background image

3

Sales 800-633-0405

www.productivity1000.com

P1-4ADL2DAL-1 Schematic

I1+

I2+

I3+

I4+

0V

I1+

COM

I2+

CH1 ADC
CH2 ADC
CH3 ADC
CH4 ADC

CH5 DAC
CH6 DAC

ISOLATED ANALOG

CIRCUIT COMMON

INTERNAL

MODULE CIRCUITRY

INPUTS

OUTPUTS

1234567

89

10

24V

COM

+ -

24VDC User

Supplied

Power

4–20 mA Current Sourcing

4–20 mA Current Sourcing

ȍ

ȍ

ȍ

ȍ

ISOLATED ANALOG

CIRCUIT POWER

P1-4ADL2DAL-1  Wiring Diagram

+

Current Input Circuits

Current Output Circuits

COM

3-Wire Current

Transmitter

.032A

2-Wire 4-20 mA

Transmitter

fuse

2-Wire Transmitter

3-Wire Transmitter

+24VDC User 

Supplied Power 

+

+

+

.032A

fuse

Note: Do not connect both ends of shield.

4-Wire 4-20 mA

Transmitter

4-Wire Transmitter

+

User Supplied

Transmitter Power 

AC or DC

4 - 20mA

Load

Note: Shield is connected to common at the source device.

+24VDC User 

Supplied Power 

An Edison S500-32-R

0.032A fast-acting fuse 

is recommended for all 

4-20 mA current loops.

.032A

fuse

+ –

Summary of Contents for Productivity 1000 P1-4ADL2DAL-1

Page 1: ...wiring options on page 5 General Specifications Operating Temperature 0º to 60ºC 32º to 140ºF Storage Temperature 20º to 70ºC 4º to 158ºF Humidity 5 to 95 non condensing Environmental Air No corrosive gases permitted Vibration IEC60068 2 6 Test Fc Shock IEC60068 2 27 Test Ea Field to Logic Side Isolation 1800VAC applied for 1 second Insulation Resistance 10M 500VDC Heat Dissipation 2470mW Enclosur...

Page 2: ...ontinuous Overload Outputs open circuit protected Type of Output Protection Electronically current limited to 20mA or less Output Signal at Power Up and Power Down 4mA Input Specifications Inputs per Module 4 Module Signal Input Range 0 20 mA Signal Resolution 13 bit Resolution Value of LSB least significant bit 0 20 mA 2 44 µA per count 1LSB 1 count Data Range 0 8191 counts Input Type Sinking Sin...

Page 3: ...CUIT POWER P1 4ADL2DAL 1 Wiring Diagram Current Input Circuits Current Output Circuits COM 3 Wire Current Transmitter 032A 2 Wire 4 20 mA Transmitter fuse 2 Wire Transmitter 3 Wire Transmitter 24VDC User Supplied Power 032A fuse Note Do not connect both ends of shield 4 Wire 4 20 mA Transmitter 4 Wire Transmitter User Supplied Transmitter Power AC or DC 4 20mA Load Note Shield is connected to comm...

Page 4: ...cked position and then pull modules apart Step Two Attach field wiring using the removable terminal block or ZIPLink wiring system LOCK UNLOCK WIRE STRIP LENGTH MIN MAX P1 08TD1 Check all latches are secure after modules are connected QR Code Use any QR Code reader application to display the module s product insert P1 08TD1 P1 08TD1 1 2 3 4 5 6 7 8 9 10 L L L L L L L L 24V 1 2 3 4 0V 5 6 7 8 12 24...

Page 5: ...nly P1 10RTB Quantity 1 4 Spring Clamp Terminal Block only P1 10RTB 1 Quantity 1 5 Accessories ZL RTB COM TW SD SL 1 TW SD MSL 2 ZL RTB20 ZL RTB20 1 2 1 Cable ZIPLink Module Complete System 2 ZL RTB COM provides a common connection point for power or ground Complete System ti i t f Module Configuration Using the Hardware Configuration tool in the Productivity Suite programming software drag and dr...

Page 6: ... raw input signals to engineering units for use in the program or convert engineering units to output signals for control purposes max min min max 1045 0 8191 220 Level Transmitter Tank Level Non Linear Scaling Non Linear Scalin 0 5 1 1 55 2 25 3 4 55 6 75 7 0 0 0 0 0 0 0 0 1 2 3 4 5 6 6 5 7 0 0 0 0 0 0 0 Level Transmitter Tank Level 7 0 0 0 0 0 0 0 Select the minimum and maximum values of the raw...

Page 7: ...7 Sales 800 633 0405 www productivity1000 com ...

Page 8: ... determine which codes should be followed and to verify that the equipment installation and operation are in compliance with the latest revision of these codes Equipment damage or serious injury to personnel can result from the failure to follow all applicable codes and standards We do not guarantee the products described in this publication are suitable for your particular application nor do we a...