1 Modbus RTU Protocol
© Copyright Reserved Autonics Co., Ltd.
13
1.3
Read holding registers (Func 03–03H)
Read the Binary data of Holding Registers (4X reference) in Slave device.
(1)
Query (Master)
Slave address Function Starting address
No. of points
Error check (CRC16)
High
Low
High
Low
Low
High
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
(2)
Response (Slave)
Slave address Function Byte count Data
Data
Data
Error check (CRC16)
High Low High Low High Low Low
High
1Byte
1Byte
1Byte
1Byte 1Byte 1Byte 1Byte 1Byte 1Byte 1Byte
1Byte
If read the 2 values from Holding Register 400001 (0000 H) to 400002 (0001 H), in Slave
(Address 17) from the Master.
Query (Master)
Slave address Function Starting address
No. of points
Error check (CRC16)
High
Low
High
Low
Low
High
11 H
03 H
00 H
00 H
00 H
02 H
## H
## H
If the value of 400001 (0000 H) on Slave is “555 (22B H)” and the value of 400002 (0001 H) is
“100 (64 H)”.
Response (Slave)
Slave address Function Byte count Data
Data
Error check (CRC16)
High
Low
High
Low
Low
High
11 H
03 H
04 H
02 H
2B H
00 H
64 H
## H
## H
CRC16
CRC16
Summary of Contents for MP Series
Page 1: ... Copyright Reserved Autonics Co Ltd i ...
Page 2: ...ii Copyright Reserved Autonics Co Ltd ...
Page 8: ...Safety Precautions viii Copyright Reserved Autonics Co Ltd ...
Page 10: ...Table of Contents x Copyright Reserved Autonics Co Ltd ...
Page 24: ...2 Modbus Mapping Table 24 Copyright Reserved Autonics Co Ltd MCP MPC1 V1 0 1801US ...