■ Mode specifications

Mode

Digital Input

Number of channels

16-CH (I/Q: 8-CH, C/Q:8-CH)

I/O common

NPN / PNP

Input current

5 mA

ON voltage/current

Voltage: ≥ 15 VDCᜡ

Current: ≥ 5 mA

OFF voltage

≤ 5 VDCᜡ

Mode

Digital Output

Number of channels

8-CH (C/Q)

I/O common

NPN / PNP

Power supply

24 VDCᜡ (18 - 30 VDCᜡ), Max. 300 mA

Leakage current

≤ 0.1 mA

Residual voltage

≤ 1.5 VDCᜡ

Short circuit protection

YES

Mode

IO-Link

Input current

2 mA

ON voltage/current

Voltage: ≥ 15 VDCᜡ

Current: ≥ 2 mA

OFF voltage

≤ 5 VDCᜡ

  

Environmental conditions 

Ambient temperature

 01)

-5 to 70 °C, Storage: -25 to 70 °C 

(no freezing or condensation)

Ambient humidity

35 to 75%RH (no freezing or condensation)

Protection rating

IP67 (IEC standard)

 01)  UL approved ambient temperature: 45 ℃

  

Approvals

Approval

ᜢ ᜨ ᜣ  

Association approval

 

  

■ Electrical/Mechanical specifications 

Supply voltage

18 - 30 VDCᜡ

Rated voltage

24 VDCᜡ

Current consumption

2.4 W ( ≤ 216 W)

Supplying current per port

≤ 2 A/Port

Sensor current (US)

≤ 9 A

Dimensions

W 66 × H 215 × D 38 mm

Material

Zinc Die casting

Ethernet port

M12 (Socket-Female), 4-pin, D-coded, Push-Pull

Number of ports: 2 (IN/OUT)

Supported function: daisy chain

Power supply port 

Input: 7/8” (Plug-Male), 5-pin 

Output: 7/8” (Socket-Female), 5-pin

Number of ports: 2 (IN/OUT)

 

Supported function: daisy chain

PDCT port

M12 (Socket-

Female)

, 5-pin, A-coded, Push-Pull 

Number of ports: 1

Connection method: USB serial communication

I/O port

M12 (Socket-Female), 5-pin, A-coded, Push-Pull

Number of ports: 8

Mounting method

Mounting hole: fixed with M4 screw

Grounding method

Grounding hole: fixed with M4 screw

Unit weight (packaged)

≈ 700 g (≈ 900 g)

Specifications

Communication Interface

  

Ethernet

Version

1.1

Transmission rate 

COM1 : 4.8 kbps / COM2 : 38.4 kbps / COM3 : 230.4 kbps 

Port class

Class A

Standard

IO-Link Interface and System Specification Version 1.1.2

IO-Link Test Specification Version 1.1.2

  

IO-Link

Ethernet standard

100BASE-TX

Cable spec.

STP (Shielded Twisted Pair) Ethernet cable over Cat 5

Transmission rate

10 / 100 Mbps

Cable length

≤ 100 m

Protocol

EtherNet/IP

Address settings

Rotary switches, DHCP, BOOTP, atIOLink

Factory settings

• IP Address: 192.168.2.3

• Subnet Mask: 255.255.255.0

• Gateway Address: 192.168.2.1

EDS file

Download the EDS file at the Autonics website.

Summary of Contents for ADIO-EI

Page 1: ... modify the unit Failure to follow this instruction may result in fire 06 Do not touch the product during operation or for a certain period of time after stopping Failure to follow this instruction may result in burn Caution Failure to follow instructions may result in injury or product damage 01 Use the unit within the rated specifications Failure to follow this instruction may result in fire or ...

Page 2: ...tion Install and ground the ADIO ADIO EI Product Manual Connect the ports of ADIO Supply power to the ADIO IO Link device settings Set parameters and functions of IO Link device atIOLink User Manual EtherNet IP Master ADIO EI Integrate the ADIO EI to EtherNet IP project ADIO EI Studio5000LogixDesignerGuide 01 Set the ports of ADIO EI Checking the operation Check the indicators ADIO EI Product Manu...

Page 3: ... 4 1 TX Transmit Data 2 RX Receive Data 3 TX Transmit Data 4 RX Receive Data Power supply port OUT 7 8 Socket Female IN 7 8 Plug Male Pin Function Description 1 2 3 4 5 5 4 3 2 1 1 2 0 V Sensor and actuator supply 3 F G Frame ground 4 24 VDCᜡ Sensor supply 5 24 VDCᜡ Actuator supply PDCT port M12 Socket Female A coded Pin Function 1 4 5 3 2 1 Not Connected N C 2 Data 3 0 V 4 Not Connected N C 5 Dat...

Page 4: ...ide 20 38 29 6 4 7 1 3 6 3 215 1 3 8 35 33 4 24 26 5 26 5 26 5 35 26 30 5 Ø4 5 M4 X 0 7 Ø4 5 M12 X 1 X 11EA 7 8 X 2EA 66 203 35 Dimensions Unit mm For the detailed dimensions of the product follow the Autonics website ...

Page 5: ... Prepare a flat or metal panel in the enclosure 02 Drill a hole to mount and ground the product on the surface 03 Turn off all power 04 Fix the product using M4 screws in the mounting holes Tightening torque 1 5 N m M4 M4 Installation UnitDescriptions 1 2 3 2 4 4 5 5 6 7 9 10 8 01 Grounding hole 02 Mounting hole 03 Insertion part for the name plate 04 Ethernet port 05 Power supply port 06 PDCT por...

Page 6: ...y settings 192 168 2 3 Static IP Address 001 to 255 The IP address of the Ethernet port Set the last octet of the IP address 192 168 2 BOOTP 800 to 899 The IP address is assigned by the Bootstrap Protocol BOOTP server IP Address Subnet Mask etc DHCP 900 to 999 The IP address is assigned by the DHCP server IP Address Subnet Mask etc 02 Turn on the ADIO EI again 03 Check that green LED of the US ind...

Page 7: ...Function Connector 2 Pin no Connector 2 Function 1 N C 1 5 VDCᜡ 2 Data 2 Data 3 0 V 4 0 V 4 N C 5 Data 3 Data 01 Connect to the EtherNet IP 01 Connect the M12 connector to the Ethernet port See the connections below 1 2 3 4 1 TX Transmit Data 2 RX Receive Data 3 TX Transmit Data 4 RX Receive Data 02 Connect the connector to the EtherNet IP network Network device PLC or EtherNet IP device supportin...

Page 8: ... 24 VDCᜡ Sensor supply 5 24 VDCᜡ Actuator supply 1 2 3 4 5 5 4 3 2 1 PWR OUT PWR IN PortConnections 03 Connect with the atIOLink Do not use the PDCT port and the Ethernet port at the same time 01 Connect the M12 connector to the PDCT port See the connections below 1 4 5 3 2 1 Not Connected N C 2 Data 3 0 V 4 Not Connected N C 5 Data 02 Connect the connector to the network device Network device PC ...

Page 9: ...ress Flashing Device self testing Power Green ON The connection is established Flashing No connection Red ON IP address conflict Another device has the same IP address Flashing Connection timeout 06 Ethernet connection Indicator LED color Status Description L A1 L A2 Green OFF No Ethernet connection ON The Ethernet connection is established Yellow Flashing Data transmission 07 Transmission rate of...

Page 10: ...or current US 9 A Dimensions W 66 H 215 D 38 mm Material Zinc Die casting Ethernet port M12 Socket Female 4 pin D coded Push Pull Number of ports 2 IN OUT Supported function daisy chain Power supply port Input 7 8 Plug Male 5 pin Output 7 8 Socket Female 5 pin Number of ports 2 IN OUT Supported function daisy chain PDCT port M12 Socket Female 5 pin A coded Push Pull Number of ports 1 Connection me...