controller displays 78ºC, set input correction value [

IN-B

] as 

'002' and controller displays 80ºC.

  As the result of input correction, if current temperature value (PV) is over each temperature range 

of input sensor, it displays '

HHHH

' or '

LLLL

'.

9. Input digital filte

[

MAvF

]

If current temperature (PV) is fluctuating repeatedly by rapid change of input signal, it reflects to MV 

and stable control is impossible. Therefore, digital filter function stabilizes current temperature value. 

For example, set input digital filter value as 0.4 sec, and it applies digital filter to input values during 0.4     

sec and displays this values. Current temperature may be different by actual input value. 

1. Auto tuning [

AT

]

Auto tuning measures the control subject’s thermal characteristics and thermal response rate, and then 

determines the necessary PID time constant. (When control type[

C-MD

] is set as 

PID

, it is displayed.) 

Application of the PID time constant realizes fast response and high precision temperature control. 

If error [

OPEN

] occurs during auto tuning, it stops this operation automatically. To stop auto tuning, 

change  the set as [

OFF

]. (It maintains P, I, D values of before auto tuning.) 

2. Hysteresis [

HYS

]

In case of ON/OFF control, set between ON and OFF intervals 

as hysteresis. (When control type [

C-MD

] is set as 

ONOF

, it 

is displayed.) If hysteresis is too small, it may cause control 

output  hunting (takeoff, chattering) by external noise, etc. 

Time

Hysteresis

[

HYS

]

ON

Heating operation

OFF

Temperature

SV

 Condition of re-applied standby sequence for standby sequence 1, alarm latch and standby sequence 1: Power ON

    Condition of re-applied standby sequence for standby sequence 2, alarm latch and standby sequence 2: Power ON, 

    changing set temperature, alarm temperature (

AL1

AL2

) or alarm operation (

AL-1

,

 AL-2

), switching STOP mode  

    to RUN mode.

 key: Moves parameter and saves the set, 

 key: Moves digit,   or   key: Changes the set

ON

ON

OFF

OFF

AC

OUT

50Cycle

50Cycle

50%

80%

AC

OUT

10%

50%

AC

OUT

Mode Name

Alarm operation

Description

AM)_

-

-

No alarm output 

AM!

Deviation

high-limit

alarm

SV         

100

PV

110

OFF

ON

H

PV

90

SV

100

OFF

ON

H

If deviation between PV and SV 

as high-limit is higher than set 

value of deviation temperature, 

the alarm output will be ON.

High deviation: Set as 10

High deviation: Set as -10

AM@

Deviation

low-limit

alarm

PV

90

SV

100

OFF

ON

H

SV

100

PV

110

OFF

ON

H

If deviation between PV and SV 

as low-limit is higher than set 

value of deviation temperature, 

the alarm output will be ON.

Lower deviation: Set as 10

Lower deviation: Set as -10

 

AM#

Deviation

high/low-

limit

alarm

PV

90

PV

110

SV

100

OFF

ON

ON

H

H

If deviation between PV and SV 

as high/low-limit is higher than set 

value of deviation temperature, 

the alarm output will be ON.

High/Lower deviation: Set as 10

AM$

Deviation

high/low-

limit

reserve 

alarm

PV

90

PV

110

SV

100

OFF

OFF

ON

H

H

If deviation between PV and SV 

as high/low-limit is higher than set 

value of deviation temperature, 

the alarm output will be OFF.

High/Lower deviation: Set as 10

AM%

Absolute

value high

limit alarm

PV

90

SV

100

OFF

ON

H

SV

100

PV

110

OFF

ON

H

If PV is higher than the absolute 

value, the output will be ON.

Absolute-value Alarm:

Set as 90

 

Absolute-value Alarm:

Set as 110

AM^

Absolute

value low

limit alarm

PV

90

SV

100

OFF

ON

H

SV

100

PV

110

OFF

ON

H

If PV is lower than the absolute 

value, the output will be ON.

Absolute-value Alarm:

Set as 90

Absolute-value Alarm:

Set as 110

SBa

Sensor 

break alarm

-

It will be ON when it detects 

sensor disconnection.

LBa

Loop break 

alarm

-

It will be ON when it detects loop 

break.

 H: Alarm output hysteresis[

AHYS

3. Parameter 2 group

2. Parameter 1 group

1. SV setting

Parameter Default

Parameter Default

Parameter Default

Parameter Default

IN-T

KCaH

H-SV

1200

T

02)0

LBaB

0002

UNIT

?C

O-FT

HEAT

AL-1

AMiA

DI-K

STOP

IN-B

0000

C-MD

PID

LA-2

Am@A

ErMV

00)0

MAvF

00)1

OUT

RLY

AHYS

001

LOC

OFF

L-SV

-050

SSrM

STND

LBaT

0000

Parameter Default

Parameter Default

Parameter Default

Parameter Default

AL1

1250

AT

OFF

I

0000

REST

05)0

AL2

1250

P

01)0

D

0000

HYS

002

Parameter Default
-

0

 

Installation

 TCN4S(48×48mm) Series

Other Series

 Insert product into a panel, fasten bracket by pushing with tools as shown above.

  The AC/DC voltage models do not have SSR drive output method[

SSrM

]. In case of control output 

 [ 

OUT

] , if set as 

SSR

, it supports only ON/OFF output. 

Set both alarm operation and alarm option by combining. 

Alarm outputs are two and each one operates individually.   

When the current temperature is out of alarm range, alarm clears 

automatically. If alarm option is alarm latch or alarm latch and standby 

sequence 1/2, press digital input key( +  3 sec., digital input 

key[

DI-K

] of parameter 2 group set as 

AlRE

), or turn OFF the power 

and turn ON to clear alarm.

Parameter

Operation

OFF

OFF

It does not use digital input key function. 

RUN/STOP

STOP

Pauses control output. Auxiliary output (except loop break alarm, sensor break alarm)

except Control output operates as setting. Hold the digital input keys for 3 sec. to restart. 

RUN

RUN

t

t

t

t

STOP

STOP

RUN

Digital input key

(t: over 3 sec.)

Clear alarm

AlRE

Clears alarm output by force. 

(only when alarm option is alarm latch, or alarm latch and standby sequence 1/2 .

)

This function is applied when present value is out of alarm operation range but alarm 

output is ON. 

Alarm operates normally right after clearing alarm.  

Auto-tuning

AT

Starts/Stops auto-tuning. This function is same as auto-tuning[

AT

] of parameter 1 group. 

(You can start auto-tuning [

AT

] of parameter 1 group and stop it by digital input key.)

※ 

This parameter 

AT

 appears only when 

control method 

[

C-MD

parameter 2 group

 

is set as 

PID

. When 

control method 

[

C-MD

parameter 2 group

 is set as 

ONOF

, this 

parameter is changed as 

OFF

3. SSR drive output selection(SSRP function) [

SSrM

]

● 

 

SSRP function is selectable one of standard ON/OFF control, cycle control, phase control by utilizing 

standard SSR drive output.

● 

Realizing high accuracy and cost effective temperature control as linear output(cycle control and 

phase control).

● 

Select one of standard ON/OFF control [

STND

], cycle control [

CYCL

] , phase control [

PHAS

] at [

SSrM

parameter of parameter 2 group.  For cycle control, connect zero cross turn-on SSR or random 

turn-on SSR. For phase control, connect random turn-on SSR.     

5. Parameter reset

Change SV 
by  ,  ,   keys

Press any key among 

,  ,  ,   once. 

RUN mode

SV setting mode

 Completes 

SV setting

Check SV

Reset all parameters as factory default. Hold the front  + + keys for 5 sec., to enter parameter reset 

[

INIT

] parameter. Select '

YES

' and all parameters are reset as factory default. Select ‘

NO

’ and previous 

settings are maintained. If setting parameter lock [

LOC

] or processing auto-tuning, parameter reset is 

unavailable. 

 Photoelectric Sensors  Temperature Controllers

 Fiber Optic Sensors

 Temperature/Humidity Transducers

 Door Sensors

 SSRs/Power Controllers

 Door Side Sensors

 Counters 

 Area Sensors

 Timers

 Proximity Sensors

 Panel Meters

 Pressure Sensors

 Tachometer/Pulse (Rate) Meters

 Rotary Encoders

 Display Units

 Connector/Sockets

 Sensor Controllers

 Switching Mode Power Supplies

 Control Switches/Lamps/Buzzers

 I/O Terminal Blocks & Cables

 Stepper Motors/Drivers/Motion Controllers

 Graphic/Logic Panels

 Field Network Devices

 Laser Marking System (Fiber, Co

, Nd: YAG)

 Laser Welding/Cutting System

1.  Follow instructions in 'Cautions during Use'. Otherwise, It may cause unexpected accidents.

2.  Check the polarity of the terminals before wiring the temperature sensor. 

For RTD temperature sensor, wire it as 3-wire type, using cables in same thickness and length. 

For thermocouple (CT) temperature sensor, use the designated compensation wire for extending wire.

3.  Keep away from high voltage lines or power lines to prevent inductive noise. 

In case installing power line and input signal line closely, use line filter or varistor at power line and 

shielded wire at input signal line. 

Do not use near the equipment which generates strong magnetic force or high frequency noise.

4.  Install a power switch or circuit breaker in the easily accessible place for supplying or disconnecting 

the power.

5.  Do not use the unit for other purpose (e.g. voltmeter, ammeter), but temperature controller.

6.  When changing the input sensor, turn off the power first before changing.

 

After changing the input sensor, modify the value of the corresponding parameter.

7.  24VAC, 24-48VDC power supply should be insulated and limited voltage/current or Class 2, SELV

power supply device.

8.  Make a required space around the unit for radiation of heat. 

For accurate temperature measurement, warm up the unit over 20 min after turning on the power.

9.  Make sure that power supply voltage reaches to the rated voltage within 2 sec after supplying power.

10.  Do not wire to terminals which are not used.

11.  This unit may be used in the following environments.

Indoors (in the environment condition rated in 'Specifications')      

Altitude max. 2,000m

Pollution degree 2

Installation category II