1 Functions and features

The unit detects the system temperature in machines and  installations.

2 Function

The unit generates 2 output signals: 1 x NO + 1 x NC with separately adjustable 

switch points [SET1] and [SET2].

OUT1

With rising temperature OUT1 closes when the set value [SET1] is reached.
With falling temperature OUT1 opens, when the value [SET1] minus hysteresis 

is reached.

OUT2

With rising temperature OUT2 opens when the set value [SET2] is reached.
With falling temperature OUT2 closes, when the value [SET2] minus hysteresis 

is reached.

The hysteresis is fixed. It is 5 K.

• 

Measuring range: -25...140°C / -13...284°F.

• 

Measuring element: Pt 1000 according to DIN EN 60751, class B

3 Installation

Before mounting and removing the unit: ensure that no medium can leak 

at the process connection.

 

Insert the unit in a G½ NPT process connection.

 

Tighten firmly. Tightening torque: max. 25 Nm.

4 Electrical connection

The unit must be connected by a qualified electrician.

The national and international regulations for the installation of electrical 

equipment must be adhered to.

Operating voltage „supply class 2“ to cULus.

 

Disconnect power.

 

Connect the unit as indicated on the type label.