■ Parameter 2 group
■ Parameter 0 group
Parameter
Mark
Defaults
Setting range
Display
condition
2-1
Output
operation
mode
OUtT
OFF
[Except
in
dicator model]
OFF, L.ST, H.ST, LH.ST, HH.ST, LL.ST,
LD.ST
•
Refer to Output Operation Mode
-
2-2
Hysteresis
HYS
001
[Except indicator model]
Within 10 % of max. display range, digit
2-1
Output
operation
mode:
exce
pt
OFF
2-3
Startup
compensation
time
STaT
0)0
[Except
in
dicator model]
0.0 to 99.9 sec
-
2-4
Peak
monitoring
delay time
PEkT
00 S
00 to 30 sec
-
2-5
Display cycle
DIsT
)2 S
0.1 to 5.0 sec
-
2-6
Keys for zero
adjustment
ZERO
NO
NO, YES
• YES: Press the [◀] + [▲] keys for 3
sec to adjust zero.
-
2-7
External
input
terminal
EVLN
HOLD
[Except indicator model]
HOLD, ZERO
• If the external input terminal is
short-circuited for 50 ms or more, it
operates with the set function.
-
2-8
High-limit
value of
transmission
output
FS-H
50)0
[DC voltage & Transmission (DC 4 - 20
mA) output model],
[AC voltage & Transmission (DC 4 - 20
mA) output model]
Max. value of display range
-
%000
[DC current &
Transmission (DC 4 - 20
mA) output model],
[AC current &
Transmission (DC 4 - 20
mA) output model]
Max. value of display range
2-9
Low-limit
value of
transmission
output
FS-L
00)0
[DC voltage & Transmission (DC 4 - 20
mA) output model],
[AC voltage & Transmission (DC 4 - 20
mA) output model]
Min. value of display range
-
)000
[DC current &
Transmission (DC 4 - 20
mA) output model],
[AC current &
Transmission (DC 4 - 20
mA) output model]
Min. value of display range
2-10
Comm.
Address
ADRS
01
[RS485 Comm. output model]
01 to 99
-
2-11
Comm.
speed
BPS
9600
[RS485 Comm. output model]
38.4k, 19.2k, 9600, 4800, 2400, 1200 bps
-
2-12
Parity bit
PRTY
NONE
[RS485 Comm. output model]
NONE, EVEN, ODD
-
2-13
Stop bit
STP
2
[RS485 Comm. output model]
2,
1 bit
-
2-14
Response
waiting time
RSwT
5
[RS485 Comm. output model]
5 to 99 sec
-
2-15
Lock
LOC
OFF
OFF: unlock,
LOC1: lock parameter 1,
LOC2: lock parameter 1, 2,
LOC3: lock parameter 0, 1 and 2
-
Parameter
Mark
Defaults
Setting range
Display
condition
0-1
Output high-
limit output
setting value
hSET
50)0
[DC voltage &
P
reset setting model]
-5 to 110 % of display range
[AC voltage &
P
reset setting model]
0 to 110 % of display range
2-1
Output
operation
mode:
exce
pt
OFF
%000
[DC current & P
reset setting model]
-5 to 110 % of display range
[AC current & P
reset setting model]
0 to 110 % of display range
0-2
Output low-
limit output
setting value
lSET
00)0
[DC voltage &
P
reset setting model]
-5 to 110 % of display range
[AC voltage &
P
reset setting model]
0 to 110 % of display range
2-1
Output
operation
mode:
exce
pt
OFF
)000
[DC current & P
reset setting model]
-5 to 110 % of display range
[AC current & P
reset setting model]
0 to 110 % of display range
0-3
Display max.
peak value
01)
hPEK
)0
[DC voltage], [AC voltage]
Max. peak value in run mode
2-1
Output
operation
mode:
exce
pt
OFF
&
2-4
Peak
monitoring
delay time:
except 00
)000
[DC current], [AC current]
Max. peak value in run mode
0-4
Display min.
peak value
01)
lPEK
)0
[DC voltage], [AC voltage]
Min. peak value in run mode
)000
[DC current], [AC current]
Min. peak value in run mode
01) Reset: Press any one of [◀], [▼], [▲] keys.
Input range
Display range
Input
impedance
Diaplay method: STND (fixed) Diaplay method
: SCAL
01)
0 - 5 A
0.000 to 5.000
5A
Decimals
Display range
0
-1999 to 9999
)0
-199.9 to 999.9
)00
-19.99 to 99.99
)000
-1.999 to 9.999
0.02 Ω
0 - 2.5 A
0.000 to 2.500
@5A
0.02 Ω
0 - 1 A
0.000 to 1.000
1A
0.102 Ω
0 - 500 mA
0.0 to 500.0
)5A
0.202 Ω
0 - 250 mA
0.0 to 250.0
)25A
0.202 Ω
0 - 100 mA
0.0 to 100.0
)1A
1.022 Ω
0 - 50 mA
0.00 to 50.00
50MA
1.022 Ω
01) Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input
range to measure.
When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.
Input range
Display range
Input
impedance
Diaplay method: STND (fixed) Diaplay method
: SCAL
01)
0 - 500 VACᜠ
0.0 to 500.0
500V
Decimals
Display range
0
-1999 to 9999
)0
-199.9 to 999.9
)00
-19.99 to 99.99
)000
-1.999 to 9.999
5.01092 MΩ
0 - 250 VACᜠ
0.0 to 250.0
250V
5.01092 MΩ
0 - 110 VACᜠ
02)
0.0 to 440.0
110P
1.11092 MΩ
0 - 50 VACᜠ
0.00 to 50.00
50V
1.11092 MΩ
0 - 20 VACᜠ
0.00 to 20.00
20V
200.92 kΩ
0 - 10 VACᜠ
0.00 to 10.00
10V
200.92 kΩ
0 - 2 VACᜠ
0.000 to 2.000
2V
20.92 kΩ
0 - 1 VACᜠ
0.000 to 1.000
1V
20.92 kΩ
01) Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input
range to measure.
When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.
02) In case of 0 to 110 VACᜠ of AC voltage range and using P.T (potential transformer) for 440 VACᜠ / 110 VACᜠ, if
110 VACᜠ is input, and the unit displays 440 VACᜠ automatically by preset scale value for P.T user’s convenient.
Input Range and Display Range
When the max. input value is over the 100 %, it may result in input terminal damage.
■ DC voltage model
Input range
Display range
Input
impedance
Diaplay method: STND (fixed) Diaplay method
: SCAL
01)
0 - 500 VDCᜡ
0.0 to 500.0
500V
Decimals
Display range
0
-1999 to 9999
)0
-199.9 to 999.9
)00
-19.99 to 99.99
)000
-1.999 to 9.999
4.33348 MΩ
0 - 100 VDCᜡ
0.0 to 100.0
100V
4.33348 MΩ
0 - 50 VDCᜡ
0.00 to 50.00
50V
433.48 kΩ
0 - 10 VDCᜡ
0.00 to 10.00
10V
433.48 kΩ
0 - 5 VDCᜡ
0.000 to 5.000
5V
43.48 kΩ
0 - 1 VDCᜡ
0.000 to 1.000
1V
43.48 kΩ
0 - 250 mVDCᜡ 0.0 to 250.0
)25V
2.28 kΩ
0 - 50 mVDCᜡ
0.00 to 50.00
50MV
2.28 kΩ
01) Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input
range to measure.
When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.
■
DC current model
■ AC voltage model
■
AC current model
Input range
Display range
Input
impedance
Diaplay method: STND (fixed) Diaplay method
: SCAL
01)
0 - 5 A
0.000 to 5.000
5A
Decimals
Display range
0
-1999 to 9999
)0
-199.9 to 999.9
)00
-19.99 to 99.99
)000
-1.999 to 9.999
0.022 Ω
0 - 2 A
0.000 to 2.000
2A
0.022 Ω
0 - 500 mA
0.0 to 500.0
)5A
0.222 Ω
0 - 200 mA
0.0 to 200.0
)2A
0.222 Ω
0 - 50 mA
0.00 to 50.00
50MA
2.222 Ω
4 - 20 mA
4.00 to 20.00
4-20
2.222 Ω
0 - 5 mA
0.000 to 5.000
5MA
22.222 Ω
0 - 2 mA
0.000 to 2.000
2MA
22.222 Ω
01) Connect to the input terminals whose 30 % to 100 % of the input range includes the max. value of the input
range to measure.
When the max. input value is under the 30 % of the input terminal range, display accuracy is degraded.