Error Display Information
14
The chart below shows the possible error displays on the Solo Basic temperature controller.
Controller Error Display
Display Position
Display
Meaning
Cause
Corrective Action
PV
no
Cont
No sensor input
The input terminals
are open.
Check the input wiring. If the problem still exists, replace the
sensor or the controller.
SV
PV
sen
err
Sensor type error
Temperature is out of
range for sensor type
Check sensor type and its condition. If damaged or wrong,
replace and update settings. Check actual condition to make
sure temperature is within sensor range.
SV
Alarm Outputs
For models equipped with alarms there are two alarm outputs. Each alarm can be programmed for one of nine
different alarm types. To set up the first alarm output, press the
;
button for three seconds. Press the
•
button repeatedly until the parameter
ALA1
appears. If the controller is configured for dual output control,
parameter
ALA1
is not available. Use the
.
button to choose the set value for the desired alarm type. Refer
to the chart below for alarm type information. Press the
;
button to save the selected value. If additional
alarm outputs are required press the
•
button to proceed to
ALA2
. Follow the same procedure to program
the additional alarm. When the desired alarm(s) are programmed, press the
;
button repeatedly until the
controller returns to the main screen.
The alarm output limits are controlled by the parameters
Al
n
h
and
Al
n
l
, where “n” corresponds to the
alarm output chosen. After selecting the desired alarm, press the
•
button repeatedly until the parameter
Al
n
h
and/or
Al
n
l
appears. Use the
.
and
,
buttons to enter the high and/or low values for each
alarm outputs selected. Press the
;
button to save each selected value. Press the
;
button again to
return to the controller main screen.
For advanced alarm options
Al1o
/
al2o
and alarm delay
al1d
/
al2d
please reference the parameter
descriptions in chapter 3 of the user manual.
ALA1
and
ALA2
are both SPST resistive load 3A @ 250 VAC, normally open relay outputs with a shared
common.
13
Set Value
Alarm Type
Alarm Output Operation
0
Alarm function disabled
Output is OFF
1
Deviation upper- and lower-limit:
Alarm output activates when PV value is higher than the setting value SV+(AL-H) or
lower than the setting value SV-(AL-L).
ON
OFF
SV-(AL-L)
SV
SV+(AL-H)
2
Deviation upper limit:
Alarm output activates when PV value is higher than the setting value SV+(AL-H).
ON
OFF
SV
SV+(AL-H)
3
Deviation lower limit:
Alarm output activates when PV value is lower than the setting value SV-(AL-L).
ON
OFF
SV-(AL-L)
SV
4
Absolute value upper and lower limit:
Alarm output activates when PV value is higher than the setting value AL-H or lower
than the setting value AL-L.
ON
OFF
AL-L
AL-H
5
Absolute value upper limit:
Alarm output activates when PV value is higher than the setting value AL-H.
ON
OFF
AL-H
6
Absolute value lower limit:
Alarm output activates when PV value is lower than the setting value AL-L.
ON
OFF
AL-L
7
Hysteresis upper limit alarm output:
Alarm output activates when PV value is higher than the setting value SV+(AL-H). The
alarm output turns OFF when the PV value is lower than the setting value SV+(AL-L).
ON
OFF
SV SV+(AL-L) SV+(AL-H)
8
Hysteresis lower limit alarm output:
Alarm output activates when PV value is lower than the setting value SV-(AL-H). The
alarm output turns OFF when the PV value is higher than the setting value SV-(AL-L).
ON
OFF
SV-(AL-H) SV-(AL-L) SV
9
Disconnection Alarm: This alarm output is enabled if the sensor connection is
incorrect or has been disconnected.
Parameter Default Settings
15
Parameter Default Settings
Display
Description
Default Setting
1234
Use
.
or
,
to set temperature set point. Press
•
to switch digits and
;
to set value.
r-S
RUN/STOP: Control setting RUN/STOP
RUN
SP
SELECT POINT: Decimal point setting (0: integer; 1: one decimal point)
0
LoC
LOCK: Setting lock mode (LOCK1: all; LOCK2: only SV changes are allowed)
OFF
AL1H
ALARM1 HIGH: Upper limit alarm 1 (display according to the setting in ALARM mode)
4.0
AL1L
ALARM1 LOW: Lower limit alarm 1 (display according to the setting in ALARM mode)
4.0
AL2H
ALARM2 HIGH: Upper limit alarm 2 (display according to the setting in ALARM mode)
4.0
AL2L
ALARM2 LOW: Lower limit alarm 2 (display according to the setting in ALARM mode)
4.0
out1
OUT1: Display and adjust output value of 1st output group
0.0
out2
OUT2: Display and adjust output value of 2nd output group (display when
s-hC
is set to a dual
output mode)
0.0
o1ma
OUT1 MAX.: Upper limit % of 1st output group
100.0
o1mC
OUT1 MIN.: Lower limit % of 1st output group
0.0
o2mA
OUT2 MAX: Upper limit % of 2nd output group (display when
s-hC
is set to a dual output mode)
100.0
o2mi
OUT2 MIN: Lower limit % of 2nd output group (display when
s-hC
is set to a dual output mode)
0.0
inpt
INPUT: Set input type (refer to section 11 for a list of supported temperature sensors)
K
tpun
TEMP. UNIT: Set temperature unit C/F
C
tp-h
"TEMP. HIGH: Set up upper temperature limit
(the upper limit setting is different for different types of sensors)"
1300
tp-l
"TEMP. LOW: Set up lower temperature limit
(the lower limit setting is different for different types of sensors)"
-200
Ctrl
CONTROL: Select control modes (3 different modes: ON-OFF, PID, and MANUAL)
PID
S-HC
SELECT HEAT/COOL: Select heating, cooling or dual-output heating and cooling.
H1
ALA1
ALARM1 SET: Set up Alarm 1 mode (refer to section 13 "Alarm Outputs")
0
Al1o
ALARM1 OPTION: Set up Alarm 1 options
0
al1d
ALARM1 DELAY: Set up Alarm 1 delay
0
ala2
ALARM2 SET: Set up Alarm 2 mode (refer to section 13 "Alarm Outputs")
0
al2o
ALARM2 OPTION: Set up Alarm 2 options
0
al2d
ALARM2 DELAY: Set up Alarm 2 delay
0
at
AT: Auto tuning (display when setting
Ctrl
= PID/RUN)
OFF
p
P: Proportional Band (display when setting
Ctrl
= PID automatically set after auto tuning)
30.0
i
I: Integral Time (display when setting
Ctrl
= PID automatically set after auto tuning)
120
d
D: Deviation Time (display when setting
Ctrl
= PID automatically set after auto tuning)
30
pdof
PD OFFSET: PD offset when Integral = 0 to eliminate a consistent deviation (display when setting
Ctrl
= PID automatically set after auto tuning)
50.0
o1-s
OUT1 HYSTERESIS: Adjust Output 1 hysteresis (when
Ctrl
= ON/OFF)
0
o2-s
OUT2 HYSTERESIS: Adjust Output 2 hysteresis (when
Ctrl
= ON/OFF)
0
o1-h
OUT1 HEAT: Heating control cycle for Output 1 (when
Ctrl
= PID/MANUAL)
Output type:
C: 1 sec
V: 5 sec
R: 20 sec
o1-C
OUT1 COOL: Cooling control cycle for Output 1 (when
Ctrl
= PID/MANUAL)
o2-h
OUT2 HEAT: Heating control cycle for Output 2 (when
Ctrl
= PID/MANUAL)
o2-C
OUT2 COOL: Cooling control cycle for Output 2 (when
Ctrl
= PID/MANUAL)
Coef
COEF: Proportional band coefficient of Output 1 against Output 2 (when
Ctrl
= PID and when
in dual output control)
1.00
dead
DEAD: Set up deadband (when
Ctrl
is not set to MANUAL and when in dual output)
0
pv-f
PV FILTER: Set up input filter factor of PV
2
pv-r
PV RANGE: Set up input filter range of PV
1.00
pvof
PV OFFSET: Adjust input compensation of PV
0
pv6a
PV GAIN: Adjust input gain of PV
0.000
a1ma
ANALOG OUT1 MAX.: Adjust upper limit compensation for analog Output 1 (1 scale = 1 μA)
0
a1mi
ANALOG OUT1 MIN.: Adjust lower limit compensation for analog Output 1 (1 scale = 1 μA)
0
Notes: