-|Transparent Guide|-

DRW180136AE

3-Phase Slim  

Power Controllers

SPR3 Series

PRODUCT MANUAL

For your safety, read and follow the considerations written in the instruction 
manual, other manuals and Autonics website.

The specifications, dimensions, etc. are subject to change without notice for product 
improvement. Some models may be discontinued without notice. 

Features

• 

Slim and elegant design

• 

LED display allows real-time monitoring of control input, load voltage, load current, 
load power, load resistance, and heat-sink temperature

• 

Stable control with feedback control (constant current, constant voltage, constant 

power)

• 

Communication output models available: RS485 (Modbus RTU)

• 

Parameter configuration via PCs (RS485) : Free device management software 
(DAQMaster)

• 

Various alarm functions (alarm output) : overcurrent, overvoltage, heater 
disconnection, fuse break, heat-sink overheat, diode (SCR) error

• 

Easy installation with mounting brackets

• 

Easy fuse replacement and maintenance

• 

Inter phase insulating barrier included

• 

High performance SCR (IXYS) diode

Safety Considerations

• 

Observe all ‘Safety Considerations’ for safe and proper operation to avoid hazards.

• 

᜸ symbol indicates caution due to special circumstances in which hazards may occur.

᜸ Warning

  

Failure to follow instructions may result in serious injury or death.

01. 

Fail-safe device must be installed when using the unit with machinery that 

may cause serious injury or substantial economic loss.(e.g. nuclear power 

control, medical equipment, ships, vehicles, railways, aircraft, combustion 

apparatus, safety equipment, crime / disaster prevention devices, etc.)

Failure to follow this instruction may result in personal injury, economic loss or fire.

02. 

Do not use the unit in the place where flammable / explosive / corrosive gas, 

high humidity, direct sunlight, radiant heat, vibration, impact or salinity may 

be present.

Failure to follow this instruction may result in explosion or fire. 

03. 

Install on the device panel, and ground to the bolt for grounding separately.

Failure to follow this instruction may result in fire or electric shock.

04. 

Do not connect, repair, or inspect the unit while connected to a power source.

Failure to follow this instruction may result in fire or electric shock.

05. 

Check ‘Connections’ before wiring.

Failure to follow this instruction may result in fire.

06. Do not disassemble or modify the unit.

Failure to follow this instruction may result in fire or electric shock.

᜸ Caution

  

Failure to follow instructions may result in injury or product damage.

01. 

Use the unit within the rated specifications.

Failure to follow this instruction may result in fire or product damage.

02. 

Use a dry cloth to clean the unit, and do not use water or organic solvent.

Failure to follow this instruction may result in fire or electric shock.

03. 

Keep the product away from metal chip, dust, and wire residue which flow 

into the unit.

Failure to follow this instruction may result in fire or product damage.

04. 

Since leakage current still flows right after turning off the power or in the 

output OFF status, do not touch the load terminal.

Failure to follow this instruction may result in electric shock.

Cautions during Use

• 

Follow instructions in ‘Cautions during Use’. 

 

Otherwise, it may cause unexpected accidents.

• 

Use the product, after 3 sec of supplying power.

• 

Before use, set the mode and function according to the specification. Especially, 

be cautious that the product does not operate when OUT ADJ. is set to 0%. Since 

changing the mode / parameter during operation may result in malfunction, set the 

mode and function after disconnecting load output. 

• 

Re-supply the power to the unit after the unit is discharged completely. Failure to 

follow this instruction may result in malfunction. 

• 

To ensure the reliability of the product, install the product on the panel or metal 

surface vertically to the ground.

• 

Install the unit in the well ventilated place.

• 

While supplying power to the load or right after turning off the power of the load, do 

not touch the body and heat sink. Failure to follow this instruction may result in a burn 

due to the high temperature.

• 

Install a power switch or circuit breaker in the easily accessible place for supplying or 

disconnecting the power.

• 

Do not wire to terminals which are not used.

• 

Since inter element can be damaged when using with coil load, inductive load, etc., 

the inrush current must be under the rated load current.

• 

Do not use near the equipment which generates strong magnetic force or high 

frequency noise.

• 

This unit may be used in the following environments.

 

- Indoors (in the environment condition rated in ‘Specifications’)

 

- Altitude max. 2,000 m

 

- Pollution degree 2

 

- Installation category III

Summary of Contents for SPR3 Series

Page 1: ...k Connections before wiring Failure to follow this instruction may result in fire 06 Do not disassemble or modify the unit Failure to follow this instruction may result in fire or electric shock Caution Failure to follow instructions may result in injury or product damage 01 Use the unit within the rated specifications Failure to follow this instruction may result in fire or product damage 02 Use ...

Page 2: ...multiple power controllers keep space between power controllers for heat radiation Horizontal 50 mm vertical 100 mm UnitDescriptions U V W R S T 01 08 09 09 07 05 03 02 12 13 13 10 11 06 04 14 15 01 Bracket except rated load current 100 150 A model 02 Indicator Indicator Function RUN Operation indicator green Turns on in the RUN mode MAN Manual control indicator green Turns on when adjusting load ...

Page 3: ...rrent feedback control within 3 F S of rated load current Constant voltage feedback control within 3 F S of rated load voltage Constant power feedback control within 3 F S of rated load power Power supply 100 240 VACᜠ 10 50 60 Hz Min load current 1 A Power consumption Rated load current 25 35 50 A 14 VA Rated load current 70 A 22 VA Rated load current 100 150 A 32 VA Insulation resistance 200 MΩ 5...

Page 4: ... value U A Feedback control model 0 to rated current range A M1 6 V phase load current value V A M1 7 W phase load current value W A M1 8 Load power value L W Feedback control model 0 to rated Power range kW M1 9 Resistance value percentage L R Feedback control model 0 to 100 Displays the present resistance as percentage compared to the set resistance of full load auto recognition M1 10 Heatsink t...

Page 5: ... G Y Y G G Y Y G G Y Y H H Z Z H H Z Z H H Z Z H H Z Z Function Output limit OUT ADJ Control input output limit setting output It controls the power supplied into the load Although control input is 100 the output is the 50 which is proportioned with OUT ADJ It is not available at ON OFF control method SV 50 SV 100 Output Control input Output high low limit value This function is to limit output ra...

Reviews: