1 Modbus RTU protocol
16
© Copyright Reserved Autonics Co., Ltd.
1.8
Exception Response-Error Code
If occurs an error, send a response command and transmit each Exception Code after set(1) the
highest-level bit of received command(Function).
Slave Address
Function
+80 H
Exception Code
Error Check(CRC16)
Lo(Lower)
Hi(Upper)
1Byte
1Byte
1Byte
1Byte
1Byte
ILLEGAL FUNCTION (Exception Code: 01 H): A command that is not supported.
ILLEGAL DATA ADDRESS (Exception Code: 02 H): Starting address of queried data
is inconsistent with transmittable address from the device.
ILLRGAL DATA VALUE (Exception Code: 03 H): Numbers of queried data are
inconsistent with the numbers of transmittable (transferable) data from the device.
SLAVE DEVICE FAILURE (Exception Code: 04 H): Not properly completed the
queried command (order).
If reading the output status of non-existing coil 001001(03E8 H) [ON: 1, OFF: 0] on
Slave(Address 17) from Master.
Query (Master)
Slave Address Function
Starting Address
No. of Points
Error Check(CRC16)
Hi(Upper)
Lo(Lower)
Hi(Upper)
Lo(Lower)
Lo(Lower)
Hi(Upper)
11 H
01 H
03 H
E8 H
00 H
01 H
## H
## H
Response (Slave)
Slave
Address
Function
+80 H
Exception Code
Error Check(CRC16)
Lo(Lower)
Hi(Upper)
11 H
81 H
02 H
## H
## H
CRC16
Summary of Contents for BFC Series
Page 1: ... Copyright Reserved Autonics Co Ltd i USER MANUAL For COMMUNICATION ...
Page 2: ...ii Copyright Reserved Autonics Co Ltd ...
Page 8: ...Table of Contents viii Copyright Reserved Autonics Co Ltd ...
Page 45: ...2 Modbus Mapping Table Copyright Reserved Autonics Co Ltd 45 ...
Page 46: ...2 Modbus Mapping Table 46 Copyright Reserved Autonics Co Ltd MSB BFCC1 V1 3 1701US ...