I N S T R U C T I O N M A N U A L
Indicator (MP5M- N)
Specifications
Connections
※
1: Setting range will vary depending on the decimal point.
※
2: The weight includes packaging. The weight in parenthesis is for unit only.
※
Environment resistance is rated at no freezing or condensation.
Model
MP5M-2N
MP5M-4N
MP5M-21
MP5M-41
MP5M-22
MP5M-42
Indicator
High-limit setting
High/Low-limit setting
Display method
7-segment LED (zero blanking method)
Character size
W4×H8mm
Display range
-19999 to 99999
Power
supply
AC voltage
100-240VAC 50/60Hz
AC/DC voltage 24VAC 50/60Hz, 24-48VDC
Power
consumption
AC voltage
Max. 9VA (100-240VAC 50/60Hz)
AC/DC voltage Max. 6.5VA (24VAC 50/60Hz), Max. 5W (24-48VDC )
Permissible voltage range 90 to 110% of rated voltage
External power supply
Max. 12VDC
±10% 80mA
Input frequency
·
Solid state input 1: Max. 50kHz (pulse width: min. 10
㎲
)
·
Solid state input 2: Max. 5kHz (pulse width: min. 100
㎲
)
※
For F7, F8 operation mode, max. 1kHz (pulse width: min. 500
㎲
)
·
Contact input: Max. 45Hz (pulse width: min. 11ms)
Input method
[Voltage Input] High: 4.5-24VDC
, Low: 0-1VDC, input impedance: 3.9kΩ
[No-voltage Input]
Short-circuit impedance: Max. 80Ω, Residual voltage: Max. 1VDC,
Open-circuit impedance: Min. 100kΩ
Measurement range
·Operation
mode F1, F2, F7, F8
·Operation
mode F3, F4, F5, F6
·Operation
mode F9, F10, F11, F14
·Operation
mode F12, F13
: 0.0005Hz to 50kHz
: 0.01 to max. of each time range
: 0 to 99999
: -19999 to 99999
Measurement accuracy
(23
℃
±5
℃
)
·Operation
mode F1, F2, F7, F8
·Operation
mode F3, F4, F5, F6
: F.S.±0.05%rdg±1-digit
: F.S.±0.01%rdg±1-digit
Display cycle
OFF (for F2, F14 operation mode), 0.05, 0.5, 1, 2, 4, 8 sec (same as update output cycle)
Operation mode
Frequency/Revolutions/Speed (F1), Passing speed (F2), Cycle (F3),
Passing time (F4), Time interval (F5), Time differential (F6), Absolute ratio (F7),
Density (F8), Length measurement 1 (F9), Interval (F10), Accumulation (F11),
Addition/Subtraction-individual input (F12), Addition/Subtraction-phase difference
input (F13), Length measurement 2 (F14)
Prescale function
Direct input method (0.0001×10
-9
to 9.9999×10
9
)
Hysteresis
-
0 to 9999
※
1
Main
output
Relay single
-
250VAC 3A resistive load 1c -
Relay dual
-
250VAC 3A resistive load 1a
×2
NPN open
collector
Max. 30VDC 100mA
Max. 30VDC 100mA ×2
Memory retention
Non-volatile memory (number of inputs: 100,000 operations)
Insulation resistance
Over 100MΩ (at 500VDC megger)
Dielectric strength
2,000VAC 60Hz for 1 min
Noise immunity
±2kV the square wave noise (pulse width: 1
㎲
) by noise simulator
Vibration
Mechanical
0.75mm amplitude at frequency of 10 to 55Hz in each X, Y, Z direction for 1 hour
Malfunction
0.5mm amplitude at frequency of 10 to 55Hz in each X, Y, Z direction for 10 min
Shock
Mechanical
300m/s² (approx. 30G) in each X, Y, Z direction for 3 times
Malfunction
100m/s² (approx. 30G) in each X, Y, Z direction for 3 times
Relay
life cycle
Mechanical
-
Min. 5,000,000 operations
Electrical
-
Min. 100,000 operations (250VAC 3A resistive load)
Environ-
ment
Ambient temp. -10 to 50
℃
, storage: -20 to 60
℃
Ambient humi.
35 to 85%RH, storage: 35 to 85%RH
Approval
ᜢ
ᜧ
Weight
※
2
Approx. 243g (approx. 168g) Approx. 256g (approx. 181g) Approx. 265g (approx. 190g)
High/Low-limit setting (MP5M- 2)
Ordering Information
Product Description
Main output (Comparative value output)
N
Indicator
1
Relay single (high-limit)
NPN open collector output
2
Relay dual (
high
/low-limit)
NPN open collector output
2
24VAC 50/60Hz, 24-48VDC
4
100-240VAC 50/60Hz
M
DIN W72×H72mm
5
99999 (5-digit)
MP
Pulse meter
MP 5 M
4
-
N
Output
Power supply
Size
Digit
Item
Dimensions
(unit: mm)
Panel Cut-out Dimensions
Bracket
Parameter Groups
Operation Mode By Parameter Groups
※
1: Only appears in high/low-limit setting models.
※
2: Only appears in high-limit setting models, high/low-limit setting models.
※
3: The settings for
IN-B
and
IN-A
are applied.
※
4: ( ) F output mode[
OUT-F
] cannot be set.
※
5: ( ) setting range:
OFF
,
)05
,
)5
,
1
,
2
,
4
,
8
Output mode
S mode
H mode
L mode
B mode
I mode
F mode
Parameter
STARD
OVT-;
OVT-L
OVT-B
OVT-I
OVT-F
Comparative output limit
Start compensation timer
Monitoring delay function by output mode
● Parameter 3 group
● Parameter 2 group
00000
tSEC
10 01
10 01
Decimal point location of display value
●
Setting range:
00000
,
000)0
,
00)00
,
0)000
,
)0000
RUN mode
DOT
PARa1
PARa2
tUNT
PScaY
PScbY
99(99
99(99
tMIN
^0000
^0000
PScaH
PScbH
PARa3
)05
99999
DISpT
COUnB
●
Setting range
Time unit and range
Prescale mantissa (X) of input A
●
Setting range:
)0001
to
(9999
Prescale mantissa (X) of input B
●
Setting range:
)0001
to
(9999
Prescale exponent (y) of input A
●
Setting range:
10 - 9
(10
-9
) to
10 09
(10
9
)
Prescale exponent (y) of input B
●
Setting range:
10 - 9
(10
-9
) t
o 10 09
(10
9
)
Setting value of Input B
●
Setting range:
1
to
99999
High-limit setting (MP5M- 1)
※
Operation mode F1 to F10
: Display value HOLD
Operation mode F11 to F14
: Display value RESET
Terminal
input
11-12
RUN
mode
Parameter 0 group
(Max./Min. monitoring value)
HOLD/RESET
Input
※
Parameter 1/2/3 group
2 sec
3 sec
RUN mode
hPEK
lPEK
`9999
99999
Max. monitoring
value
Min. monitoring
value
● Parameter 0 group
2 sec
14.3
11.8
75
67.5
Min. 91
46
8.3
4
7.3
40.7
68
0.7
0
68
0.7 0
Min. 91
● Parameter 1 group
ㄹF1
NPnhF
NPnhF
STARD
0001
fDEFY
999(9
999(9
OFF
9(9
STArT
Operation mode
●
Setting range:
F1
to
F14
Sensor type of
input A
Sensor type of
input B
L comparative output
limit
※
Only appears in high/low-limit setting models.
Start compensation timer function & compensation time
●
Setting range:
)0
to
9(9
(sec)
※
Only appears in high/low-limit setting models.
Output hysteresis
●
Setting range:
0000
to
9999
(
the setting range varies depending on the decimal point setting
)
※
Only appears in high-limit setting models,
high/low-limit setting models.
Auto-zero time for input A
Auto-zero time for input B
Memory retention
●
Setting range:
ㄹㄹON
,
OFF
RUN mode
MODE
PARa1
IN-A
IN-B
OUT-T
HYS
GUARD
AUToA
AUToB
MEMO
PARa2
PARa3
Parameter Input sensor type
NPnhF
NPN solid state input 1
NPnmF
NPN solid state input 2
NPnlF
NPN contact input
PNphF
PNP solid state input 1
PNpmF
PNP solid state input 2
PNplF
PNP Contact input
Parameter Output mode Parameter Output mode
STARD
S (Standard)
OUT-B
B (Block)
OUT-H
H (High)
OUT-I
I (One-shot)
OUT-L
L (Low)
OUT-F
F (Deflection)
●
Setting range
2 sec
Output mode
●
Setting range
3 sec
OFF
Lock
RUN mode
LOC
PARa1
PARa2
PARa3
Parameter Function
OFF
Unlock
LOc0
Locks all
LOc1
Parameter 1, 2, 3 lock
LOc2
Parameter 2, 3 lock
LOc3
Parameter 3 lock
2 sec
3 sec
Model
Source
MP5M-21
24-48VDC
24VAC 50/60Hz
MP5M-22
MP5M-2N
MP5M-41
100-240VAC
50/60Hz
MP5M-42
MP5M-4N
※
1: Operation mode F1 to F10
: Display value HOLD
Operation mode F11 to F14
: Display value RESET
※
2:
※
Resetting monitoring value
: Hold the key for over 2 sec.
(reset current value)
※
Only appears in high/low-limit setting model.
tSEC
(sec)
tMIN
(min)
99(99
999.99s
99(99
999.99m
999(9
9999.9s
999(9
9999.9m
99999
99999s
99999
99999m
Operation
mode
Parameter
F1
F2
F3
F4
F5
F6
F7
F8
F9
F10 F11 F12 F13 F14
0 group
hPEK
lPEK
1 group
MODE
Appears in all operation modes(F1 to F14).
IN-A
IN-B
OUT-T
HYS
GVARD
AVToA
AVToB
MEMO
2 group
DOT
tUNT
PScaH
PScaY
PScbH
PScbY
DISpT
ㄹCOUnB
3 group
LOC
Appears in all operation modes(F1 to F14).
※
3
※
4
※
1
※
2
※
1
※
5
Display cycle of measurement value
●
Setting range:
)05
,
)5
,
1
,
2
,
4
,
8
(sec)
※
Setting range in operation mode F2, F14
:
OFF
,
)05
,
)5
,
1
,
2
,
4
,
8
(sec)
3 sec
●
Setting range:
)1
to
999(9
(sec)
※
The above specifications are subject to change and some models may be discontinued
without notice.
●
Setting range:
※
The high-limit setting model(MP5M- 1) does not include the dotted line parts.
INA
Black
Black
Brown
Blue
+12V
HOLD/
RESET
※
1
INB
0V
8
1
10
3
12
5
9
2
11
4
13
6
14
7
SOURCE
※
2
+
-
15
17
16
INA
+12V
HOLD/
RESET
※
1
CONTACT OUT:
250VAC 3A
RESISTIVE LOAD
INB
0V
High
8
1
10
3
12
5
9
2
11
4
13
6
14
7
+
-
SOURCE
※
2
Black
Black
Brown
Blue
15
17
16
HOLD/
RESET
※
1
INA
H
L
+12V
CONTACT OUT:
250VAC 3A
RESISTIVE LOAD
INB
0V
High Low
8
1
10
3
12
5
9
2
11
4
13
6
14
7
SOURCE
※
2
+
-
Black
Black
Brown
Blue
15
17
16
1:
Display
Displays current value in RUN mode.
Alternately displays setting parameters and cor-
responding value in SETTING mode.
2:
key
In RUN mode, press the key once to check max./
min. value.
In RUN mode, hold the key for over 2 sec to enter
parameter groups.
3:
,
key
Select parameter groups, and select or setting
values in the corresponding parameters.
4: Output status indicator
5: Thumbwheel switch for HIGH/LOW setting value
※
Press the ,
keys to select or set the desired value.
※
Press the
key once after changing the setting value, to save the setting value and move to the
next parameter.
※
Hold the
key for 1.5 sec at any parameters to return to the select parameter group mode.
※
Hold the
key for
3 sec to save the setting value and return to RUN mode after changing the
setting value.
※
If there is no key input for 60 sec while setting the parameters, the new settings are ignored, and the
unit will return to RUN mode with previous settings.
※
The dotted line parameters may not appear depending on output specifications or other parameter
settings. Please refer to ' Operation mode by parameter group'.
※
1: Each parameter and corresponding setting value will flash alternately every 0.5 sec.
Flashes
alternately
※
1
Flashes
alternately
※
1
Flashes
alternately
※
1
Flashes
alternately
※
1
( : parameter display,
X: no parameter display)
1
4
3
5
2
72
DRW160446AC
PULSE METER
MP5M SERIES
1. Fail-safe device must be installed when using the unit with machinery that may cause
serious injury or substantial economic loss. (e.g. nuclear power control, medical equipment,
ships, vehicles, railways, aircraft, combustion apparatus, safety equipment, crime/disaster
prevention devices, etc.)
Failure to follow this instruction may result in personal injury, fire, or economic loss.
2. The unit must be installed on a device panel before use.
Failure to follow this instruction may result in electric shock.
3. Do not connect, repair, or inspect the unit while connected to a power source.
Failure to follow this instruction may result in electric shock.
4. Do not disassemble or modify the unit. Please contact us if necessary.
Failure to follow this instruction may result in electric shock or fire.
5. Check the terminal numbers before connecting the power source and measurement input.
Failure to follow this instruction may result in fire.
1. Do not use the unit outdoors.
Failure to follow this instruction may result in electric shock or shortening the life cycle of the unit.
2. When connecting the power input or measuring input, make sure to tighten the terminal
screw bolt above 0.74N•m to 0.90N•m.
Contact failure may result in fire.
3. Use the unit within the rated specifications.
Failure to follow this instruction may result in electric shock or shortening the life cycle of the unit.
4. Do not use loads beyond the rated switching capacity of the relay contact.
Failure to follow this instruction may result in insulation failure, contact failure, contact bonding, relay
damage, or fire.
5. Do not use water or oil-based detergent when cleaning the unit. Use dry cloth to clean the
unit.
Failure to follow these instructions may result in electric shock or fire.
6. Do not use the unit where flammable or explosive gas, humidity, direct sunlight, radiant heat,
vibration, and impact may be present.
Failure to follow this instruction may result in fire or explosion.
7. Keep dust and wire residue from flowing into the unit.
Failure may result in fire or product malfunction.
8. Check the polarity of the measurement input contact before wiring the unit.
Failure to follow this instruction may result in fire or explosion.
Thank you for choosing our Autonics product.
Please read the following safety considerations before use.
Safety Considerations
Warning
※
Please observe all safety considerations for safe and proper product operation to avoid hazards.
※
Safety considerations are categorized as follows.
Warning
Failure to follow these instructions may result in serious injury or death.
Caution
Failure to follow these instructions may result in personal injury or product damage.
※
The symbols used on the product and instruction manual represent the following
symbol represents caution due to special circumstances in which hazards may occur.
Caution