Chapter 1: Getting Started
Page 1–6
S
tride
®
MB Gateway User Manual
–
1st Edition Rev. E – August 2020
Installation, DIN Rail Mounting
NOTE: The gateway can also be panel mounted with purchase of accessory mounting bracket
(part #SE2-PM1 for SGW-MB1511-T and SGW-MB1512-T, part #SE2-PM3 for SGW-MB1524-T).
These devices are open-type and are meant to be installed in an enclosure which is only accessible
with the use of a tool and suitable for the environment when installed in Class 1, Division 2
Hazardous Locations. The gateway can be snapped onto a standard 35mm x 7.5 mm height DIN
rail (Standard: CENELEC EN50022) and can be mounted either vertically or horizontally. Allow
20mm [0.79”] of clearance between the gateway and other equipment on the DIN rail, side-to-side
and top-to-bottom.
DIN rail mounting steps:
1) Hook top back of unit over the DIN rail.
2) Push bottom back onto the DIN rail until it snaps into place.
DIN rail removal steps:
1) Push the unit down to free the bottom of the DIN rail.
2) Rotate the bottom of the unit away from the DIN rail.
3) Unhook top of unit from DIN rail.
Mounting
Removal