Autonics KT-502H Quick Start Manual Download Page 4

Temperature Transmitter

G-5

A. Recorder

B. Indicator

C. Converter

D. Controller

E. Thyristor 

     unit

F. Pressure 

    transmitter

G. Temp. 

     transmitter

H. Accessories

KT-502H

Temperature Range Setting

Error Display And Troubleshootings

1. PV LRV

2. URV

HELP

HOME

 Select 

'1. PV LRV'

(Low temperature range) and 

    press the 

  key. 

   PV LRV

   0.000 deg C

0.000

HELP

DEL

ESC

ENTER

 Set Low temperature range and press the 

 (F4) key.

   PV URV

   100.000 deg C

   100.000

HELP

DEL

ESC

ENTER

 Set High temperature range and press the 

 (F4) key. 

1. PV LRV 0.000 deg C

2. URV 100.000 deg C

HELP

SEND

HOME

 When the set temperature range is correct, 

     press the 

 (F2) key. 

1. PV LRV

2. URV

HELP

HOME

 Select 

'2. URV'

(High temperature range) and

     press the 

 key. 

Online (Generic)

1. Device Setup

2. PV

3. PV Ao

4. PV LRV

5. URV   

SAVE

 Press the   key for 3 sec.

   Select the 

'4. PV LRV'  

by  

,   

 keys and press the 

 key.

                 - WARNING -

           Pressing ' OK ' will

           change device output

           put 100P in manual

  Press the 

 (F4) key. 

                 - WARNING -

           Return control 100P

           To automatic control

O K

  Press the 

 (F4) key. 

1. PV LRV 0.000 deg C

2. URV 100.000 deg C

HELP

HOME

 Check the set temperature range. Press the 

 (F3) 

key. HART communication is OFF.

•  For connecting the power, use a crimp terminal  

(M3.5, max. 7.2mm).

•  The connection of this unit should be separated from 

the power line and high voltage line in order to prevent 

inductive noise.

•  Install a power switch or a circuit breaker to supply or cut 

off the power.

•  Switch or circuit breaker should be installed nearby 

users for convenient control. 

•  Do not use this unit near the high frequency instruments 

(high frequency welding machine & sewing machine, 

large capacity SCR controller).

•  Installation environment.
 

 Indoor / Outdoor                                            

 

 Altitude max. 2,000m

 

 Pollution degree 2              

 

 Installation category 

•  Use the verified explosion-proof electric connection 

 

(cable gland or sealing fitting) 

 

(explosion proof standard: over Ex d IIC T6,  

IP rating: over IP67 protection structure).

•  Use the dedicated external terminal for earth. For 

connecting earth, use a spring washer and earth cable 

which is over 4mm

2

.

•  We are not responsible for any damages and claims 

for careless. Must read the cautions for your safety 

and using.

•  This explosion-proof unit is certified and the same 

specifications which is reported to Korea Gas Safety 

Corporation. 

•  If there are any problems with the unit, contact the 

head office.

•  Failure to follow these instructions may result in 

product damage.

 

Cautions During Use

Proper Usage

Connect a HART communicator and set temperature range as 

below by a HART communicator.

Display

Error

Troubleshooting

ERR05

Temperature sensor 

A, B or all sensors are 

disconnected.

Check the temperature 

sensor.

ERR06

Temperature sensor B 

is disconnected.

ERR07

When PV is lower than 

the low-limit value of set 

temperature range.

Check low-limit value 

of the set temperature 

range.

ERR08

When PV is higher than 

the high-limit value of 

set temperature range. 

Check high-limit value 

of the set temperature 

range. 

Summary of Contents for KT-502H

Page 1: ...100 100mV 100 500mV 100 2000mV Output DC4 20mA 2 wire Accuracy 0 3 Alarm Below 3 8mA Over 20 5mA Sensor break 3 6mA Load Max V power supply 7 5V 0 22A Galvanic insulation 2kVAC input output Environ ment Ambient temperature 20 to 70 storage 20 to 80 Ambient humidity 0 to 85 RH storage 0 to 85 RH Explosion class Ex d IIC T6 Protection structure IP67 IEC standard Material Body Aluminum AlDc 8S Cover ...

Page 2: ... Ω 0 to400Ω 0 to2000Ω Thermocouple B PtRh30 PtRh6 0 to 1820 32 to 3308 E NiCr CuNi 270 to 1000 454 to 1832 J Fe CuNi 210 to 1200 346 to 2192 K NiCr Ni 270 to 1372 454 to 2501 6 N NiCrSi NiSi 270 to 1300 454 to 2372 R PtRh13 Pt 50 to 1768 58 to 3214 4 S PtRh10 Pt 50 to 1768 58 to 3214 4 T Cu CuNi 270 to 400 454 to 752 Analog Voltage 10 75mV 100 100mV 100 500mV 100 2000mV Opening cover Dimensions Co...

Page 3: ...o 4 PV LRV 5 URV 1 Process Variables 2 Diag Service 3 Basic Setup 4 Detailed Setup 5 Review 1 Test device 2 Loop test 3 Calibration 4 D A trim Connect reference meter ABORT O K Fid dev output 4 000 mA equal to reference meter 1 Yes 2 No ABORT ENTER Enter meter Value 4 000 HELP DEL ABORT ENTER Setting fid dev output to 4mA ABORT O K WARN Loop should be removed from automatic control ABORT O K Selec...

Page 4: ...supply or cut off the power Switch or circuit breaker should be installed nearby users for convenient control Do not use this unit near the high frequency instruments high frequency welding machine sewing machine large capacity SCR controller Installation environment Indoor Outdoor Altitude max 2 000m Pollution degree 2 Installation category Ⅱ Use the verified explosion proof electric connection c...

Reviews: