C2-02CPU Quick Start Guide 

Copyright© 2020, 

Automationdirect.com

 Incorporated/All Rights Reserved Worldwide

Safety Warnings

Please follow these instructions for personal and operational safety. 

WARNING

Assumes that incorrect handling may cause hazardous 
conditions, resulting in severe injury or death.

CAUTION

Assumes that incorrect handling may cause hazardous 
conditions, resulting in medium or slight injury, or 
may cause equipment damage.

WARNING

 

ƒ

Don’t use this equipment in a flammable or explosive 
environment in order to avoid accidental injury or fire.

 

ƒ

You should use external electromechanical devices that are 
independent of the PLC (Programmable Logic Controller) 
system to provide protection for any part of the system; 
otherwise malfunction or output failures may result in a 
hazardous accident.

 

ƒ

24VDC power is required from a secondary circuit or a specific 
power supply unit only.

 

ƒ

Ensure the Ground Terminal of the Power Supply (C0-00AC/
C0-01AC) for the CLICK PLUS CPU is connected to Earth 
Ground to avoid electric shock or equipment damage during a 
short circuit.

 

ƒ

Don’t operate the equipment with a nonconforming external 
power supply to avoid electric shock, equipment damage or fire.

 

ƒ

Don’t intentionally fault the wiring; this may cause equipment 
damage or fire.

 

ƒ

To avoid electric shock or malfunctions which might result in an 
accident, don’t touch any terminal while the PLC power is on.

 

ƒ

Don’t put metals (e.g. screwdriver) into vent holes, or drop trash 
or foreign objects (e.g. wire cut-offs) into the device, in order to 
avoid electric shock or equipment damage.

 

ƒ

If the equipment is used in a manner not specified by the 
manufacturer, the protection provided by the equipment may be 
invalidated.

CAUTION

 

ƒ

For use in Pollution Degree 2 Environment. Use and store the 
equipment in an environment described in the specifications 
(regarding temperature, humidity, vibrations, shock, etc.) in 
order to avoid equipment damage or fire.

 

ƒ

Ensure all wiring has strain reliefs in order to avoid damage to 
insulation that might result in electric shock or fire.

 

ƒ

Ensure secondary external power circuits are only live after PLC 
control program is started; otherwise a malfunction or output 
failure may result in a hazardous accident.

 

ƒ

Don’t block the vent holes. This may cause an increase of inter-
nal temperature resulting in equipment damage or fire.

 

ƒ

Don’t disassemble or modify equipment so as to avoid electric 
shock, equipment damage, or fire.

 

ƒ

Cut off all phases of the external power source before mainte-
nance work, thus avoiding electric shock or equipment damage.

Hardware Installation

ENCLOSURES

It is important to select the appropriate enclosure to ensure 
safe and proper operation of your CLICK PLUS PLC 
system. Please use this product in a metal enclosure/cabinet. 
Control applications vary and yours may require additional 
considerations. At a minimum your enclosure should include:

 

ƒ

Conformance to electrical standards

 

ƒ

Protection from the elements in an industrial environment

 

ƒ

Common ground reference

 

ƒ

Maintenance of specified ambient temperature

 

ƒ

Access to equipment

 

ƒ

Security or restricted access

 

ƒ

Sufficient space for proper installation and maintenance of 
equipment

CLEARANCES AND ORIENTATION

 

ƒ

Mount the unit horizontally to 
provide proper ventilation.

 

ƒ

There is a minimum clearance 
requirement of 2in. (51mm) 
from all sides of the cabinet and 
the equipment.

 

ƒ

There is a minimum clearance 
requirement of 1.5 in. (38mm) 
from the wiring ducts and the 
equipment

 

ƒ

Do not mount the unit upside down, on a horizontal surface, or 
in a vertical arrangement.

Minimum clearance requirement 

of 51mm for A, B, and C. 

Air

Flow

TX

2

PORT

2

PORT

1

RX

2

RX

1

TX

1

PWR

ER

R

RU

N

ST

OP

RU

N

Air

Flow

TX

2

PORT

2

PORT

1

RX

2

RX

1

TX

1

PWR

ER

R

RU

N

ST

OP

RU

N

Summary of Contents for CLICK PLUS C2-02CPU

Page 1: ...ICK PLUS CPU PC or Android or iOS mobile device for setup provisioning Click Software ver 3 00 or later PC or Click App mobile device 24VDC power supply SELV and Limited Energy CLICK power supply C0 00AC or C0 01AC is recommended Appropriate enclosure with vertical surface for DIN rail or surface mount M4 screws spring washers and flat washers if surface mounting Ferrules and crimping tool for wir...

Page 2: ...ent may be invalidated CAUTION For use in Pollution Degree 2 Environment Use and store the equipment in an environment described in the specifications regarding temperature humidity vibrations shock etc in order to avoid equipment damage or fire Ensure all wiring has strain reliefs in order to avoid damage to insulation that might result in electric shock or fire Ensure secondary external power ci...

Page 3: ...the 4 pin connector located on the bottom of the CPU unit 16 28 AWG wiring is supported We recommend using crimping ferrules on all wire terminations for a more secure connection The following crimping ferrules are recommend ed for the 24VDC power terminals Company Type Model No Compliant Wire AutomationDirect Ferrule V30AE000009 V30AE000041 0 2 0 5 mm2 22 26AWG Maximum tightening torque is 0 22 t...

Page 4: ...e module into its slot Press the module into place until it is fully seated 3 Push the top and bottom locking clips backward until they click into place Lift slightly on the locking clips until they release then slide each clip forward Reverse the procedure To install an Option Slot Module To install an Option Slot Module To remove an Option Slot Module To remove an Option Slot Module 3 Push the t...

Page 5: ...r SE ANT250 A remote mounted antenna is recommended to connect with the enclosure closed PREPARE A MOBILE DEVICE FOR CONNECTION Install the CLICK PLUS Provisioning App using one of the QR codes below or search for the app in the appropri ate app store CLICK PLUS Provisioning published by Automationdirect com FIND THE NEW CPU Connect to the CPU as follows 1 Open the CLICK PLUS Provisioning App 2 Ta...

Page 6: ... need to connect SET UP NETWORK PARAMETERS 9 Once the PLC is connected to the wireless access point or wired network choose which IP address configuration to use then tap Next to continue 9a Use DHCP Automatically assign a network IP address to the CLICK PLUS PLC This is often the simplest way to connect 9b Use Default Fixed Address Wireless 192 168 0 11 Wired 192 168 0 10 9c Use the following IP ...

Page 7: ...g No Error Off Blink WLAN LED Green On Link Activity No Link Off Blink POWER LED Green On Power Good USB Low Power Mode Power Failure Off Blink RUN LED Green On CPU Run Mode Initializing Analog Module CPU Program Mode Off Blink LED Status Indicators Connecting via USB To connect the CLICK PLUS CPU to a PC use a USB A to USB micro B cable such as the AutomationDirect USB CBL AMICB6 cable 1 Connect ...

Page 8: ...0 MC BAT recommended Technical Specifications Power Specifications Power Input Voltage Range 20 28 VDC Class 2 or SELV Safety Extra Low Voltage or Limited Energy Circuit power supply Maximum Power Consumption 20W Maximum Inrush Current 30A 1ms Acceptable External Power Drop Max 10ms AC Power Failure with C0 00AC or C0 01AC Wire Range 16 28 AWG Wire Strip Length 7 0 mm Wire Specification Lead free ...

Page 9: ...0 Automationdirect com Incorporated All Rights Reserved Worldwide Mechanical Drawings Unit Dimensions mm in BLUETOOTH PAIRING MODE SWITCH MICRO USB POWER TERMINAL BLOCK OPTIONAL MODULE SLOT ANTENNA STATUS LED s 101 8 4 01 85 0 3 35 46 6 1 83 46 4 1 83 FULLY EXTENDED OVERALL 53 5 2 11 60 8 2 39 32 3 1 27 126 8 4 99 PART NO SE ANT210 ...

Page 10: ...mmunications Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense The C2 02CPU complies with Part 15 247 modular Inten tional Radiator FCC rules and regulations Changes or mod ifications not expressly approved by AutomationDirect could void the user s authority to operate the...

Reviews: