background image

Heating Loop with PID Control

1. Access the Initial Setup mode by pressing and holding the 

;

 button for three seconds. Press the 

 

button repeatedly until the parameter 

Ctrl

 appears. Confirm the default value 

Pid

 is selected for PID 

control.  Press the 

 button to access the parameter 

s-hC

Confirm the default value

 

h1

 is selected for 

controlling a heating loop. Press the 

;

 button to return to the controller main screen.

2. Press the 

 button to access the parameter 

r-s

. Verify that the default value 

run

 is selected. Press 

the 

;

 button to return to the controller main screen.

3. Refer to Section 12-1 of this Quick Start Guide to set up the PID control parameters.
4. If the temperature controller’s output is discrete, access the regulation mode again by pressing the 

;

 

button for less than three seconds. Press the 

 

button repeatedly until the parameter 

o1-h

 appears. Use 

the 

,

 and 

.

 

buttons to set the time period in seconds for the heating control. Press the 

;

 button twice 

to save the value and return to the controller main screen.

12-2

Cooling Loop with ON / OFF Control

1. Access the Initial Setup mode by pressing and holding the 

;

 button for three seconds. Press the 

 

button repeatedly until the parameter 

Ctrl

 appears. Use the 

,

 and 

.

 

buttons to select 

onof

 for ON 

/ OFF control. Press the 

;

 button to save the value. Press the 

 button to access the parameter 

s-hC

Use the 

.

 

button to select 

C1

 for controlling a cooling loop. Press the 

;

 button twice to save the value 

and return to the controller main screen.
2. Press the 

 button to access the parameter 

r-s

. Verify that the default value 

run

 is selected. Press 

the 

;

 button to return to the controller main screen.

3. Press the 

;

 button for less than three seconds to access the parameter 

o1-s

. Use the 

,

 and 

.

 

buttons to enter hysteresis. This is the amount the PV must go above the SV before the controller output turns 
on. Press the 

;

 button twice to save the selected value and return to the controller main screen.

12-5

Heating Loop with ON / OFF Control

1. Access the Initial Setup mode by pressing and holding the 

;

 button for three seconds. Press the 

 

button repeatedly until the parameter 

Ctrl

 appears. Use the 

,

 and 

.

 

buttons to select 

onof

 for ON 

/ OFF control. Press the 

;

 button to save the value. Press the 

 button to access the parameter 

s-hC

Confirm the default value 

h1

 is selected for controlling a heating loop. Press the 

;

 button to return to the 

control

ler main screen.

2. Press the 

 button to access the parameter 

r-s

. Verify that the default value 

run

 is selected. Press 

the 

;

 

button to return to the controller main screen.

3. Press the 

;

 button for less than three seconds to access the parameter 

o1-s

. Use the 

,

 and 

.

 

buttons to enter hysteresis. This is the amount the PV must go below the SV before the controller output turns 
on. Press the 

;

 button twice to save the selected value and return to the controller main screen.

12-3

Cooling Loop with PID Control

1. Access the Initial Setup mode by pressing and holding the 

;

 button for three seconds. Press the 

 

button repeatedly until the parameter 

Ctrl

 appears. Confirm the default value 

Pid

 is selected for PID 

control.  Press the 

 button to access the parameter 

s-hC

. Use the 

.

 

button to select 

C1

 for 

controlling a cooling loop. Press the 

;

 button twice to save the value and return to the controller main screen.

2. Press the 

 button to access the parameter 

r-s

. Verify that the default value 

run

 is selected. Press 

the 

;

 button to return to the controller main screen.

3. Refer to Section 12-1 of this Quick Start Guide to set up the PID control parameters.
4. If the temperature controller’s output is discrete, access the regulation mode again by pressing the 

;

 

button for less than three seconds. Press the 

 

button repeatedly until the parameter 

o1-C

 appears. Use 

the 

,

 and 

.

 

buttons to set the time period in seconds for the cooling control. Press the 

;

 button twice 

to save the value and return to the controller main screen.

12-4

PID Control Setup

The parameters for PID can be auto-tuned using the 

At

 parameter. Access this parameter by pressing the 

;

 

button for less than three seconds. Use the 

.

 

button to turn the auto-tune feature 

on

. Press the 

;

 button to save the value. Optimal PID values are automatically determined with the auto-tune feature. 

PID operation can also be controlled by programming the individual 

p

i

, and 

d

 parameters. Access these 

parameters by pressing the 

;

 button for less than three seconds and press the 

 button repeatedly 

until the parameter 

p

 appears. Use the 

,

 and 

.

 

buttons to change the value for the Proportional band 

if desired and press the 

;

 button to save the value. Press the 

 button to access the 

i

 parameter. Use 

the 

,

 and 

.

 

buttons to change the value for the Integral time if desired and press the 

;

 button to 

save the value. Press the 

 button to access the 

d

 parameter. Use the 

,

 and 

.

 

buttons to change 

the value for the Derivative time if desired and press the 

;

 button twice to save the value and return to the 

controller main screen.

12-1

Note:  PID options only available when control mode is set to PID. 

Use the 

,

 

and

 

.

 

buttons to set the desired setoint and press

 

;

 

to save before  

starting the auto-tune process

Dual Output with PID Control

Only available on the SOLO Basic units with alarms. When used in a dual output mode the output for Alarm 1 
is reassigned as Output 2. Output 2 and Alarm 2 will share the same common in this configuration and should 
be taken into consideration when planning unit wiring.
1. Access the Initial Setup mode by pressing and holding the 

;

 button for three seconds. Press the 

 

button repeatedly until the parameter 

CtrL

 appears. Confirm the default value 

pid

 is selected for PID 

control. Press the 

 button to access the parameter 

s-hC

. Use the 

.

 or 

,

 button to select 

h1C2

 

for controlling a dual heating / cooling loop or 

C1H2

 a dual cooling / heating loop. The 

h1C2

 setting will 

assign the heating control to Output 1 and the cooling control to Output 2 and 

C1H2

 will assign the cooling 

control to Output 1 and the heating control to Output 2. Press the 

;

 button twice to save the value and return 

to the controller main screen. 
2. Press the 

 button to access the parameter 

r-s

. Verify that the default value 

run

 is selected. Press 

the 

;

 button to return to the controller main screen. 

3. Refer to Section 12-1 of this Quick Start Guide to set up the PID control parameters. 
4. To adjust the control cycle for Output 1 access the regulation mode again by pressing the 

;

button for less 

than three seconds. Press the 

 button repeatedly until the parameter 

o1-H

 or 

o1-C

 appears if heating or cooling is assigned to Output 

1. Use the 

.

 and 

,

 buttons to set the time period in seconds for 

the control cycle of Output 1. Press the 

;

 button to save the value. 

To adjust the control cycle for Output 2 press the 

 button repeatedly 

until the parameter 

o2-H

 or 

o2-C

 appears if heating or cooling is 

assigned to Output 2. Use the 

.

 and 

buttons to enter the cycle 

period in seconds for Output 2. Press the 

;

 button twice to save the 

value and return to the controller main screen. 
5.Optional regulation parameters can be programmed for dual output 
control. If this is desired, access the regulation mode again by pressing 
the 

;

 button for less than three seconds. Press the 

 button repeat-

edly until the parameter 

Coef

 appears. This value allows the control 

selected for Output 2 to have a different proportional setting than the 
control selected for Output 1. The Output 1 proportional band setting is 
multiplied by the 

Coef

 value to create a proportional band setting for 

Output 2. Use the 

.

 and 

,

 buttons to change this value if desired. Press the 

;

 button to save the 

selected value. Press the 

 button to access the parameter 

dead

. Use the 

.

 and 

,

 buttons to enter 

a deadband zone value around the setpoint where the output is not affected by the proportional control value. If 
the PV remains within the deadband zone the output is not affected by the proportional control. The integral and 
derivative controls ignore the deadband setting and may cause the output to be on within the deadband zone. 
Press the 

;

 button twice to save the value and return to the controller main screen.

12-7

PV

0

Output

Dead band: dead

band width=positive

Set point

Heating

Cooling

dead

PV

0

Output

Dead band: dead

band width=negative

Set point

Heating

Cooling

dead

Dual control with PID 

positive deadband

Dual control with PID 

negative deadband

Dual Output with ON / OFF Control

Only available on the SOLO Basic units with alarms. When used in a dual output mode the output for Alarm 1 
is reassigned as Output 2. Output 2 and Alarm 2 will share the same common in this configuration and should 
be taken into consideration when planning unit wiring.
1. Access the Initial Setup mode by pressing and holding the 

;

 button for three seconds. Press the 

 

button repeatedly until the parameter 

CtrL

 appears. Use the 

.

 and 

,

 buttons to select 

onof

 for 

ON / OFF control and press the 

;

 button to save the selected value. Press the 

 button to access the 

parameter 

s-hC

. Use the 

.

 and 

,

 buttons to select 

H1C2

 for controlling a dual heating / cooling loop 

or 

C1h2

 a dual cooling / heating loop. The 

H1C2

 setting will assign the heating control to Output 1 and the 

cooling control to Output 2 and 

C1h2

 will assign the cooling control 

to Output 1 and the heating control to Output 2. Press the 

;

 button 

twice to save the value and return to the controller main screen. 
2. Press the 

 button to access the parameter 

r-s

. Verify that 

the default value 

run

 is selected. Press the 

button to return 

to the controller main screen.
3. Press the 

;

 button for less than three seconds to access the 

parameter 

o1-S

. Use the 

.

 and 

,

 buttons to enter hyster-

esis for Output 1, the heating control in the example diagram. This is the 
amount the PV must go below, or above if Output 1 is setup for cooling, the SV before the controller output turns 
on. Press the 

;

 button to save the selected value. Press the 

 button to access the parameter 

o2-S

Use the 

.

 and 

,

 buttons to enter hysteresis for Output 2, the cooling control in the example diagram. 

This is the amount the PV must go above, or below if Output 2 is setup for heating, the SV before the controller 
output turns on. Press the 

;

 button twice to save the selected value and return to the controller main screen.

4. Optional regulation parameters can be programmed for additional dual loop control. If this is desired, access 
the regulation mode again by pressing the 

;

 button for less than three seconds. Press the 

 button 

repeatedly until the parameter 

dead

 appears. Use the 

.

 and 

,

 buttons to enter a deadband zone 

value around the setpoint where the output is not on. The PV must go beyond the deadband range for either 
the heating or cooling output to turn on. Press the 

;

 button twice to save the selected value and return to 

the controller main screen.

12-8

OFF

PV

Set point

ON

Heating

Dead band

Output 1 Hysteresis 

Output 2 Hysteresis 

Cooling

o1-s

02-s

dead

Dual loop ON / OFF control 

output operation

Manual Control

1. Access the Initial Setup mode by pressing and holding the 

;

 button for three seconds. Press the 

 

button repeatedly until the parameter 

Ctrl

 appears. Use the 

,

 and 

.

 

buttons to select 

manu

 for 

manual control. Press the 

;

 button twice to save the selected value and return to the controller main screen.

2. Press the 

 button to access the parameter 

out1

. Use the 

,

 and 

.

 

buttons to set a value 

between 

)0

 and 

10)0 

to control output directly. If the controller has a discrete output, a value of 

2)0 

turns the output on 20% of the time. A value of 

10)0

 would turn the output on 100% of the time. A manually 

controlled analog output value is a percentage of the analog signal. For example, if the controller has a 4-20mA 
current output, a setting of 

)0

 would mean that the output would be 4mA. The output would be 20mA with a 

setting of 

10)0

. Press the 

;

 button  to save the selected value. The same process can be followed for 

out2

 on units with alarms configured for dual output. Refer to Section 12-7 or 12-8.

12-6

Control Setup

Please choose the desired control mode and follow the instructions in that section. For example, to control 
heat in an oven, the Heating Loop with PID Control could be used by following the steps in 12-2. For a cooling 
operation like a freezer one could use Cooling Loop with ON / OFF Control in section 12-5.
To change the control mode, it is recommended to do a factory reset before setting up the new control mode. 
Please see section 10 of this document for instructions on how to complete a reset to factory defaults.

12

Reviews: