Autometers Systems IC 970 Installation & Operating Manual Download Page 4

7

Please follow these instructions precisely.

1. Press Func tion Key

The display will change to.

You will notice the cursor is flashing at the first digit on the left of the two digits. Press the key 
with 

2

 on it, the cursor will now move to the next digit, now press 

1.

2. Press Enter

The display will change to. 

You will notice the cursor is flashing at the first digit on the left TO ALTER THE OUTPUT VALUE (kWh)

Select the value you require by pressing the keys numbered 1, 2, 3 or 4. When you press one of 
these keys the meter will automatically update & return you back to the default display.

The kVah pulse output will automatically be set to the same value.

6

Your Current Transformer Ratio requires to be programmed into this meter. Please follow these 
instructions precisely.

1. Press Func tion Key

The display will change to.

You will notice the cursor is flashing at the first digit on the left of the two digits

Press the key with 

1

 on it, the cursor will now move to the next digit, now press 

3.

3. Press Enter.

The display will change to. 

Enter the current transformer value by pressing the numbers which are on the front of the key pad. 
The cursor will automatically move to the right as you enter the numbers. The cursor will drop 
down to the NT primar y, repeat the previous steps. 

When you have completed inputting the value of the current transformers.

Press Enter.

This will programme the meter and take you back to the default register.

To check you have programmed the correct value press the I nformation key continuously until 
you reach the correct screen.  

Please Note.

When setting the C.T or N.T ratios and you have only three digits you must enter “0” as the first digit. 
E.g. 100/5 would be entered as 0100/5.

To change the pulse output value
Code 21 (switch 8 on)

To enter the C.T. Ratio code 13 (switch 8 on)

Summary of Contents for IC 970

Page 1: ...of data collection units this enabling complete measurement and data collection systems to be built up A new feature to the IC 970 is the protocol set up information which can be viewed on the displa...

Page 2: ......

Page 3: ...e current transformer ratio If you want to monitor the neutral current then the neutral current transformer ratio will also need to be programmed If the meter has been purchased with the communication...

Page 4: ...ay will change to You will notice the cursor is ashing at the rst digit on the left of the two digits Press the key with 1 on it the cursor will now move to the next digit now press 3 3 Press Enter Th...

Page 5: ...lay 8 Please follow these instructions precisely 1 Press Function Key The display will change to You will notice the cursor is ashing at the rst digit on the left of the two digits Press the key with...

Page 6: ...ate meter readings Press Enter The meter will automatically take you back to the default display 10 Please follow these instructions precisely 1 Press Function Key The display will change to You will...

Page 7: ...position Press Enter The meter will automatically take you back to the default display 12 Please follow these instructions precisely 1 Press Function Key The display will change to You will notice th...

Page 8: ...ow the meter has been programmed The Function Key to select special functions Display of 4 lines with 20 characters per line Membrane Keypad with 15 sealed keys To View Minimum and Maximum Values Pres...

Page 9: ...correct protocol in the meter See below You will notice two red binary switches next to each other one is marked ADDR and the other switch is marked FUNC The binary switch has 8 switches numbered 1 8...

Page 10: ......

Page 11: ...tion Technical Parameters Meter standard BS EN 61036 Accuracy Active 1 0 reactive 2 0 Reference Voltage 3 x 230 400 volt Basic Current 5 amp Maximum Current 6 amp Frequency 50 60 Hz Pulse Constant 500...

Page 12: ...0 246 0 223 0 189 0 105 0 069 0 102 0 068 0 048 0 055 0 046 Customer care is the cornerstone of the company s success A positive service policy is observed throughout every specialist area of operatio...

Reviews: