background image

4

2  Functions and features

The vibration sensor detects the vibration in the system (measured / evaluated 

physical unit = vibration velocity)� This is converted into an analog signal at the 

current output� The switching output behavior is determined using the two setting 

rings�

3  Installation 

 

► Mount only in a thick housing wall (e.g. transport thread).

 

Ensure that the signal direction is correct�

 

Ensure a safe vibration transmission and allow no elastic intermediate layers�

 

Tighten the sensor with a tightening torque of 15 Nm�

4  Electrical connection

The unit must be connected by a qualified electrician� The national and 

international regulations for the installation of electrical equipment must be 

adhered to�

M12

4

1

2

3

L+

L

3

2

4

1

4...20 mA

4:

2:

Pin 1: L+
Pin 2: 4...20 mA
Pin 3: GND
Pin 4:  digital output 

(normally closed)

5  Settings

RMS Set 

Effective value of the switching threshold, defining the limit value of the vibration 

velocity�

Delay Set

 

Time in seconds during which the limit value must be effectively above the swit-

ching threshold (RMS Set) to activate the switching output (normally closed pin 4)� 

Summary of Contents for prosense VCST-25-1000

Page 1: ...by Automationdirect com Operating instructions Vibration switch transmitter VCST 25 1000 VCST 50 1000 11429420 00 12 2021 80308506 00 ...

Page 2: ...ctions 3 2 Functions and features 4 3 Installation 4 4 Electrical connection 4 5 Settings 4 5 1 Switching output behavior 5 6 Operating and display elements 6 7 Scale drawing 7 8 Maintenance repair disposal 7 9 Technical data 7 ...

Page 3: ... prior to set up of the unit Ensure that the product is suitable for your application without any restrictions The unit conforms to the relevant regulations and EC directives Improper or non intended use may lead to malfunctions of the unit or to unwanted effects in your application That is why installation electrical connection set up operation and maintenance of the unit must only be carried out...

Page 4: ...intermediate layers Tighten the sensor with a tightening torque of 15 Nm 4 Electrical connection The unit must be connected by a qualified electrician The national and international regulations for the installation of electrical equipment must be adhered to M12 4 1 2 3 L L 3 2 4 1 4 20 mA 4 2 Pin 1 L Pin 2 4 20 mA Pin 3 GND Pin 4 digital output normally closed 5 Settings RMS Set Effective value of...

Page 5: ...ff 4 Switching threshold 5 Delay Vss vibration velocity t time Implementation of the time delays The time delay starts when the defined switching threshold is exceeded 1 2 The time delay is cancelled when the value falls below the switching threshold without switch off The switch off is triggered when the switching threshold is exceeded during a full time delay 3 ...

Page 6: ... setting rings manually adjustable after unlocking 3 LED green voltage supply 4 M8 process connection 5 LED yellow lights when switching threshold and time delay are exceeded 6 setting marks To achieve the setting accuracy first position the rings to the lower end stop value then set the requested value ...

Page 7: ...nce repair disposal The operation of the unit is maintenance free It is not possible to repair the unit After use dispose of the unit in an environmentally friendly way in accordance with the applicable national regulations 9 Technical data Technical data and further information at www automationdirect com ...