1 Modbus RTU protocol
12
© Copyright Reserved Autonics Co., Ltd.
1.4
Read Input Registers(Func 04–04H)
Reads the Binary data of Input Registers(3X reference) in Slave device.
(1)
Query (Master)
Slave Address Function
Starting Address
No. of Points
Error Check(CRC16)
Hi(Upper)
Lo(Lower)
Hi(Upper)
Lo(Lower)
Lo(Lower)
Hi(Upper)
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
(2)
Response (Slave)
Slave Address Function
Byte Count
Data
Data
Data
Error Check(CRC16)
Lo(Lower)
Hi(Upper)
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
1Byte
If reading the values of 2 range from Input Register 300001(0000 H) to 300002(0001 H) on
Slave (Address 17) from Master.
Query (Master)
Slave Address Function
Starting Address
No. of Points
Error Check(CRC16)
Hi(Upper)
Lo(Lower)
Hi(Upper)
Lo(Lower)
Lo(Lower)
Hi(Upper)
11 H
04 H
00 H
00 H
00 H
02 H
## H
## H
If the values of 300001(0000 H) on Slave is “10(A H)” and the values of 300002(0001 H) on
Slave is “20(14 H)”.
Response (Slave)
Slave Address Function
Byte Count
Data(Data)
Data(Data)
Error Check(CRC16)
Hi(Upper) Lo(Lower) Hi(Upper) Lo(Lower) Lo(Lower) Hi(Upper)
11 H
04 H
04 H
00 H
0A H
00 H
14 H
## H
## H
CRC16
CRC16
Summary of Contents for BFC Series
Page 1: ... Copyright Reserved Autonics Co Ltd i USER MANUAL For COMMUNICATION ...
Page 2: ...ii Copyright Reserved Autonics Co Ltd ...
Page 8: ...Table of Contents viii Copyright Reserved Autonics Co Ltd ...
Page 45: ...2 Modbus Mapping Table Copyright Reserved Autonics Co Ltd 45 ...
Page 46: ...2 Modbus Mapping Table 46 Copyright Reserved Autonics Co Ltd MSB BFCC1 V1 3 1701US ...